This document will be used to specify the general features of Variable Speed Drives with a power from 0,18kW to 4kW and a voltage supply from 120V (single phase) to 240V (single phase or three phases). The document is to be used together with the Project-Specific Specification for Variable Speed Drives. All quotations from vendors have to be based on these documents. Any deviations have to be listed and supplied together with the quotation.

This specification defines:

1. General requirements 2

2. Applicable standards 2

3. Specific requirements 3

4. Operation 4

5. Maintenance 5

6. Sustainable development 6

7. Quality 6

1

Spec_ATV12_V1.doc

SUMMARY

1. General requirements 2

2. Applicable standards 2

3. Specific requirements 3

3.1. Protection 3

3.2. Commissioning 3

3.3. Control and power connections 3

3.4. Integration on a solution offer 4

3.5. Software 4

4. Operation 4

4.1. Ratings 4

4.2. Environmental ratings 4

4.3. Size 5

5. Maintenance 5

5.1. Built-in 5

5.2. Manufacturer 5

5.3. Local support 5

5.4. Warranty and after sales 5

6. Sustainable development 6

7. Quality 6

5

Last update: 2009-06-29

Spec_ATV12_V1.doc

1.  General requirements

This section provides general requirements for pulse-width modulated (PWM) adjustable frequency drives, herein referred to as AC Drives, for use with NEMA design AC motors, or standard IEC motors.

The AC drive shall provide a power from 0,18kW to 4 kW and a voltage supply from 120V (single phase) to 240V (single phase or three phases).

The AC drive is a system for controlling the rotational speed of an AC motor and providing on demand the right torque for a simple application in industry or residential areas.

To avoid any mismatch between the motor and its control equipment, the AC drive shall be capable of auto adjustment by automatic measurement of the motor parameters without motor rotation.

The AC drive shall be noiselessly (< 50dba). There is a fan management for the AC drive above 0,75kW. Until 0,75kW, the AC drive doesn’t need a fan.

The AC drive shall provide a braking torque up to 70% of the nominal torque without resistor and up to 150% of the nominal motor torque with an optional braking unit at high inertia.

2.  Applicable standards

The AC drive is qualified to address all the major standards in order to be worldwide commercialized.

The AC drives shall be:

¨  CE marked, conforming to European Low Voltage (2006/95/EC modified from 73/23/EEC and 93/68/EEC and EMC (2004/108/EC modified from 89/336/EEC) Directives, and Machinery directive N0 98/37/EC modified by 98/79/EC,

¨  UL marked according to UL 508C,

¨  CSA marked according to CSA 22.2 N14-05,

¨  C-Tick marked to comply with Australasian Communication Authorities,

¨  NOM marked (Mexican area),

¨  GOST marked (Baltic and Russian area).

Moreover it shall comply with National and International standards and the recommendations for electrical industrial control devices (IEC, EN, UL, NFC and VDE). Major standards of IEC are listed below:

Standard / Title
IEC 61800-3
IEC 61800-5-1 / Semiconductor power converters for adjustable frequency drive systems environments 1 and 2.
Adjustable speed electrical power drive systems safety requirements – Electrical, thermal and energy.
IEC 60068-2-3
IEC 60068-2-6
IEC 60068-2-27 / Environmental testing; Part 2-3: Tests - Test Ca: Damp heat, steady state
Part 2-6: Tests - Test Fc: Vibration (sinusoidal)
Part 2-27: Tests - Test Ea and guidance: Shock
IEC 60529 / Degrees of protection provided by enclosures (IP Code)

3.  Specific requirements

3.1.  Protection

The AC drive must have fault detection against the risks of equipment destruction from component’s failures. The AC drive shall:

¨  be protected against short-circuits between motor and phases;

¨  be protected against the over current between motor phases and earth;

¨  have a thermal protection against overheating;

¨  have an input phase loss protection, in three-phases;

¨  be protected in the event of line over voltage and under voltage;

¨  have a thermal protection integrated in the drive;

¨  be IP20;

¨  have coated cards in order to fight the pollution (IEC 60721-3-3 classes 3C3 and 2S2).

3.2.  Commissioning

The AC drive must be “plug & play”. For simple applications, the factory settings are enough to get a quick start (a quick start sheet is delivered with the product).

The navigation of the AC drive is done by the jog dial. The START; STOP/RESET buttons on face allow to have a local control.

The AC drive can be configured power OFF in his box thanks to a loader toll. This possibility allows saving time: the user can configure 10 drives power OFF during 5 minutes.

The AC drive shall be compatible with friendly PC software which allows the user to configure the drive and to store configurations. This PC software must have the oscilloscope function which facilitates the diagnostics. The PC software allows selecting the number of the parameters that the user wants (by selecting the box ‘YES’ or ‘NOT’ on the screen of the software).

The AC drive allows the configuration with a cell phone throughout Bluetooth. The user will find the application for his cell phone on a website. He can download it free of charge.

3.3.  Control and power connections

The control voltage for the digital inputs and outputs shall be 24Vdc.The input logic type source (positive logic) or sink (negative logic) can be configured.

The internal power supply shall incorporate automatic current feedback that protects the internal power supply against wrong connections or short-circuits. The transistor logic outputs will be current limited and will not be damaged if short-circuit occurred.

One relay output contact will be provided. The relay will indicate AC drive fault status or no line voltage present (NO - NF relay).

The power terminals of the AC drive are compatible with the ring terminals.

The analog inputs have an accuracy of +/-1% at 25 °C.

The logic inputs have an update time lower than 20 ms (with a precision of +/- 1ms).

3.4.  Integration on a solution offer

The AC drive must have the possibility to be integrated on automatism solution. The AC drive shall have an integrated RJ45 port for Modbus as a standard product.

3.5.  Software

The AC drive shall offer a simple menu divided in 3 modes in order to find a parameter easily:

¨  “Reference” ,

¨  “Monitoring” ,

¨  “Configuration” with 2 parts (“My Menu” and “FULL Menu”)

The AC drive shall provide 3 motors control laws:

¨  “Standard” (based on the U/f law) which allows to have a smooth and a quick start for all types of motors,

¨  “Performance” (based on SVC law) which allows a TUN and is compatible with the different type of motors,

¨  “Pump & fan” which allows saving energy.

The AC drive shall offer a personalized menu (named “MyMenu”). The user can customize the AC drive thanks to PC software. The user can choose 25 parameters to personalize his menu.

4.  Operation

4.1.  Ratings

Voltage / Phases / Power rating
100 -15% to 120 +10% / Single phase / 0.18 to 0.75 kW
200 -15% to 240 +10% / Single phase / 0.18 to 2.2 kW
200 -15% to 240 +10% / Three phase / 0.18 to 4 kW

The AC drive shall operate from an input frequency range of 50Hz -5% to 60Hz +5%.

The requested AC drive maximum transient current is 150% of the nominal drive current for one minute.

4.2.  Environmental ratings

Operating ambient temperature / -10°C to +40°C without derating
Up to 60% with a derating
Storage ambient temperature / -25°C up to 70°C
Maximum operating altitude / 1000m to 2000m for single phase networks with a current derating of 1% per additional 100m
1000m to 3000m for three phase networks with a current derating of 1% per additional 100m
Maximum relative humidity / 5 to 95% without condensation and dripping water

The AC drive shall be able to give 100% output current continuously in the above specified conditions. The derating factor must not have an impact on the lifetime of the AC drive, the unit’s performance, overload capability included and the reliability of the AC drive.

EMC filter class C1 is integrated with the 200-240V single phase drives. The user can disconnect the EMC filter thanks to an IT jumper.

EMC filter class C1 must be embedded for the 100-110V single phase and 200-240V three phase drives.

4.3.  Size

The AC drive shall be the very compact. Until 0,75 kW, the AC drive must have dimensions below 72 cm for the width, 130 cm for the height and 131,2 cm for the depth.

5.  Maintenance

5.1.  Built-in

The AC drive shall provide maintenance information like the running time of the fan.

Maintenance and monitoring tools such as fault history are built-in the drive and used for trouble shooting.

The AC drive shall provide an easy maintenance of the fan. Up to 0,75 kW the drive is fan less. Above 0,75kW, you can replace the fan.

5.2.  Manufacturer

The AC drive manufacturer must have a minimum of 40 years experience in world-class drive design and manufacturing. The installed base product quantity must be large enough to be credible in its capacity to be an edge company continuously enhancing its product management process.

5.3.  Local support

On the major countries, the supplier shall have a permanent representative office with a trained and skilled support staff, in the country where the goods are delivered. The support team must be able to attend to site problems on site within 24 to 48 hours with fair notice from customer.

5.4.  Warranty and after sales

A factory test report shall be delivered by the AC drive manufacturer on request.

A 24 month parts warranty shall be provided on materials and workmanship from the date delivery.

6.  Sustainable development

The manufacturer of the AC drive shall be a qualified ISO 14001 facility.

The materials used in the AC drive shall be recyclable, non-toxic and flame retardant. The AC drive shall comply with the European directive RoHS (Restriction of Hazardous Substances) 2002/95/EC.

The Product Environmental Profile (PEP) analysis must be performed in conformity with standard ISO 14040 “Environmental management: life cycle assessment, principle and framework”.

7.  Quality

The frequency converter manufacturer shall have a valid ISO 9001 (2000 version) certification and applicable quality assurance system.

The AC drive shall have the main power components designed for 10 years, fan included, for defined duty cycle (80% Pn; 24h/day).

The AC drive shall have been tested by the manufacturer with campaigns of internal and “in situ” tests.

END of the document