XMT-3000 / Manual ofIntelligent Model
Digital DisplayTemperature Controller

1. Confirmation of the Instrument

This product is suitable for using to control temperature in the equipments of the industries of injection molding,extrusion,bottleblowing,foodstuff, package, printing,constant temperature drying, metal heat treating and etc. This product is an intelligent instrument whose PID parameters can be auto-tuning, and then its employing method is very convenient. So this product is an optimumrenewal instrument to replace the older generation of thepointer electronic controller and analog digital temperature controller. This productmeets the requirements stipulated by the industrial standard of Q/SQG01-1999 for the intelligent digital display instrument. ,

Pleaseaccording to the following codesto affirm whether or not that your product received is in full agreement with the model that you selected:

XMT□-□□□□ □ □ □—□ □

①②③④⑤⑥⑦⑧ ⑨⑩

①Size of the Instrument Surface(mm)

D:96×96

E:72×72

F: 96×48(Vertical Type)

F(H):48×96(Horizontal Type)

G:48×48

②Display Type:

3:Dual-Rows Display (Economical Model)

③Control Type

4: On-Off PID Control

9:Continuous PID Control

④Alarm Output 1

0: Without Alarm

1: Upper LimitDeviation Alarm

2: Lower Limit Deviation Alarm

3: Upper and Lower Limit Deviation Alarm (Withhold)

4: Upper LimitAbsolute Value Alarm

5: Lower Limit Absolute Value Alarm

⑤Alarm Output 2

0: Without Alarm

1: Upper LimitDeviation Alarm

⑥Output Type

Empty: Relay (Maximum 3A)

V: Logical Level Output Used for SSR

I1: 0~10mA Continuous Current

I2: 4~20mA Continuous Current

⑦Input Type:K(0-700),J(0-550),E(0-400),PT100(0-500),PT100(0.0-99.9),CU50(0.0-99.9)

⑧Lower Limit of Measurement Range

⑨Upper Limit of Measurement Range

⑩ AttachedControl

Empty: Without ON/OFF Control

ON/OFF: With ON/OFF Control

2. Mounting of the Instrument

2.1 Matters Needing Attention

(1) Instrument needs to install in following environment:

(2)Atmospheric Pressure:8~106kPa

Environment Temperature:0~50℃

Relative Humidity:45~85%RH

(3)During installation, the following items should be paid attentionto:

Rapid change of environment temperature may cause dew

Certain corrosive and inflammable gases

Directshake or impact acting on themain structure of the instrument

Water,oil,chimerical articles,smoke fog orvaporpollution.

Too muchdust, salt or metalpowder

Direct blowing by air-conditioning or directprojection by sunlight

Accumulating place of heatradiation

2.2Mounting Process

(1)According to the needed hole size for install,cut out the rectangle holeson the panel for mounting the instruments.

(2)When installingthe instruments more than one, the distance between two edges of the holes should be largerthan 25mm in horizontal direction and than30mm in vertical direction.

(3)Insert the instrument into the hole on the panel.

(4)Insert mounting holder in the slot for mounting the instruments.

(5)Push tightly the mounting holder to connect the instrument and the panelfirmly.

2.3 Size

Unit mm :See the Picture in Right

Side

3 Wiring

3.1 Noticesof Wiring

(1)For thermocouple input, thecompensate line corresponding to the type of the thermocouple is needed to usage

(2)For thermo-resistance input, the three conducting wires with identical and low electric resistance and identical length for connecting the thermo-resistance are needed.

(3)The input signal line should be mounted separated from the instrument’spower line, power supply line and load line for avoidingleading-in the electromagnetisminterference.

3.2 The Terminals of Wiring

4.Configuration of the Instrument Surface

①Measurement Value(PV)Indicator(Red)

 Display the Measurement Value

 According to the instrument state,a variety of prompt symbol are displayed.

② Set point Value(SV)Indicator(Green)

 Display Set point Value

 According to the instrument state,a variety of parameters are displayed.

③ Indicators

 Control output indicator(OUT)(Green): Bright at operation

 Auto-tuning indicator(AT)(Yellow):Twinkle at operation

Alarm output 1(ALM1)( Red): Bright at operation

Alarm output 2(ALM2)(Red): Bright at operation

④FUNCTION KEY:SET

 This key isused to take out the parameters, update parameters anditsaffirming.

⑤SHIFT KEY:

This key is used toselectthe place of the parameter and the On/Off state of the control output in the light of requirements of user.

⑥DIGITAL ADJUSTING KEY:▲ and▼

 Used to adjust the digits and Start/Quit of the Auto-tuning state

5. Operation

5.1Sequence of the variety of functions

Display of Input Type:

Display of Input Range: After about 4 seconds of display,the automatic conversationaccomplished

Standard Display Mode: Automatically returning if not press Key about 1 minute

Press the Function KeyMode of Updating and Setting:

Press the Function Key more than 4 seconds Updating Control Parameter

5.2Thedetailedexplanation of the functions

After the instrument is power on, the upper row displays Inp and the lower row displays the calibration mark of the temperature sensor. Passing through 2 seconds, the upper row displays the upper limit of the measurement range and the lower row displays the lower limit of the measurement range. After 2 seconds again, the upper row displays the Measurement Value and the lower row displays the Set Point Value then the system comes into its normal operation state.

Set the temperature value: Press the SET key, the upper row displays SP value. Press the SHIFT KEY to make the digital place that is needed to be updatedto be twinkle. Pressor KEY,the lower row displays its needed value. Press SET KEY, system return to its standard model state.

The Control Parameters’ Setting: Pressing the SET KEY above 4 seconds, the upper row displays the prompt symbol of the control parameter (Detailed can see the list table for the control parameters). Press the SHIFT KEY to make the digital place that is needed to be updated to be twinkle. PressorKEY the lower Row displays the needed value of the parameter. Carrying on pressing the SET KEY, the upper row displays the parameter’s symbolin turn and pressing the SHIFT KEY to make the place needed tobe updated twinkle then press orKEY to make the control parameter equal to its needed value. Again pressing the SET KEY more than 4 seconds, system returns to its standard model state.

 If the lower part of the display window of PV value appears in , it illustrates that the thermocouple is connected in reverse or the thermo-resistance is in short circuit state or the measured temperature exceeded its measurement range. If the upper part of thedisplay window of PV value appears in , it illustrates that the thermocouple was in open circuit state or the measured temperature exceeded its measurement range.

 The Auto-tuning Function for the instrument control parameters: After pressing orKEY more than 4seconds, the AT indicator twinkle, the controller starts its Auto-Tuning process. After the temperature displayed passing through 1~2 times of wave propagation, Auto-tuning ended and the AT indicator turn off,and then the system obtains a new set of PID parameters and the instrument can operate according to this new set of PID parameters and this set of PID parameters would save automatically in the controller.

]

AT Start AT End time

On/Off Control: When the instrument has provided the function of ON/OFF, under thePV/SV display state,if pressing the KEY more than 4 seconds, the control output andindication stop, the SV window display OFF. Again press KEY more than 4seconds, the normal control output isrestored

unction parameter can be seen in following table:

Prompt Symbol / name / Setting
Range / Illustration / Beginning Value
/ Setting of Alarm1 / 0…Range
℃ / Setting of Alarm1,
Insensitive interval of alarm
is equal to a constant value 0.4 / 50 or 50.0
AL1
/ Setting of Alarm 2 / 0…Range
℃ / Setting of Alarm 2,
Insensitive interval of alarm
is equal to a constant value 0.4 / 50 or50.0
AL2
/ Proportion
-al band
(Heating
Side) / 0…300
℃ / Proportional Control: The more the value of P, the lessthe proportional action and the less the system gain; only acting on the heating side. (P=0 is ON/OFF Control) / 30or 30.0
P
/ Integral Time / 0…999
Seconds / Integral Time: The more the value of I, the less the Integral action
I=0 is PD Control,Ar=(Remained Error/P)×100 / 240
I
/ Differential Time / 0…999
seconds / Differential time: The more the
Value of D, the more the
differential action, which is able to to overcome overshoot
(D=0 is PI Control) / 60
d
/ Overshoot restrain
Proportion re-setting
Insensitive i
interval of
ON/OFF Control / 0~100% / Used to restrain Overshoot
(Ar is setto 1.5~2 times of the output empty ratio in the steady state of the system) / 100
Ar
/ Control period
(Heating Side) / 1…100
Seconds / When the relay output≮20s,
SSR and
Si-controlled switch transwitch≮2s,continuous output T is equal to
1s, only acting on heating side / 20
T
/ Offset of the Process Value / -10(-10.0)~
10(10.0)℃ / Using for correct the
measurement error caused by the sensor and the compensate line of the thermocouple / 0or0.0
Pb
/ coded lock / 000,001,002 / 000:All parameters can be updated
001:Only the Set PointValue can be updated
002:All parameters cannot be updated. / 000
LCK

Notice:Change of each function parameter in the table may alter the control effectof the system.

5.3 Illustration and sketch map of the alarm

Code / Alarm Form / The following two sets of Alarm(ALM1、ALM2)are independent with each other
Alarm1(ALM1)Output / Alarm 2(ALM2)Output
1 / Upper LimitDeviation Alarm /
SP AL1 PV / SP AL2 PV
2 / Lower LimitDeviation Alarm / AL1
SP PV
3 / Upper/Lower LimitDeviation Alarm(With Hold) / AL1 AL1
PV SP PV
4 / Upper LimitAbsolute Value Alarm /
AL1 PV
5 / Lower LimitAbsolute Value Alarm /
AL1 PV

6. Maintain and Conservation of the Instrument

 In theeighteen months aftermaking out the invoice, our company is in charge of the guarantee to keep the instrument in good and general repair. For the damage caused by not properly usage by users, our company will charge the repair costappropriately. The Instruments manufactured by our company will be obtained maintenance in all the instruments’ life.

 The instrument ought to save in the place which is drying and non corrosive gas.

 If the instrument wiring in manual is not agree with that one which is labeling on the instrument surface, should take the wiring diagram labeled on the instrument surface as the accurate one.