SECTION 264113 - LIGHTNING PROTECTION FOR STRUCTURES

PART 1 - GENERAL

1.1RELATED DOCUMENTS

  1. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division01 Specification Sections, apply to this Section.

1.2SUMMARY

  1. Section includes lightning protection for structures,structure elements, andbuilding site components.

1.3ACTION SUBMITTALS

  1. Product Data: For each type of product indicated.
  2. Shop Drawings: For air terminals and mounting accessories.
  3. Layout of the lightning protection system, along with details of the components to be used in the installation.
  4. Include indications for use of raceway, data on how concealment requirements will be met, and calculations required by NFPA780 for bonding of grounded and isolated metal bodies.

1.4INFORMATIONAL SUBMITTALS

  1. Qualification Data: For qualified Installer and manufacturer. Include data on listing or certification by UL.
  2. Certification, signed by Contractor, that roof adhesive is approved by manufacturer of roofing material.
  3. Field quality-control reports.
  4. Comply with recommendations in NFPA780, Annex D, "Inspection and Maintenance of Lightning Protection Systems," for maintenance of the lightning protection system.
  5. Other Informational Submittals: Plans showing dimensioned as-built locations of grounding features, including the following:
  6. Ground rods.

1.5QUALITY ASSURANCE

  1. Installer Qualifications: Certified by UL, trained and approved for installation of units required for this Project.
  2. System Certificate:
  3. UL Master Label.
  4. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA780, "Definitions" Article.

1.6COORDINATION

  1. Coordinate installation of lightning protection with installation of other building systems and components, including electrical wiring, supporting structures and building materials, metal bodies requiring bonding to lightning protection components, and building finishes.
  2. Coordinate installation of air terminals attached to roof systems with roofing manufacturer and Installer.
  3. Flashings of through-roof assemblies shall comply with roofing manufacturers' specifications.

PART 2 - PRODUCTS

2.1LIGHTNING PROTECTION SYSTEM COMPONENTS

  1. Comply with UL96and NFPA780.
  2. Roof-Mounted Air Terminals: NFPA780, ClassI, copper unless otherwise indicated.
  3. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
  4. East Coast Lightning Equipment Inc.
  5. ERICO International Corporation.
  6. Harger.
  7. Heary Bros. Lightning Protection Co. Inc.
  8. Independent Protection Co.
  9. Preferred Lightning Protection.
  10. Robbins Lightning, Inc.
  11. Thompson Lightning Protection, Inc.
  12. Air Terminals More than 24 Inches Long: With brace attached to the terminal at not less than half the height of the terminal.
  13. Single-Membrane, Roof-Mounted Air Terminals: Designed specifically for single-membrane roof system materials. Comply with requirements in roofing Sections.
  14. Main and Bonding Conductors: Copper.
  15. Ground Rods: Copper-clad steel; 3/4 inch in diameter by 10 feet long.

PART 3 - EXECUTION

3.1INSTALLATION

  1. Install lightning protection components and systems according to UL96AandNFPA780.
  2. Install conductors with direct paths from air terminals to ground connections. Avoid sharp bends.
  3. Conceal the following conductors:
  4. Interior conductors.
  5. Conductors within normal view of exterior locations at grade within 200 feet of building.
  6. Cable Connections: Use exothermic-welded connections for all conductor splices and connections between conductors and other components.
  7. Exception: In single-ply membrane roofing, exothermic-welded connections may be used only below the roof level.

Retain first paragraph below for single-ply membrane roofing.

  1. Air Terminals on Single-Ply Membrane Roofing: Comply with roofing membrane and adhesive manufacturer's written instructions.

3.2SLEEVE AND SLEEVE-SEAL INSTALLATION FOR ELECTRICAL PENETRATIONS

  1. Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply with requirements in Division26 Section "Sleeves and Sleeve Seals for Electrical Raceways and Cabling."

3.3CORROSION PROTECTION

  1. Do not combine materials that can form an electrolytic couple that will accelerate corrosion in the presence of moisture unless moisture is permanently excluded from junction of such materials.
  2. Use conductors with protective coatings where conditions cause deterioration or corrosion of conductors.

3.4FIELD QUALITY CONTROL

  1. Notify Architect at least 48 hours in advance of inspection before concealing lightning protection components.
  2. UL Inspection: Meet requirements to obtain a UL Master Label for system.

END OF SECTION