COLDWATER FIRE DEPT. FIRE SPRINKLER SYSTEM
PLAN SUBMITTAL
CHECKLIST [Property Address - ]
SHOWN
/NOT SHOWN
/INCORRECT
/ITEM
ADMINISTRATIVE
Permit Applied forContractor Information
Location of Installation
Owner of System
GENERAL INFORMATION
NFPA Edition
System Type (Wet, Dry, Pre-Action, Deluge)
Method of Alarm
Design Method (Room, Remote Area Density or Pipe Schedule)
PLANS & SPECS
Compass & Scale IndicatorDesigner Seal or NICET #
Ceiling Height & Cross Section & Construction
Rooms & Concealed Spaces Identified
Structure & Roof Information
Sprinkler Types & Numbers (SIN)
Temperature Ratings
High Temp Locations
Additional Area Design Hazards
PLANS & SPECS
Cont.Protection Areas per Riser(s)
Floor Plans & Locations of Walls, Draftstops
FDC & Ball Drip Valve Information & Hydrant Location
Hydraulic Data Plate
Number of Sprinklers on Each Riser
Sprinkler Spacing
Gallon Capacity (Dry)
<750 Gallons
Number of Sprinklers
Types
(Dry System)
Quick Opening Device
>500 Gallons
Location of Riser & ITV
Hanger / Support Detail
Hanger Locations & Spacing
Riser, Indicating Control Valve & Alarm Details
Hose Cabinets & Standpipes
Aux. Drainage
Main, Branch-line & Supply Main Sizing
Antifreeze System Details
Obstructions Addressed
Fire Pump Details
Pump Controller Alarm Details
Fire Pump Room Access
Elevation Details
HYDRAULIC DESIGN CALCULATIONS
SHOWN
/NOT SHOWN
/INCORRECT
/ITEM
WATER SUPPLY
INFORMATION
Flow LocationStatic Pressure
Residual Pressure
Design Flow GPM
Date of Flow Test
Time of Test
Person or Firm Conducting Test
Other Sources of Water Supply
Water Main Type Distance to Circulating Main (if Dead End)
Backflow – RPZ Detail
Backflow – RPZ Pressure Loss Factored
Sprinkler K Factor
Sprinkler Flow & Pressure
Acceptable Safety Margin
Pipe Sizes & Schedule Wall Thickness
Types of Fittings
Nominal Pipe Sizes
Hydraulic Reference Points
Density & Hazard Design
Total System Demand (Per Calc Area)
Water Supply Graph
WATER SUPPLY Cont.Summery Sheet
Fitting & Pipe Sheet
Plan Reviewed By: ______
Date Received: ______
Date Returned: ______
ACCEPTANCE TESTING CHECKLIST
PASSED
/FAILED
/ITEM
Hydrostatic Test
Main Drain TestAlarm Trip Test
Outside Alarm/Notification
DRY VALVE TRIP
Air Pressure
Time for Water
FIRE PUMP
Jockey PumpHydraulic Nameplate
FLOW______STATIC______RESIDUAL______
Acceptance Test Witnessed By: ______
Date of Test: ______
Pld/forms/sprinklerreview 04