1.1.1.All Work Shall Be in Conformance to the Latest Revision of Régie Du Bâtiment Du Québec

1.1.1.All Work Shall Be in Conformance to the Latest Revision of Régie Du Bâtiment Du Québec

PROJECT TITLEAir SeparatorSection 15516

Page 1

Project No: SEP17-Nov-2010

  1. PART 1 – GENERAL
  2. References

1.1.1.All work shall be in conformance to the latest revision of « Régie du bâtiment du Québec - Chapter 1 », unless otherwise indicated.

1.1.2.All work shall conform to the latest revised codes and standards that having jurisdiction, including but not limited to :

1.1.2.1.ANSI / ASME B16.1, Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 and 800.

1.1.2.2.ANSI / ASME, Section VIII, Boiler and Pressure Vessel Code (BPVC).

1.1.2.3.ASTM A47M, Specification for Ferritic Malleable Iron Castings.

1.1.2.4.ASTM A278M, Specification for Gray Iron Castings for Pressure-Containing Parts for Temperatures up to 345°C.

1.1.2.5.ASTM A516 / 516M, Specification for Pressure Vessel Plates, Carbon Steel, for Moderate and Lower Temperature Service.

1.1.2.6.ASTM A536, Specification for Ductile Iron Castings.

1.1.2.7.ASTM B62, Specification for Composition Bronze or Ounce Metal Castings.

1.1.2.8.ASTM E202, Test Method for Analysis of Ethylene Glycols and Propylene Glycols.

1.1.2.9.CSA B51, Code des chaudières, appareils et tuyauteries sous pression.

1.2.Submittals

1.2.1.Submit dimensional drawings and technical data in conformance with client’s instructions.

1.3.Instruction and Maintenance Manual

1.3.1.Submit manufacturer’s installation and start-up instructions, and incorporate them into the operation & maintenance manual.

1.3.2.The maintenance manual will comprise of or indicate the following:

1.3.2.1.A description of the major components: the manufacturer’s series or model reference number, power rating, flow and pressure;

1.3.2.2.All details relating to the operation, care and maintenance of component;

1.3.2.3.A list of equivalent component replacements.

  1. PART 2 – PRODUCTS
  2. Air purge

3.

2.1.1.The Contractor shall provide and install, as indicated on plans and specifications, one or more air purge in compact line.

2.1.2.The design and fabrication will conform to ASME Section VIII Division 1 and CSA B51 relating to pressure vessels used at 150 psi (1034 kPa) and 550 ° F (288 ° C) maximum.

2.1.3.The inlet and outlet of each vessel will be equipped with an aperture of [____] inch ([____] mm) [Flanged].

2.1.4.The vessels will be equipped with separated superior NPT connector(s) for evacuation of air and lower connector(s) for other connections, such as components of pressure control (CPC).

2.1.5.Acceptable Products: Flo Fab series SEP (Suffix F flange) (suffix G for Grooved) (Suffix L with mounting brackets) and / or (Suffix F-4 stainless steel screen 304) (Suffix F-6 stainless steel screen 316).

3.PARTIE 3 – EXECUTION

3.1.General

3.1.1.Install the tank and associated parts in accordance with installation diagram of the pipe and as recommended by the manufacturer. Connect the vent fittings and bleed.

3.1.2.Provide adequate clearance to allow access to equipment for maintenance. If the final location would be different than the drawings, consult the owner before proceeding with the installation.

3.1.3.If eligible clearances cannot be met, consult the owner and comply with its directives.

3.1.4.Refer to installation drawings supplied by the manufacturer.

3.1.5.Check and adjust the pressure before starting the system, it must correspond to the minimum pressure of the system. (Filling pressure).

3.1.6.Make sure all the holes used to connect accessories and appliances, and the mass of the equipment operating status are consistent with indications of shop drawings.

3.1.7.If the items and related accessories are delivered in parts, check assemblymethod with the manufacturer.

End of section

60120 - 15463 - Domestic water heater RLU