Customer Name & Address

Customer Name & Address

Date: 3/7/2009

Technical Specification

Project name : Four Seasons Hotel LondonSoftware version: E4.20 (4-3-2009)/A

Quotation no. : 0876-09-o / 001Eurovent identification number: 08.02.365

GENERAL DATA
Product / Air handling unit / Customer reference / AHU 001 - Ground Flr Front of House
Number off / 1 / AHU configuration / Inline
Location / Internal / Total weight (each) / kg / 2648
Delivery / In sections / Radiated casework SWL / dB(A) / 72
AHU finish / Outside in standard colour (RAL 7042) / Eurovent energy classification / C /
SFPe / kJ/m3 / 2.62 / SFPv / kJ/m3 / 2.47
ACCESS DATA
Handle type / L-Handle
EXHAUST DATA
Type / 39HQ 11.10 / Air volume / m3/s / 7.93
Casing construction / RP080
60 mm / Internal sheet / Polyester coated steel 0.80mm
Insulation / Rockwool 70-90 kg/m3 / External sheet / Polyester coated steel 0.80mm
SFPe / kJ/m3 / 1.06 / SFPv / kJ/m3 / 1.06
Mechanical performance according EN1886 / Selected unit / D1 / L2 / -- / T2 / TB2 / (R)
Model box / D1 / L2 / F9 / T2 / TB2 / (M)
Sound data exhaust / Hz / 125 / 250 / 500 / 1k / 2k / 4k / 8k / dB(A)
Inlet Top / dB / 86 / 88 / 84 / 80 / 76 / 72 / 65 / 86
Outlet Top / dB / 88 / 88 / 83 / 82 / 77 / 72 / 64 / 87
SUPPLY DATA
Type / 39HQ 13.12 / Air volume / m3/s / 8.83
Casing construction / RP080
60 mm / Internal sheet / Polyester coated steel 0.80mm
Insulation / Rockwool 70-90 kg/m3 / External sheet / Polyester coated steel 0.80mm
SFPe / kJ/m3 / 1.68 / SFPv / kJ/m3 / 1.52
Mechanical performance according EN1886 / Selected unit / D2 / L2 / F7 / T2 / TB2 / (R)
Model box / D1 / L2 / F9 / T2 / TB2 / (M)
Sound data supply / Hz / 125 / 250 / 500 / 1k / 2k / 4k / 8k / dB(A)
Inlet Top / dB / 85 / 87 / 82 / 72 / 65 / 51 / 41 / 82
Unit outlet / dB / 94 / 92 / 87 / 86 / 81 / 76 / 68 / 91
In direction of airflow, the unit comprises:
DELIVERY SECTION(S)
Section / Width (mm) / Height (mm) / Length (mm) / Baseframe (mm) / Weight (kg)
1 / 1858 / 1698 / 2818 / 62 / 823
2 / 2178 / 2018 / 2449 / 62 / 749
3 / 2178 / 2018 / 2769 / 62 / 1076
EXHAUST COMPONENTS
INLET
Opening, width x height / mm / 738 x 1698 / Provided with:
Pressure drop / Pa / 27 / Opening product / Duct spigot
FAN
Fan type / VTZ 710 A
Fan arrangement / Single / Installed motor power / kW / 7.50
Air volume / m3/s / 7.93 / Motor / Run
Fan outlet velocity / m/s / 9.83 / Motor efficiency class / EFF2
System effect / Pa / 116 / Motor speed / rpm / 1500
External static pressure / Pa / 400 / Voltage / V / 400/690
Total static pressure / Pa / 583 / Current / A / 14.7
Dynamic pressure / Pa / 58 / Abs. motor power incl. F.I. / kW / 8.37
Total pressure / Pa / 641
Fan speed / rpm / 990
Efficiency / % / 78
Fan shaft power / kW / 6.48
Fan sound data SWL / Hz / 63 / 125 / 250 / 500 / 1k / 2k / 4k / 8k
Total / Inlet dB / 87 / 86 / 88 / 84 / 80 / 76 / 72 / 65
Outlet dB / 90 / 88 / 88 / 83 / 82 / 77 / 72 / 64
FAN EXTRAS
Drive guard - closed
ACCESS
Access type / Door / Viewport / Included
Access side / Left
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
1 x Cable connection box / 1 x Frequency inverter incl. isolator, Danfoss, 7,5kW - 16A - 400V - IP55 - H3
Motor to be wire DOL using EMC (screened) cable / Wiring to be extended to 1.5 Meters outside unit (flying lead)
Inverter delivered as a separate item
SUPPLY COMPONENTS
SUPPLY UNIT CHANGE
Type / 39HQ 11.10/39HQ 13.12 / Internal sheet / Polyester coated steel 0.80mm
Casing construction / RP080
60 mm / External sheet / Polyester coated steel 0.80mm
Insulation / Rockwool 70-90 kg/m3
Mechanical performance according EN1886 / Selected unit / (R)
Model box / (M)
DOUBLE MIXING BOX
Exhaust opening, w x h / mm / 738 x 1698 / Provided with:
Pressure drop / Pa / 40
Damper / External, Opposed blades,
Suitable for actuator,
Aluminium
Recirc opening, w x h / mm / 1698 x 738 / Provided with:
Pressure drop / Pa / 73
Damper / Internal, Opposed blades,
Suitable for actuator,
Aluminium
Fresh air opening, w x h / mm / 738 x 2018 / Provided with:
Pressure drop / Pa / 36
Damper / External, Opposed blades,
Suitable for actuator,
Aluminium
ACCESS (EXHAUST)
Access type / Door / Viewport / Included
Access side / Left
EXTRAS (EXHAUST)
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
ACCESS (SUPPLY)
Access type / Door / Viewport / Included
Access side / Left
EXTRAS (SUPPLY)
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
COMBINED FILTER
Primary filter type / Panel (Synthetic) / Secondary filter type / Bag (Synthetic)
Filter class / G4 / Filter class / F7
Initial pressure drop / Pa / 71 / Initial pressure drop / Pa / 122
Design pressure drop / Pa / 111 / Design pressure drop / Pa / 161
Final pressure drop / Pa / 150 / Final pressure drop / Pa / 200
Filter length / mm / 48 / Filter length / mm / 500
Withdrawal method / Side
Filter frame material / Galvanised / Measuring section / Included
ACCESS
Access type / Door / Access side / Left
EXTRAS
1 x Pressure gauge wall mounted, Minihelic 5000 (0-250 Pa) / 1 x Pressure gauge wall mounted, Minihelic 5000 (0-500 Pa)
4 x Measuring nipple, 6mm
CHILLED WATER COIL / Number of coils / 1
Air volume / m3/s / 8.83 / Fluid / 100% / Water
Duty / kW / 163.08 / Fluid flow rate / l/s / 6.49
Air on db / °C / 26.5 / Fluid on / °C / 6.0
Air on wb/RH / °C/% / 18.0 / 44 / Fluid off / °C / 12.0
Air off db / °C / 13.0 / Fluid pressure drop / kPa / 25
Air off wb/RH / °C/% / 12.3 / 93
Air pressure drop coil (Wet) / Pa / 154 / Air pressure drop elim. / Pa / 23
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Left)
Coil frame / Standard / Connection size / 2 1/2"
Tube thickness / mm / 0.4 / Fin spacing / mm / 2.0
Tube diameter / mm / 16.5 / Fin thickness / mm / 0.13
Face velocity / m/s / 2.77 / Eliminator / Plastic
Drainpan type / Sloping (cleanable) / Drainpan material / Stainless steel 304
INSPECTION
ACCESS
Access type / Door / Viewport / Included
Access side / Left
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
HOT WATER COIL / (lphw) / Number of coils / 1
Air volume / m3/s / 8.83 / Fluid / 100% / Water
Duty / kW / 149.81 / Fluid flow rate / l/s / 3.33
Air on / °C / 9.0 / Fluid on / °C / 82.0
Air off / °C / 23.0 / Fluid off / °C / 71.0
Air pressure drop / Pa / 13 / Fluid pressure drop / kPa / 12
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Left)
Coil frame / Standard / Connection size / 2"
Tube thickness / mm / 0.35 / Fin spacing / mm / 2.5
Tube diameter / mm / 12.45 / Fin thickness / mm / 0.12
Face velocity / m/s / 2.64
FAN
Fan type / VTZ 710 A
Fan arrangement / Single / Installed motor power / kW / 15.00
Air volume / m3/s / 8.83 / Motor / Run
Fan outlet velocity / m/s / 10.95 / Motor efficiency class / EFF2
System effect / Pa / 36 / Motor speed / rpm / 1500
External static pressure / Pa / 495 / Voltage / V / 400/690
Total static pressure / Pa / 1028 / Current / A / 27.4
Dynamic pressure / Pa / 72 / Abs. motor power incl. F.I. / kW / 14.80
Total pressure / Pa / 1100
Fan speed / rpm / 1231
Efficiency / % / 81
Fan shaft power / kW / 11.94
Fan sound data SWL / Hz / 63 / 125 / 250 / 500 / 1k / 2k / 4k / 8k
Total / Inlet dB / 91 / 90 / 92 / 88 / 84 / 80 / 76 / 69
Outlet dB / 99 / 94 / 92 / 87 / 86 / 81 / 76 / 68
Opening, width x height / mm / 1058 x 1058 / Provided with:
Pressure drop / Pa / 0 / Opening product / Duct spigot
FAN EXTRAS
Drive guard - closed
ACCESS
Access type / Door / Viewport / Included
Access side / Right
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
1 x Frequency inverter incl. isolator, Danfoss, 15kW - 32A - 400V - IP55 - H3 / Motor to be wire DOL using EMC (screened) cable
Wiring to be extended to 1.5 Meters outside unit (flying lead) / Inverter delivered as a separate item

Page 1 of 51

Date: 3/7/2009

Technical Specification

Project name : Four Seasons Hotel LondonSoftware version: E4.20 (4-3-2009)/A

Quotation no. : 0876-09-o / 002Eurovent identification number: 08.02.365

GENERAL DATA
Product / Air handling unit / Customer reference / AHU 002 - Grnd+Basement Back of House
Number off / 1 / AHU configuration / Inline
Location / Internal / Total weight (each) / kg / 904
Delivery / In sections / Radiated casework SWL / dB(A) / 68
AHU finish / Outside in standard colour (RAL 7042) / Eurovent energy classification / B /
ACCESS DATA
Handle type / L-Handle
SUPPLY DATA
Type / 39HQ 08.08 / Air volume / m3/s / 3.52
Casing construction / RP080
60 mm / Internal sheet / Polyester coated steel 0.80mm
Insulation / Rockwool 70-90 kg/m3 / External sheet / Polyester coated steel 0.80mm
SFPe / kJ/m3 / 1.47 / SFPv / kJ/m3 / 1.34
Mechanical performance according EN1886 / Selected unit / D1 / L2 / F7 / T2 / TB2 / (R)
Model box / D1 / L2 / F9 / T2 / TB2 / (M)
Sound data supply / Hz / 125 / 250 / 500 / 1k / 2k / 4k / 8k / dB(A)
Inlet Full face / dB / 82 / 85 / 81 / 73 / 64 / 49 / 39 / 81
Unit outlet / dB / 90 / 90 / 85 / 84 / 78 / 73 / 66 / 88
In direction of airflow, the unit comprises:
DELIVERY SECTION(S)
Section / Width (mm) / Height (mm) / Length (mm) / Baseframe (mm) / Weight (kg)
1 / 1378 / 1378 / 1649 / 62 / 398
2 / 1378 / 1378 / 2129 / 62 / 506
SUPPLY COMPONENTS
INLET
Opening, width x height / mm / 1218 x 1218 / Provided with:
Pressure drop / Pa / 7
Damper / External, Opposed blades,
Suitable for actuator,
Aluminium
HOT WATER COIL / (lphw) / Number of coils / 1
Air volume / m3/s / 3.52 / Fluid / 100% / Water
Duty / kW / 38.19 / Fluid flow rate / l/s / 0.83
Air on / °C / -4.0 / Fluid on / °C / 82.0
Air off / °C / 5.0 / Fluid off / °C / 71.0
Air pressure drop / Pa / 17 / Fluid pressure drop / kPa / 11
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Right)
Coil frame / Standard / Connection size / 1 1/4"
Tube thickness / mm / 0.4 / Fin spacing / mm / 6.0
Tube diameter / mm / 16.5 / Fin thickness / mm / 0.13
Face velocity / m/s / 2.81
COMBINED FILTER
Primary filter type / Panel (Synthetic) / Secondary filter type / Bag (Synthetic)
Filter class / G4 / Filter class / F7
Initial pressure drop / Pa / 66 / Initial pressure drop / Pa / 116
Design pressure drop / Pa / 106 / Design pressure drop / Pa / 158
Final pressure drop / Pa / 146 / Final pressure drop / Pa / 200
Filter length / mm / 48 / Filter length / mm / 500
Withdrawal method / Side
Filter frame material / Galvanised / Measuring section / Included
ACCESS
Access type / Door / Access side / Right
EXTRAS
1 x Pressure gauge wall mounted, Minihelic 5000 (0-250 Pa) / 1 x Pressure gauge wall mounted, Minihelic 5000 (0-500 Pa)
4 x Measuring nipple, 6mm
CHILLED WATER COIL / Number of coils / 1
Air volume / m3/s / 3.52 / Fluid / 100% / Water
Duty / kW / 34.72 / Fluid flow rate / l/s / 1.38
Air on db / °C / 30.0 / Fluid on / °C / 6.0
Air on wb/RH / °C/% / 20.0 / 40 / Fluid off / °C / 12.0
Air off db / °C / 22.0 / Fluid pressure drop / kPa / 13
Air off wb/RH / °C/% / 17.1 / 62
Air pressure drop coil (Wet) / Pa / 93 / Air pressure drop elim. / Pa / 26
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Right)
Coil frame / Standard / Connection size / 1 1/2"
Tube thickness / mm / 0.4 / Fin spacing / mm / 4.0
Tube diameter / mm / 16.5 / Fin thickness / mm / 0.13
Face velocity / m/s / 2.93 / Eliminator / Plastic
Drainpan type / Sloping (cleanable) / Drainpan material / Stainless steel 304
INSPECTION
ACCESS
Access type / Door / Viewport / Included
Access side / Right
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
HOT WATER COIL / (lphw) / Number of coils / 1
Air volume / m3/s / 3.52 / Fluid / 100% / Water
Duty / kW / 72.52 / Fluid flow rate / l/s / 1.61
Air on / °C / 5.0 / Fluid on / °C / 82.0
Air off / °C / 22.0 / Fluid off / °C / 71.0
Air pressure drop / Pa / 21 / Fluid pressure drop / kPa / 7
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Right)
Coil frame / Standard / Connection size / 1 1/2"
Tube thickness / mm / 0.35 / Fin spacing / mm / 2.0
Tube diameter / mm / 12.45 / Fin thickness / mm / 0.12
Face velocity / m/s / 2.81
FAN
Fan type / THLZ 450 FF A
Fan arrangement / Single / Installed motor power / kW / 7.50
Air volume / m3/s / 3.52 / Motor / Run
Fan outlet velocity / m/s / 10.87 / Motor efficiency class / EFF2
System effect / Pa / 35 / Motor speed / rpm / 1500
External static pressure / Pa / 400 / Voltage / V / 400/690
Total static pressure / Pa / 864 / Current / A / 14.7
Dynamic pressure / Pa / 71 / Absorbed motor power / kW / 5.18
Total pressure / Pa / 935
Fan speed / rpm / 1904
Efficiency / % / 80
Fan shaft power / kW / 4.14
Fan sound data SWL / Hz / 63 / 125 / 250 / 500 / 1k / 2k / 4k / 8k
Total / Inlet dB / 88 / 87 / 90 / 87 / 85 / 79 / 74 / 67
Outlet dB / 94 / 90 / 90 / 85 / 84 / 78 / 73 / 66
Opening, width x height / mm / 560 x 560 / Provided with:
Pressure drop / Pa / 0 / Opening product / Duct spigot
FAN EXTRAS
Drive guard - closed
ACCESS
Access type / Door / Viewport / Included
Access side / Right
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
1 x Isolator, 6P 16A - 2.2 to 7.5 kW, incl. wiring to motor

Page 1 of 51

Date: 3/7/2009

Technical Specification

Project name : Four Seasons Hotel LondonSoftware version: E4.20 (4-3-2009)/A

Quotation no. : 0876-09-o / 004Eurovent identification number: 08.02.365

GENERAL DATA
Product / Air handling unit / Customer reference / AHU 004 - Laundry Supply
Number off / 1 / AHU configuration / Inline
Location / Internal / Total weight (each) / kg / 1003
Delivery / In sections / Radiated casework SWL / dB(A) / 70
AHU finish / Outside in standard colour (RAL 7042) / Eurovent energy classification / B /
ACCESS DATA
Handle type / L-Handle
SUPPLY DATA
Type / 39HQ 10.08 / Air volume / m3/s / 4.05
Casing construction / RP080
60 mm / Internal sheet / Polyester coated steel 0.80mm
Insulation / Rockwool 70-90 kg/m3 / External sheet / Polyester coated steel 0.80mm
SFPe / kJ/m3 / 1.42 / SFPv / kJ/m3 / 1.26
Mechanical performance according EN1886 / Selected unit / D1 / L2 / F7 / T2 / TB2 / (R)
Model box / D1 / L2 / F9 / T2 / TB2 / (M)
Sound data supply / Hz / 125 / 250 / 500 / 1k / 2k / 4k / 8k / dB(A)
Inlet Full face / dB / 83 / 85 / 81 / 75 / 68 / 50 / 40 / 82
Unit outlet / dB / 90 / 91 / 85 / 86 / 82 / 74 / 67 / 90
In direction of airflow, the unit comprises:
DELIVERY SECTION(S)
Section / Width (mm) / Height (mm) / Length (mm) / Baseframe (mm) / Weight (kg)
1 / 1698 / 1378 / 1649 / 62 / 482
2 / 1698 / 1378 / 2129 / 62 / 521
SUPPLY COMPONENTS
INLET
Opening, width x height / mm / 1538 x 1218 / Provided with:
Pressure drop / Pa / 4
Damper / External, Opposed blades,
Suitable for actuator,
Aluminium
HOT WATER COIL / (lphw) / Number of coils / 1
Air volume / m3/s / 4.05 / Fluid / 100% / Water
Duty / kW / 43.94 / Fluid flow rate / l/s / 0.95
Air on / °C / -4.0 / Fluid on / °C / 82.0
Air off / °C / 5.0 / Fluid off / °C / 71.0
Air pressure drop / Pa / 14 / Fluid pressure drop / kPa / 4
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Left)
Coil frame / Standard / Connection size / 1 1/2"
Tube thickness / mm / 0.4 / Fin spacing / mm / 6.0
Tube diameter / mm / 16.5 / Fin thickness / mm / 0.13
Face velocity / m/s / 2.49
COMBINED FILTER
Primary filter type / Panel (Synthetic) / Secondary filter type / Bag (Synthetic)
Filter class / G4 / Filter class / F7
Initial pressure drop / Pa / 59 / Initial pressure drop / Pa / 106
Design pressure drop / Pa / 97 / Design pressure drop / Pa / 153
Final pressure drop / Pa / 134 / Final pressure drop / Pa / 200
Filter length / mm / 48 / Filter length / mm / 500
Withdrawal method / Side
Filter frame material / Galvanised / Measuring section / Included
ACCESS
Access type / Door / Access side / Left
EXTRAS
1 x Pressure gauge wall mounted, Minihelic 5000 (0-250 Pa) / 1 x Pressure gauge wall mounted, Minihelic 5000 (0-500 Pa)
4 x Measuring nipple, 6mm
CHILLED WATER COIL / Number of coils / 1
Air volume / m3/s / 4.05 / Fluid / 100% / Water
Duty / kW / 81.13 / Fluid flow rate / l/s / 3.23
Air on db / °C / 30.0 / Fluid on / °C / 6.0
Air on wb/RH / °C/% / 20.0 / 40 / Fluid off / °C / 12.0
Air off db / °C / 15.4 / Fluid pressure drop / kPa / 23
Air off wb/RH / °C/% / 14.2 / 89
Air pressure drop coil (Wet) / Pa / 115 / Air pressure drop elim. / Pa / 21
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Left)
Coil frame / Standard / Connection size / 2"
Tube thickness / mm / 0.4 / Fin spacing / mm / 2.0
Tube diameter / mm / 16.5 / Fin thickness / mm / 0.13
Face velocity / m/s / 2.60 / Eliminator / Plastic
Drainpan type / Sloping (cleanable) / Drainpan material / Stainless steel 304
INSPECTION
ACCESS
Access type / Door / Viewport / Included
Access side / Left
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
HOT WATER COIL / (lphw) / Number of coils / 1
Air volume / m3/s / 4.05 / Fluid / 100% / Water
Duty / kW / 63.81 / Fluid flow rate / l/s / 1.42
Air on / °C / 5.0 / Fluid on / °C / 82.0
Air off / °C / 18.0 / Fluid off / °C / 71.0
Air pressure drop / Pa / 10 / Fluid pressure drop / kPa / 6
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Left)
Coil frame / Standard / Connection size / 1 1/2"
Tube thickness / mm / 0.35 / Fin spacing / mm / 3.0
Tube diameter / mm / 12.45 / Fin thickness / mm / 0.12
Face velocity / m/s / 2.48
FAN
Fan type / THLZ 450 FF A
Fan arrangement / Single / Installed motor power / kW / 7.50
Air volume / m3/s / 4.05 / Motor / Run
Fan outlet velocity / m/s / 12.51 / Motor efficiency class / EFF2
System effect / Pa / 47 / Motor speed / rpm / 1500
External static pressure / Pa / 300 / Voltage / V / 400/690
Total static pressure / Pa / 760 / Current / A / 14.7
Dynamic pressure / Pa / 94 / Absorbed motor power / kW / 5.74
Total pressure / Pa / 854
Fan speed / rpm / 1958
Efficiency / % / 75
Fan shaft power / kW / 4.59
Fan sound data SWL / Hz / 63 / 125 / 250 / 500 / 1k / 2k / 4k / 8k
Total / Inlet dB / 89 / 88 / 90 / 87 / 87 / 83 / 75 / 68
Outlet dB / 94 / 90 / 91 / 85 / 86 / 82 / 74 / 67
Opening, width x height / mm / 560 x 560 / Provided with:
Pressure drop / Pa / 0 / Opening product / Duct spigot
FAN EXTRAS
Drive guard - closed
ACCESS
Access type / Door / Viewport / Included
Access side / Left
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
1 x Isolator, 6P 16A - 2.2 to 7.5 kW, incl. wiring to motor

Page 1 of 51

Date: 3/7/2009

Technical Specification

Project name : Four Seasons Hotel LondonSoftware version: E4.20 (4-3-2009)/A

Quotation no. : 0876-09-o / 005Eurovent identification number: 08.02.365

GENERAL DATA
Product / Air handling unit / Customer reference / AHU 005 - Sub Basement Plantroom Supply
Number off / 1 / AHU configuration / Inline
Location / Internal / Total weight (each) / kg / 807
Delivery / In sections / Radiated casework SWL / dB(A) / 65
AHU finish / Outside in standard colour (RAL 7042) / Eurovent energy classification / B /
ACCESS DATA
Handle type / L-Handle
SUPPLY DATA
Type / 39HQ 08.10 / Air volume / m3/s / 5.38
Casing construction / RP080
60 mm / Internal sheet / Polyester coated steel 0.80mm
Insulation / Rockwool 70-90 kg/m3 / External sheet / Polyester coated steel 0.80mm
SFPe / kJ/m3 / 1.16 / SFPv / kJ/m3 / 1.09
Mechanical performance according EN1886 / Selected unit / D1 / L2 / F7 / T2 / TB2 / (R)
Model box / D1 / L2 / F9 / T2 / TB2 / (M)
Sound data supply / Hz / 125 / 250 / 500 / 1k / 2k / 4k / 8k / dB(A)
Inlet Full face / dB / 79 / 84 / 78 / 72 / 69 / 61 / 52 / 80
Unit outlet / dB / 87 / 88 / 82 / 81 / 76 / 72 / 67 / 86
In direction of airflow, the unit comprises:
DELIVERY SECTION(S)
Section / Width (mm) / Height (mm) / Length (mm) / Baseframe (mm) / Weight (kg)
1 / 1378 / 1698 / 2658 / 62 / 807
SUPPLY COMPONENTS
INLET
Opening, width x height / mm / 1218 x 1538 / Provided with:
Pressure drop / Pa / 7
Damper / External, Opposed blades,
Suitable for actuator,
Aluminium
HOT WATER COIL / (lphw) / Number of coils / 1
Air volume / m3/s / 5.38 / Fluid / 100% / Water
Duty / kW / 149.18 / Fluid flow rate / l/s / 3.24
Air on / °C / -4.0 / Fluid on / °C / 82.0
Air off / °C / 19.0 / Fluid off / °C / 71.0
Air pressure drop / Pa / 50 / Fluid pressure drop / kPa / 9
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Left)
Coil frame / Standard / Connection size / 2"
Tube thickness / mm / 0.4 / Fin spacing / mm / 6.0
Tube diameter / mm / 16.5 / Fin thickness / mm / 0.13
Face velocity / m/s / 3.54
COMBINED FILTER
Primary filter type / Panel (Synthetic) / Secondary filter type / Bag (Synthetic)
Filter class / G4 / Filter class / F7
Initial pressure drop / Pa / 93 / Initial pressure drop / Pa / 148
Design pressure drop / Pa / 122 / Design pressure drop / Pa / 174
Final pressure drop / Pa / 150 / Final pressure drop / Pa / 200
Filter length / mm / 48 / Filter length / mm / 500
Withdrawal method / Side
Filter frame material / Galvanised / Measuring section / Included
ACCESS
Access type / Door / Access side / Left
EXTRAS
1 x Pressure gauge wall mounted, Minihelic 5000 (0-250 Pa) / 1 x Pressure gauge wall mounted, Minihelic 5000 (0-500 Pa)
4 x Measuring nipple, 6mm
FAN
Fan type / VTZ 560 A
Fan arrangement / Single / Installed motor power / kW / 7.50
Air volume / m3/s / 5.38 / Motor / Run
Fan outlet velocity / m/s / 10.52 / Motor efficiency class / EFF2
System effect / Pa / 33 / Motor speed / rpm / 1500
External static pressure / Pa / 250 / Voltage / V / 400/690
Total static pressure / Pa / 635 / Current / A / 14.7
Dynamic pressure / Pa / 66 / Absorbed motor power / kW / 6.26
Total pressure / Pa / 702
Fan speed / rpm / 1323
Efficiency / % / 76
Fan shaft power / kW / 5.00
Fan sound data SWL / Hz / 63 / 125 / 250 / 500 / 1k / 2k / 4k / 8k
Total / Inlet dB / 84 / 82 / 87 / 82 / 80 / 78 / 73 / 67
Outlet dB / 92 / 87 / 88 / 82 / 81 / 76 / 72 / 67
Opening, width x height / mm / 720 x 720 / Provided with:
Pressure drop / Pa / 0 / Opening product / Duct spigot
FAN EXTRAS
Drive guard - closed
ACCESS
Access type / Door / Viewport / Included
Access side / Left
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
1 x Isolator, 6P 16A - 2.2 to 7.5 kW, incl. wiring to motor

Page 1 of 51

Date: 3/7/2009

Technical Specification

Project name : Four Seasons Hotel LondonSoftware version: E4.20 (4-3-2009)/A

Quotation no. : 0876-09-o / 006Eurovent identification number: 08.02.365

GENERAL DATA
Product / Air handling unit / Customer reference / AHU 101 - Back of House Offices
Number off / 1 / AHU configuration / Inline
Location / Internal / Total weight (each) / kg / 676
Delivery / In sections / Radiated casework SWL / dB(A) / 66
AHU finish / Outside in standard colour (RAL 7042) / Eurovent energy classification / A /
ACCESS DATA
Handle type / L-Handle
SUPPLY DATA
Type / 39HQ 07.06 / Air volume / m3/s / 1.95
Casing construction / RP080
60 mm / Internal sheet / Polyester coated steel 0.80mm
Insulation / Rockwool 70-90 kg/m3 / External sheet / Polyester coated steel 0.80mm
SFPe / kJ/m3 / 1.42 / SFPv / kJ/m3 / 1.13
Mechanical performance according EN1886 / Selected unit / D2 / L3 / F7 / T2 / TB2 / (R)
Model box / D1 / L2 / F9 / T2 / TB2 / (M)
Sound data supply / Hz / 125 / 250 / 500 / 1k / 2k / 4k / 8k / dB(A)
Inlet Full face / dB / 82 / 82 / 78 / 71 / 64 / 50 / 38 / 79
Unit outlet / dB / 91 / 89 / 82 / 81 / 78 / 74 / 65 / 87
In direction of airflow, the unit comprises:
DELIVERY SECTION(S)
Section / Width (mm) / Height (mm) / Length (mm) / Baseframe (mm) / Weight (kg)
1 / 1218 / 1058 / 1649 / 62 / 309
2 / 1218 / 1058 / 1969 / 62 / 366
SUPPLY COMPONENTS
INLET
Opening, width x height / mm / 1058 x 898 / Provided with:
Pressure drop / Pa / 4
Damper / External, Opposed blades,
Suitable for actuator,
Aluminium
HOT WATER COIL / (lphw) / Number of coils / 1
Air volume / m3/s / 1.95 / Fluid / 100% / Water
Duty / kW / 21.16 / Fluid flow rate / l/s / 0.46
Air on / °C / -4.0 / Fluid on / °C / 82.0
Air off / °C / 5.0 / Fluid off / °C / 71.0
Air pressure drop / Pa / 14 / Fluid pressure drop / kPa / 7
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Left)
Coil frame / Standard / Connection size / 1"
Tube thickness / mm / 0.4 / Fin spacing / mm / 6.0
Tube diameter / mm / 16.5 / Fin thickness / mm / 0.13
Face velocity / m/s / 2.48
COMBINED FILTER
Primary filter type / Panel (Synthetic) / Secondary filter type / Bag (Synthetic)
Filter class / G4 / Filter class / F7
Initial pressure drop / Pa / 53 / Initial pressure drop / Pa / 98
Design pressure drop / Pa / 125 / Design pressure drop / Pa / 197
Final pressure drop / Pa / 125 / Final pressure drop / Pa / 197
Filter length / mm / 48 / Filter length / mm / 500
Withdrawal method / Side
Filter frame material / Galvanised / Measuring section / Included
ACCESS
Access type / Door / Access side / Left
EXTRAS
1 x Pressure gauge wall mounted, Minihelic 5000 (0-250 Pa) / 1 x Pressure gauge wall mounted, Minihelic 5000 (0-500 Pa)
4 x Measuring nipple, 6mm
CHILLED WATER COIL / Number of coils / 1
Air volume / m3/s / 1.95 / Fluid / 100% / Water
Duty / kW / 19.23 / Fluid flow rate / l/s / 0.77
Air on db / °C / 30.0 / Fluid on / °C / 6.0
Air on wb/RH / °C/% / 20.0 / 40 / Fluid off / °C / 12.0
Air off db / °C / 22.0 / Fluid pressure drop / kPa / 10
Air off wb/RH / °C/% / 17.1 / 62
Air pressure drop coil (Wet) / Pa / 77 / Air pressure drop elim. / Pa / 21
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Left)
Coil frame / Standard / Connection size / 1 1/4"
Tube thickness / mm / 0.4 / Fin spacing / mm / 4.0
Tube diameter / mm / 16.5 / Fin thickness / mm / 0.13
Face velocity / m/s / 2.64 / Eliminator / Plastic
Drainpan type / Sloping (cleanable) / Drainpan material / Stainless steel 304
INSPECTION
ACCESS
Access type / Door / Viewport / Included
Access side / Left
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
HOT WATER COIL / (lphw) / Number of coils / 1
Air volume / m3/s / 1.95 / Fluid / 100% / Water
Duty / kW / 40.18 / Fluid flow rate / l/s / 0.89
Air on / °C / 5.0 / Fluid on / °C / 82.0
Air off / °C / 22.0 / Fluid off / °C / 71.0
Air pressure drop / Pa / 17 / Fluid pressure drop / kPa / 14
Tubes/fins/connections / Cu / Al / Fe / Connection type / Threaded (Left)
Coil frame / Standard / Connection size / 1"
Tube thickness / mm / 0.35 / Fin spacing / mm / 2.0
Tube diameter / mm / 12.45 / Fin thickness / mm / 0.12
Face velocity / m/s / 2.51
FAN
Fan type / THLZ 355 FF A
Fan arrangement / Single / Installed motor power / kW / 3.00
Air volume / m3/s / 1.95 / Motor / Run
Fan outlet velocity / m/s / 9.50 / Motor efficiency class / EFF2
System effect / Pa / 27 / Motor speed / rpm / 1500
External static pressure / Pa / 300 / Voltage / V / 400/690
Total static pressure / Pa / 782 / Current / A / 6.2
Dynamic pressure / Pa / 54 / Absorbed motor power / kW / 2.76
Total pressure / Pa / 836
Fan speed / rpm / 2264
Efficiency / % / 79
Fan shaft power / kW / 2.05
Fan sound data SWL / Hz / 63 / 125 / 250 / 500 / 1k / 2k / 4k / 8k
Total / Inlet dB / 87 / 87 / 87 / 84 / 83 / 79 / 75 / 66
Outlet dB / 94 / 91 / 89 / 82 / 81 / 78 / 74 / 65
Opening, width x height / mm / 440 x 440 / Provided with:
Pressure drop / Pa / 0 / Opening product / Duct spigot
FAN EXTRAS
Drive guard - closed
ACCESS
Access type / Door / Viewport / Included
Access side / Left
EXTRAS
1 x Light armature, Bulleye PH-PL 9 Watt - 230V, incl. wiring / 1 x Light switch, incl. wiring to armature
1 x Isolator, 6P 16A - 2.2 to 7.5 kW, incl. wiring to motor

Page 1 of 51