PRODUCT SPECIFICATION GUIDE –XLC ExPLOSIONPROOF LIGHTING CONTACTOR
SectionS26 54 00, 26 09 23 & 26 09 19
Product Specification Guide – XLC Explosionproof Lighting Contactor
SECTION 26 54 00 – Classified Location Lighting
SECTION 26 09 23 – Lighting Control Devices
SECTION 26 09 19 – Enclosed Contactors
PART 1GENERAL
1.01SCOPE
A.Furnishing, installation, and assembly of lighting control for areas classified as hazardous.
1.02REFERENCES
A.National Fire Protection Association (NFPA):
- NFPA 70 - National Electrical Code (NEC)
B.Underwriters Laboratories, Inc. (UL):
- UL1203 - Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations
C.Underwriters Laboratories, Inc. to CSA Standard (cUL)
- C22.2 No. 30 - Explosion-Proof Enclosures for Use in Class I Hazardous Locations
D.National Electrical Manufacturers Association (NEMA):
- NEMA 3 - Outdoor use, rain, sleet, windblown, dust, external formation of ice
- NEMA 7BCD - Indoor use, Class I, Division 1, Groups B, C, D
- NEMA9EFG - Indoor use, Class II, Division 1, Groups E, F, G
1.03SUBMITTALS - FOR REVIEW/APPROVAL
A.The following information shall be submitted to the engineer.
- Manufacturer’s descriptive literature and technical specifications for each product
- Manufacturer’s product drawing (2D or 3D), when requested
- Manufacturer’s installation and maintenance document
1.04QUALIFICATIONS
A.The supplier of the assembly must be the manufacturer of the major components within the assembly.
B.For the equipment specified herein, the manufacturer must be ISO 9001 certified.
C.The manufacturer of this equipment must have produced similar electrical equipment for a minimum period of five (5) years. When requested by the engineer, an acceptable list of installations with similar equipment will be provided demonstrating compliance with this requirement.
D.Products must be free of defects in material and workmanship.
1.05REGULATORY REQUIREMENTS
1.06DELIVERY, STORAGE, AND HANDLING
A.Store products in manufacturer’s unopened packaging until ready for installation
PART 2PRODUCTS
2.01MANUFACTURERS
A.Acceptable Manufacturers:
Eaton’s Crouse-Hinds Business
1201 Wolf Street
Syracuse, NY 13208
(866) 764-5454
The listing of specific manufacturers above does not imply acceptance of their products that donot meet the specified ratings, features, and functions. Manufacturers listed above are notrelieved from meeting these specifications in their entirety. Products in compliance with thespecification and manufactured by others not named will be considered only if pre-approved bythe engineer ten (10) days prior to bid date.
2.02ELECTRICAL REQUIREMENTS
A.XLC Lighting Contactor:
- Standard line voltage of 600 VAC.
- Lighting contactor coil voltage of 120VAC.
- The lighting contactor must be rated for 30A.
- The lighting contactor must allow up to 12 poles.
2.03material requirements
A.XLC Lighting Contactor:
- Enclosure body and cover must becopper-free, die cast aluminum.
- Enclosure must contain neoprene gasket for ingress protection.
- Enclosure must contain hex head stainless steel, triple lead bolts.
2.04design and performance requirements
A.XLC Lighting Contactor:
- A C30CN lighting contactor must be used for lighting control.
- The lighting contactor must allow for both electronically and mechanically held configurations within the same unit.
- The lighting contactor must have a visual indication when the contact is closed.
- The lighting contactor must have finger and back-of-hand protection on each power terminal to prevent accidental contact with personnel or tools.
- The enclosure must have captive, triple lead, quick release, hex head stainless steel bolts.
- The enclosure must have tap-in mounting feet.
- The enclosure must have a Type 4X breather and drain.
PART 3EXECUTION
2.05INSTALLATION
A.The enclosure must be provided with two ¾” NPT control conduit entries
B.The enclosure must be provided with twelve 1” NPT power conduit entries
SECTIONS 26 54 00, 26 09 23 & 26 09 1905/19/14