PART 2- PRODUCTS – MATERIALS

2.1 SPECIAL WASTE PIPE AND FITTINGS (Under Slab)

A.  Polypropylene Pipe Schedule 40 joined by the coil fusion method. Pipe shall be manufactured of

non-flame retardant homopolymer polypropylene ( in buried applications where long piping runs may be effected by live loads above, Schedule 80 non-flame retardant copolymer pipe shall be used).

B. Polypropylene fittings shall be manufactured to Schedule 40 dimensions. Fittings shall be joined to the polypropylene pipe by means of coil fusion method.

C. All components of the system shall conform to the following applicable ASTM Standards, D4101, D3311, D1599, D2122, F1290 and F1412. All pipe shall be marked with manufacturers

name, pipe size, schedule, type, quality control mark and ASTM information. All fittings shall be legibly marked showing manufacturers trademark, fitting size, manufacturers

part number, and symbol indicating the material.

D. Shall be Fuseal pipe and fittings as manufactured by GF Piping Systems LLC Irvine CA, or approved equal.

2.2 Special Waste Pipe and Fittings (Above Slab Only)

A. Polypropylene Pipe Schedule 40 joined by the coil

fusion method. Pipe shall be manufactured of flame

retardant homopolymer polypropylene. Flammability

requirements are based on ASTM D635 “Standard Test

Method for Rate of Burning and/or Extent and Time of

Burning of Self Supporting Plastics in a Horizontal

Position”

B. Flame Retardant Polypropylene fittings shall be

manufactured to Schedule 40 dimensions. Fittings shall

be joined to the polypropylene pipe by means of coil

fusion method. Fittings shall meet the same flammability

requirements as described for pipe above.

C. All components of the system shall conform to the following

applicable ASTM Standards, D4101, D3311, D1599, D2122,

F1290 and F1412. All pipe shall be marked with manufacturers

name, pipe size, schedule, type, quality control mark and

ASTM information. All fittings shall be legibly marked

showing manufacturers trademark, fitting size, manufacturers

part number, and symbol indicating the material.

D. Shall be Fuseal pipe and fittings as manufactured by

GF Piping Systems LLC, Irvine CA or approved equal.

2.3 Special Waste Pipe and Fittings Above Grade (Plenum Ceilings/High Temperature Discharge)

A. Polyvinylidene (PVDF) Pipe Schedule 40 joined by the coil

Fusion method. Pipe shall be manufactured of flame

retardant PVDF for service in plenum rated areas or

high temperature (to 280 degrees) flow stream.

Flammability requirements are based on ASTM D635 “Standard Test

Method for Rate of Burning and/or Extent and Time of Burning of Self

Supporting Plastics in a Horizontal Position”. The pipe must also meet or exceed ASTM E84 25/50 (UL 723) and UL 94-VO.

B. Flame Retardant Polyvinylidene (PVDF) fittings shall be

manufactured to Schedule 40 dimensions. Fittings shall

be joined to the PVDF pipe by means of coil

fusion method. Fittings shall meet the same flammability

requirements as described for pipe above.

C. All components of the system shall conform to the following

applicable standards, ASTM E-84 25/50 (UL 723) and

UL 94-VO.

All pipe shall be marked with manufacturers name,

schedule, pipe size, ASTM-F1673, E-84, UPC, UL

Classified date stamp and “Made In USA”.

All fittings shall be legibly marked showing manufacturers

trademark, fitting size, manufacturers part number,

symbol indicating the material, ASTM F1673, UPC, USA.

D. Shall be Fuseal 25/50 pipe and fittings as manufactured by

GF Piping Systems LLC, Irvine CA or approved equal.

2.4 Special Waste Pipe and Fittings Above Slab (Under Bench)

A. Polypropylene Pipe Schedule 40 joined by the mechanical

joint method. Pipe shall be manufactured of flame

retardant homopolymer polypropylene. Flammability

requirements are based on ASTM D635 “Standard Test

Method for Rate of Burning and/or Extent and Time of

Burning of Self Supporting Plastics in a Horizontal

Position”

B. Flame Retardant Polypropylene fittings shall be

manufactured to Schedule 40 dimensions. Fittings shall

be joined to the polypropylene pipe by means of mechanical

joint connection. Fittings shall meet the same flammability

requirements as described for pipe above.

C. All components of the system shall conform to the following

applicable ASTM Standards, D4101, D3311, D1599, D2122,

F1290 and F1412. All pipe shall be marked with manufacturers

name, pipe size, schedule, type, quality control mark and

ASTM information. All fittings shall be legibly marked

showing manufacturers trademark, fitting size, manufacturers

part number, and symbol indicating the material.

D. Shall be Fuseal MJ fittings as manufactured by

GF Piping Systems LLC, Irvine CA or approved

equal.

Part 3 Execution

3.1  Installation

A. Pipe and fittings shall be installed according to current

installation instructions as delivered in print or documented online at

www.gfpiping.com . An on site installation seminar

shall be conducted by GF personnel who are certified to

conduct said seminar. Seminar topics

shall include all aspects of product installation ( storage, set up,

support spacing, fusion process, mechanical joint process,

testing procedure, etc.). At the conclusion of the

installation seminar, all installers will be given a certification

test and, upon successful completion of said test, will be

issued a certification card verifying that they have met

the requirements of the manufacturer with regards to knowledge

of proper product installation and testing methods.

B. Only the GF Piping Systems LLC fusion units MSA-250 SE or “Electro Plus”

may be used in the installation of the Fuseal and Fuseal 25/50 piping

systems. Under this specification, the contractor shall be responsible

for purchasing either one MSA-250 SE or one “Electro Plus” fusion unit

for use in installation of the product on site. At the completion of the

installation and testing of the piping system, the contractor shall turn over

the fusion unit to facility personnel for their use in future system

upgrades, layout changes, etc.

C. Installer shall ensure that all pipe and fittings used for the

special waste piping system are components of the same

system. No mixing of various manufacturers pipe and or

fittings shall be allowed. Acceptable manufacturers are

GF Piping Systems LLC or approved equal.

3.2  Testing

A. The system shall be tested in accordance with all local

plumbing codes. All sections of the piping system shall be

tested with a maximum of 30 foot head of water (approx.

15 PSI ) for fusion system. Under no circumstances

should the system be tested with air or any other gas.

Joints may be pressure tested 10 minutes after fusion is

completed. (Mechanical joints shall be tested to a minimum

10 foot head or 5 PSI). Fuseal PP and PVDF pipe and fitting systems

may be installed for conveyance of pumped discharge up to 50 psi, consult

your local GF representative for more information.