MicroTech II®
Multiple Air Handler Controller

BACnet® Networks

Protocol Implementation Conformance Statement

Table of Contents

Notice......

Limited Warranty......

BACnet Protocol Implementation Conformance Statement......

Product Description......

BACnet Standardized Device Profile......

BACnet Interoperability Building Blocks (BIBBs) Supported......

Standard Object Types Supported......

Segmentation Capability......

Data Link Layer Options......

Networking Options......

Device Address Binding......

Character Sets Supported......

This document contains the Protocol Implementation Conformance Statement (PICS) for the MicroTech II® Multiple Air Handler Controller from McQuay International as required by ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigeration, and Air Conditioning Engineers) Standard 135-2001, BACnet; A Data Communication Protocol for Building Automation and Control Networks. Refer to ANSI/ASHRAE 135-2001.

Notice

© 2005 McQuay International, Minneapolis MN. All rights reserved throughout the world

McQuay International reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this product is appropriate for his or her application.

BACnet is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Windows is a registered trademark of Microsoft Corporation. McQuay and MicroTech are registered trademarks of McQuay International.

Limited Warranty

Consult your local McQuay Representative for warranty details. Refer to Form 933-430285Y. To find your local McQuay Representative, go to

BACnet Protocol Implementation Conformance Statement

Date: / October, 2005
Vendor Name: / McQuay International
Product Name: / Multiple Air Handler Controller
Product Model Number: / MTII-UC-0-MAC01.1
Applications Software Version: / 01.1
BACnet Protocol Revision: / Version 1
Revision 2

Product Description

The MicroTech II Multiple Air Handler Controller is a controller designed to control a maximum of 8 MicroTech II Applied Rooftop or Self-Contained units in up to four separate multiple-unit control groups, with each group consisting of units with similar type and size. It is also designed to be integrated into BACnet building automation systems.

The controller provides three control strategies: 1) Common Outdoor Air Temperature, 2) Common Control Temperature and 3) Common Duct Static Pressure. Read/write access to temperatures, pressures and control parameters is available using Internet Explorer and the BACnet control network.

BACnet Standardized Device Profile

Based on BIBBs supported, the MicroTech II Multiple Air Handler is a BACnet Advanced Application Controller (B-AAC). Refer to the section below entitled BACnet Interoperability Building Blocks (BIBBs) Supported for a complete listing of BIBBS.

BACnet Interoperability Building Blocks (BIBBs) Supported

BIBB Name / Designation
Data Sharing – ReadProperty – A / DS-RP-A
Data Sharing – ReadProperty – B / DS-RP-B
Data Sharing – ReadPropertyMultiple – A / DS-RPM-A
Data Sharing – ReadPropertyMultiple – B / DS-RPM-B
Data Sharing – Write Property – A / DS-WP-A
Data Sharing – WriteProperty – B / DS-WP-B
Data Sharing – WritePropertyMultiple – A / DS-WPM-A
Data Sharing – WritePropertyMultiple – B / DS-WPM-B
Data Sharing – COV– A / DS-COV-A
Data Sharing – COV – Unsolicited – A / DS-COVU-A
Device Management – Dynamic Device Binding – A / DM-DDB-A
Device Management – Dynamic Device Binding – B / DM-DDB-B
Device Management – Dynamic Object Binding – A / DM-DOB-A
Device Management – Dynamic Object Binding – B / DM-DOB-B
Device Management – Router Configuration – A / DM-RC-A

Standard Object Types Supported

Object-Type / Creatable / Deleteable / Optional Properties Supported / Writeable Properties Not Required To Be Writeable
Analog Input / Description
Min_Pres_Value
Max_Pres_Value
COV_Increment
Time_Delay
Notification_Class
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable
Acked_Transitions
Notify_Type
Reliability / Description
Analog Output / Description
Reliability
Min_Pres_Value
COV_Increment
Time_Delay
Notification_Class
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable
Acked_Transitions
Notify_Type / Description
Out_Of_Service
Binary Output / Description
Inactive_Text
Active_Text
Change_Of_State_Time
Change_Of_State_Count
Time_Of_State_Count_Reset
Elapsed_Active_Time
Time_Of_Active_Time_Reset
Minimum_Off_Time
Minimum_On_Time
Notification_Class
Time_Delay
Feedback_Value
Event_Enable
Acked_Transitions
Reliability
Notify_Type / Description
Out_Of_Service
Multi-state Output
(8 States Max) / Description
State_Text
Time_Delay
Notify_Type
Acked_Transitions
Event_Enable
Feedback_Value
Notification_Class
Reliability / Out_Of_Service
Description
Reliability

Segmentation Capability

Segmented requests supported / Window Size:Any
Segmented responses supported / Window Size:Any

Data Link Layer Options

BACnet IP, (Annex J)
ISO 8802-3, Ethernet (Clause 7)
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400 bps

Networking Options

Router, Clause 6 – Ethernet IP-Ethernet, Ethernet-MS/TP, Ethernet IP-MS/TP
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? No

Device Address Binding

Static Device Binding / Yes
No

Character Sets Supported

ANSI X3.4 / BM/Microsoft DBCS / ISO 8859-1
ISO 10646 (UCS-2) / ISO 10646 (UCS-4) / JIS C 6226

Note: Support for multiple character sets does not imply they can be supported simultaneously.

1ED 15079-1