US BANK
\
AUGUST 2014
Elevator QEI / Performance Inspection Report
PASSENGER ELEVATOR 2
US BANK
1310 MADRID STREET
MARSHALL, MN
By: ELEVATOR CONSULTING SERVICES, INC.
Equipment Inventory
Control Type: SELECTIVE COLLECTIVE
VMI
Contract Speed: 100 FPM – UP
100 FPM – DN
Machine Type: TWIN JACK BOREHOLE HYDRAULIC
PUMP UNIT
INSTALLED BY MEI
Door Equipment: GAL MOD
Door Size/Type: 44” WIDE X 7’ 0” HIGH
Number of Openings: TWO (2) / FRONT INLINE
Typical Floor Height: 13’ 4.5” - OH
17’11.5” – 1 TO 2
Floors Served: *1, 2
City/State Number: 07559
MN
Capacity: 3500 LBS
Emergency Light: OK
Alarm Bell: OK
Service Vendor: MEI
ITEMS IN RED ARE THE RESPONSIBILITY OF THE ELEVATOR CONTRACTOR
ITEMS IN BLUE ARE THE RESPONSIBILITY OF THE BUILDING OWNER
PERFORMANCE
Speed Up: 100 FPM
Speed Down: 100 FPM
Perform Up: 25.0 SEC
Perform Down: 21.1 SEC
Door Open: 4.3 SEC
Door Close: 4.8 SEC
Hall Call Dwell: 9.5 SEC
Car Call Dwell: 9.5 SEC
Nudging: 15 SEC
Door Torque: 10 LBS
Ride Quality
Ride: OK
Deceleration Up: OK
Deceleration Down: OK
Acceleration Up: OK
Acceleration Down: OK
Stop: OK
Leveling: OK
Equipment Room
Access: OK
Headroom: OK
Enclosure: OK
Lighting: OK
1-2 BULB FLORESCENT
Cleanliness: OK
Air Circulation,Ventilation: NONE
Pipes, Ducts, Non Elev: NONE
Parts: NONE
GFIC Receptacles: OK
Fire Extinguisher: OK
NEW 3-2014
Guarding: OK
Self Closing, Locking door: OK
Numbering of units: N/A
Sprinkler in room: NO
Lockable, Fused Disconnect: OK
60 AMP BREAKER
110 Volt Disconnect: YES
FUSED 20A
Shunt trip protection: NO
MSDS documentation: OIL / CLEANER NEEDED
Oil monitoring sheet: LAST ENTRY 2009
Signage on door: OK
Control Panel
Type of Control: MICROPROCESSOR
VCS1
Manufacturer: VMI
Installer: MEI ELEVATOR
Install Date: 2001
Install Code: ASME 17.1 1996
ASME 17.5-1996
Cleanliness: OK
Identification: OK
VMI JOB # 002337
Software Version: N/A
Guarding: OK
U. L. Label: CSA
Components-Controller
Relays: OK
Enclosure / Open Style: ENCLOSED/OPEN
Contacts: OK
Resistors: OK
P.C. Boards / Timers: OK
Wiring: OK
Performance: OK
Camera Wire: NO
Telephone: OK
Phone #: 507-532-3621
Starters
Type: WYE DELTA
Size: 3RT 1036 3A
Mfg: SIEMENS
Contacts: OK
Connections: OK
Operation: OK
Upstarts: NO DATA
Battery Rescuvator
Existing: NO
Model: N/A
Mfg: N/A
Labeled: N/A
Operational: N/A
Batteries: N/A
Wiring: N/A
Pump Unit
Mfg: MEI
Model: 5529
Cleanliness: OK
Leaks: OK
Noise: OK
Oil level: OK
Oil: OK
Belts: N/A
Sheaves: N/A
Pump: OK
187-IMO
Subs / Dry: SUB
Shut Off: OK
Valves: UC-4E2
Muffler: WILKES MCLEAN
75 LBS
Seals: OK
Covers: OK
Viscosity Control: NO
Acceptance Test: OK
Tagged: 2003
ANLT: PAST DUE
Tagged: 1-2012
Oil Coolers
Existing: NO
Mfg: N/A
Model: N/A
Hoses: N/A
Wiring: N/A
Leaks: N/A
Air Filter: N/A
Motor: N/A
HP: N/A
RPM: N/A
AMPS: N/A
Motor
Isolation: OK
Grounded: OK
Covers: OK
HP: 25
RPM: 3440
AMPS: 70/35
Frame: 160ZBS
Starts/Hr: 80
Hoistway
Governor
Mfg: N/A
Type: N/A
Reset: N/A
Access Panel: N/A
Pull Through: N/A
Running Speed: N/A
Overspeed Switch: N/A
Trip speed: N/A
Tagged: N/A
Selector Car Top Device
Cleanliness: OK
Magnets: OK
Tape: OK
Tape Guides: OK
Limit Switches
Noise, Rollers: OK
Operation: OK
Type: OMRON
Rails
Cleanliness: OK
Lubrication: OK
Type: T / 15 LBS
Fastening: OK
Guide Shoes: OK
ELPRO / 81685
Cable Condition
Traveling: OK
TC Suspension: OK
Piston Traveler: N/A
TC Spares: OK
Hoist Cables: N /A
Cable Ties: N/A
Shackles: N/A
Hoistway Equipment
Car Top
Cleanliness: OK
Maintenance Station: OK
ADAMS
Stop Switch: OK
Data Plate: OK
Light: OK
Light Guards: OK
Slide Guides: OK
GFIC Recept: OK
Escape door locked: OK
Windows in Hoistway: NONE
Multiple Hoistways: N/A
Stenciled: N/A
Hoistway Venting
Existing: NO
Motorized: N/A
Key Switch: N/A
Size (3%): N/A
Door Operator / GAL-MOD
Cleanliness: OK
Door Protection: SAFETY EDGE & PHOTO EYE
Lubrication: OK
Belts: OK
Chains: OK
Hangers: OK
Arms: OK
Bearing: OK
Noise: OK
Tracks: OK
Upthrusts: OK
Restrictor: OK
LWZ
Gibs: OK
Car Enclosure
Ventilation: OK
MULTI SPEED FAN
Walls: LAMINATE ALL WALLS INCLUDING
FRONT
Car Lighting: OK
2 FLORESCENT
Ceiling: OK
SUSPENDED WITH MILK PLASTIC PANELS
Position Indicators: OK
DIGITAL
Handrails/Bumpers: 1 TIER
2” BARSTOCK AT 32” REAR WALL
Flooring: CARPET
Car Doors: SS #4
Sills: ALUMINUM
Certificate: NO
Entrance Equipment
Cleanliness: OK
Lubrication: OK
Tracks: OK
Hangers: OK
Gibs: OK
Clutch Release Roller: OK
Interlocks: OK
GAL
Noise: OK
Upthrust: OK
Closers: OK
Braille: OK
Star of Life: NO
ID Tactile: NO
Emergency Fire Box
Main Egress Landing: 1ST LEVEL
Existing in lobby: YES
Machine room key: YES
Phase I, II keys: ONE
Lunar key: YES
Tagged: YES
Car Operating Panel
Type: ADAMS
SURVIVOR SERIES
Height Compliance: OK
Braille Identification: OK
Buttons: OK
Phone: PUSH TO TALK
Callback #:
Alarm Button: OK
Stop Switch: KEYED
Emergency Light: OK
Capacity Plate / Engraved: OK
Certificated: NO
Fire Service – Surface Mounted
Fire Fighters Instr: OK
Phase II key sw: YES
OFF/HOLD/ON
Call Cancel: OK
Fire Hat: OK
Door Open: OK
Door Close: OK
Stop Button: KEYED
Certificated: NO
Service Panel
Light Key Sw: YES
KEYED
Fan Key Sw: YES
KEYED
Independent Serv Key Sw: NO
Access Enable Key Sw: NONE
Light Dimmer: NO
GFI Recp: NO
Emergencey Light test button: NO
Hall Buttons:
Type: ADAMS
SURVIVOR SERIES
Illuminated: OK
Height: OK
Mechanical: OK
Lanterns: OK (CDI)
Fire Signage: 5” X 8” SIGN 1ST FLOOR
Phase I key switch: YES
BYPASS/OFF/ON
Phase I instructions: ENGRAVED
Phone Jack: NO
Pit Equipment
Cleanliness: OK
Car Buffer: OK
Cwt Buffer: N/A
Lights: OK
Light Switch: OK
Light Guards: OK
Stop Switch: OK
Ladder: OK
GFIC Recept: OK
Jack Seals: OK
PVC Liner: OK
Shut Offs: OK
Piston Pans: N/A
Pit Buckets: OK
Rupture Valves: NO
Tension Sheave: N/A
Rope Dead End Hitch (left): N/A
Rope Dead End Hitch (right): N/A
Dead End Switch (left): N/A
Dead End Switch (right): N/A
Bottom of Car
Cleanliness: OK
Safeties: N/A
Trav cable suspension: OK
Toe guard length: OK
21”
Isolation: OK
Light Fixture: OK
Light Guard: OK
Slide Guides: OK
Receptacle: OK
GFI Receptacle: OK
US BANK
MARSHALL, MN
PASSENGER ELEVATOR 2
CORRECTIVE ITEMS
The following minimum items need corrective action taken. Documentation of completion is required.
STATE ID – 07559 Accep. Test – 2003 ANLT – 10-2013 - DUE
1. Provide and install a Group II security key box in the machine room. Includes providing a key for all access items for the elevator. Includes access, lunar key, fire service, fan, light, inspection, etc. Properly label each. (Inspector’s key box).
Completion Date______Initial_____
2. Perform the annual no load test per ASME 17.1 code. Properly tag the unit.
Completion Date______Initial_____
3. Provide a MCP tasking log, oil monitoring sheet, call back log, repair log and fire service testing log, in the machine room per ASME 17.1 Section 8.7. Documentation is required and enforced.
Completion Date______Initial_____
US BANK
MARSHALL, MN
PASSENGER ELEVATOR 2
RECOMMENDATIONS
1. Provide the separate black trimmed key box in the machine room labeled “ Elevator Personnel Only”. Provide the appropriate keys identified in ASME 17.1 Section 8.1 for the Group 1 / Restricted, Group 2 / Authorized Personnel and Group 3 / Emergency Operation including but not limited to access, access doors, hoistway unlocking devices, inspection switches, stop switches, etc. Budget $350.00
2. Upgrade the existing door protection to an infra-red scanner assembly. Will improve reliability, safety to pedestrian users. Budget $ 2,100.00
NI – NEEDS IMPROVEMENT 21 PASSENGER ELEVATOR 2
OK - SATISFACTORY AUGUST 2014 QEI / PERFORMANCE REVIEW