ESTC Standard No. 6 Part 1 – Electrical: 2013 Edition (Inc Amendment No. 1)

MOD FORM 2208

GENERIC SCHEDULE OF ELECTRICAL INSTALLATION TEST RESULTS

Site: / Building:
Installation Test Results - Page 1 of 4
Distribution Board Details:
DB Reference Number
Location
Zs at DB(Ω)
Ipf at DB (kA)
Correct Supply Polarity Confirmed?
Phase Sequence Confirmed (Where Appropriate)?
Details of circuits and/or installed equipment vulnerable to damage when testing:
Details of test instruments used:
Serial / Asset Number
Continuity
Insulation Resistance
Earth Fault Loop Impedance
RCD
Earth Electrode Resistance
Impedance Measured
Tested by:
Name (Block Capitals)
Signature
Date (DD/MM/YYYY)

Page...... of......

A-1

ESTC Standard No. 6 Part 1 – Electrical: 2013 Edition (Inc Amendment No. 1)

Site: / Building:
Installation Test Results - Page 2 of 4
Circuit Number & Phase / Circuit Description / Type of Wiring / Conductor Details / Max disconnection time permitted (s) / Overcurrent Device(s) / RCD / Max Zs permitted by BS7671 (Ω)
Reference Method* / Live
(mm2) / CPC
(mm2) / BS EN / Type No / Rating (A) / Breaking capacity (kA) / Operating Current In (mA)

*See Table 4A2 of Appendix 4 of BS7671

Codes For Type of Wiring
A / B / C / D / E / F / G / H / O (Other – please state)
Exposed PVC/PVC cables prohibited / PVC cables in metallic conduit / PVC cables in non-metallic conduit / PVC cables in metallic trunking / PVC cables in non-metallic trunking / Exposed PVC/ SWA cables prohibited / XLPE/SWA Armoured cables / Mineral Insulated on cable tray
Tested by:
Name (Block Capitals)
Signature
Date (DD/MM/YYYY)
Site: / Building:
Installation Test Results - Page 3 of 4
Circuit Number & Phase / Circuit Impedances (Ω) / (6)
Insulation Resistance / (7)
Separation of Circuits (S or N/S) / (8)
Polarity (S or N/S) / (9)
Earth Electrode Resistance / (10) Maximum measured earth fault loop impedance Zs (Ω) / (11)
RCD Operating Times
(4)
All Circuits / (5)
Ring final circuits only / Line / Line not line / Phase (MΩ) / Line / Neutral (MΩ) / Line / Earth (MΩ) / Neutral / Earth (MΩ) / At 50% In
(S or N/S) / At In (ms) / At 5 In (ms)
R1 + R2* / R2 / R1 / Rn / R2

* Where there are no spurs connected to a ring final circuit this value is also the (R1+R2) of the circuit

Numbers in brackets e.g. (4) represent job numbers which are detailed in section 18.

Tested by:
Name (Block Capitals)
Signature
Date (DD/MM/YYYY)

Page...... of......

A-1

ESTC Standard No. 6 Part 1 – Electrical: 2013 Edition (Inc Amendment No. 1

REMEDIAL ACTIONS ARISING FROM GENERIC SCHEDULE OF TEST RESULTS

Site: / Building:
OBSERVATION / CLASSIFICATION CODE / Recommended remedial action / Date of Action Complete

Inspected by:

Name (Capitals) ………………………………………………..

Signature ……………………………………………......

Date ……………………………………………......

Classification Codes

Each observation relating to a concern about the safety of the installation shall be attributed an appropriate Classification Code selected from the standard codes C1, C2 and C3 as follows:

Code C1‘Danger present’ Risk of injury. Immediate remedial action required

Code C2‘Potentially dangerous’ Urgent remedial action required

Code C3‘Improvement recommended’

Page...... of......