Number 2067

Category C

Issue No. 1

Date 02/01/07

Page 1 of 5

Testing RCD Protected Extension Leads with Supernova, Europa or Primetest 300

These extension leads will of course fail the Insulation Test.

The Code of Practice says to do a leakage test instead of the insulation test.

The test procedure can be done in two ways either as a manual test or an edited automatic test.

The manual procedure is as described in the Instruction Manual and selecting the test procedure to be done.

Supernova/Europa

1a) Set an automatic procedure where you encounter a lot of these types of connections.

2a) To add an automatic test then go into ‘SET UP’ from the main menu.

3a) Highlight ‘Edit Test Settings’ and press ‘Yes’.

4a) In the ‘Select Test Settings’ window scroll down the list.

5a) Find a sequence that you do not use.

6a) Open this sequence by highlighting it and pressing the ‘Yes’ button.

7a) Press the down arrow key to take the highlight to the top of the screen.

8a) Continue to press until the highlight is on ‘Earth Bond’.

9a) Press the green ‘Yes’ key.

10a) This will take you into the Earth Bond Test procedure.

11a) The left hand column is highlighted at the top ‘Output’.

12a) Ensure that the ‘25A’ is selected and shown highlighted.

13a) If not then press the up or down arrow to get this.

14a) The next column is the ‘Limit’ and should show the correct value for the leads.

15a) If not then press the right arrow button to move across to the column.

16a) Use the up/down arrow button to select the value. (We use the value 0.1 Ohm).

17a) The ‘Duration’ column should show ‘5s’ for the time for the test.

18a) The ‘Number’ column should show ‘1’ for the number of tests to be carried out.

19a) Check the details are correct then press the button underneath the screen ‘OK’.

20a) This takes you back to ‘Test Settings Editor’.

21a) Press the down arrow and scroll down to ‘Insulation’.

22a) Press the green ‘Yes’ key.

23a) This will take you into the Insulation Test procedure.

24a) The left hand column is highlighted at the top ‘Output’.

25a) Ignore this column and press the right arrow button to move to ‘Limit’ column.

26a) This needs to be set to skip if not so already.

27a) Use the up or down arrow key to get this.

28a) Check the details are correct then press the button underneath the screen ‘OK’.

29a) This takes you back to ‘Test Settings Editor’.

30a) Press the down arrow and scroll down to ‘Leakage’.

31a) Press the green ‘Yes’ key.

32a) The left hand column is highlighted at the top ‘Output’.

33a) Press the right arrow button to move across to the limit column.

34a) Use the up or down arrow key to select ‘0.75mA’.

35a) The ‘Duration’ column should show ‘5s’ for the time for the test.

36a) The ‘Number’ column should show ‘1’ for the number of tests to be carried out.

37a) Check the details are correct then press the button underneath the screen ‘OK’.

38a) This takes you back to ‘Test Settings Editor’.

39a) Press the down arrow and scroll down to ‘Polarity’.

40a) Press the green ‘Yes’ key and you will see the line change.

41a) Ensure it shows “Skip”.

42a) Press the down arrow and scroll down to ‘Name:’.

43a) Press the green ‘Yes’ key and you will see the line change.

44a) Press the key with the arrow pointing left and do so until the line is cleared.

45a) Enter the name you want for this test procedure.

46a) Press the button underneath the screen ‘OK’.

47a) This takes you back to the screen ‘Select Test Settings’.

48a) Press the red ‘No’ key to go back to the ‘Main Menu’ to complete.

49a) Before doing the test connect the LT1000 unit into the test circuit.

Primetest 300

2b) To add an automatic test then go into ‘Configuration’ from the main menu.

3b) Press ‘F4’ to go straight into ‘Edit Test Sequence’.

4b) Scroll down to the test sequence list for to one of the standard lead tests.

5b) Press 'F3' for 'Options'.

6b) In the options list scroll to 'Copy Sequence'

7b) This will copy the sequence placing it at the bottom of the test sequence list.

8b) Press 'F4' to edit the sequence and it will open with the title line highlighted.

9b) Press 'F4' to edit the name and enter the new name for the test sequence.

10b) Press 'F4' twice to get this accepted.

11b) This takes you back to the sequence.

12b) Scroll down the list and you will see 'Visual', 'IEC Lead Continuity '.

13b) Ensure the value is correct to cover the length of leads you will be testing.

14b) This can be changed by highlighting the procedure and press 'F4' to 'Edit'.

15b) The duration and p/f (pass/fail) limit can now be altered.

16b) Scroll down again until the 'Insulation Test' is highlighted.

17b) Obviously this needs to be removed.

18b) Press 'F3' to delete the procedure and 'F4' to confirm deletion.

19b) This procedure needs to be replaced.

20b) Scroll down to the next line and press 'F1' to insert a new test procedure.

21b) The next boxshows the type of tests.

22b) Press the right arrow key to get a partial list of the procedures.

23b) Scroll down this list to the 'Touch Leakage Test'.

24b) Press 'F4' to insert theprocedure and in the next box are thevalues.

25b) These values can be adjusted to the required level.

26b) The p/f limit should be '0.75'.

27b) Press 'F4' to ok this and it is added to the list of procedures.

28b) The polarityprocedure is still required.

29b) Press 'F2' to escape and it will ask for confirmation of saving the changes.

30b) Press 'F4' to accept.

31b) The new test sequence is in the list of sequences ready for use.