Data Pro Forma

Essential Services Data

Facility Name and Location:

Agency/Region:

Management Contact Person: Ph:

Engineering Contact Person: Ph:

Service / Details Required / Primary Source / Fuel / Emergency Option / Fuel / Backup /
Electricity / Provider / N/A
Av. Demand (kW)
Gas / Provider / N/A
Av. Demand (MJ/day)
Water / Provider / N/A
Av. Demand (kL/day)
Sewage / Provider
Av. Demand (kl/day)
Communications / Provider / N/A
Steam
Av. Demand (kW)
Medical Air / Provider
Av. Demand (l/day)
Linen / Provider
Av. Demand (kg/day)
Food / Provider
Demand (meals/day)
UPS to all critical equipment/areas / YES/NO
If NO, list deficiencies

* Av Demand – An estimate of the typical load on the facility excluding peaks and troughs.

Data Pro Forma

Essential Engineering Services Data

Facility Name and Location: Frankston Hospital, Hastings Road, Frankston

Agency/Region: Metropolitan - South

Management Contact Person: CEO, Ms Cherie Devison Ph: 9784 7777

Engineering Contact Person: Bruce Gilpin Ph: 9784 7855

Service / Details Required / Primary Source / Fuel / Emergency Option / Fuel / Backup /
Electricity / Provider / Citipower / N/A / 2 x 350 kW generators / Diesel / Connection points for portable gen.
Av. Demand (kW) / 1,600 kW / Essential Loads (kW): 500 kW
Comments: 1 generator skid mounted, easily relocatable.
Gas / Provider / TXU / N/A / SNG plant / LPG / Connection points for bottled LPG
Av. Demand (MJ/day) / 30 / 5 MJ/day
Water / Provider / CitiWest / N/A / Underground tanks / Electric Pumps / Connections for tanker supplies
Portable generator for pumps.
Av. Demand (kL/day) / 30 / Capacity 20 kl
Sewage / Provider / CitiWest / Elec. Pumps / Tanker disposal / Overflow to street.
Portable generator for pumps.
Av. Demand (kl/day) / 30 / 0.25kW
Communications / Provider / Telstra PABX / Mains elec; Battery back-up / Secondary switchboard / Mains elec; Battery back-up / Mobile phones; runners
Inter campus microwave link / Mains elec; Battery back-up
Steam / 2 x 300 kW boilers
2 x 150 kW boilers / Gas / 1 x 300 kW boiler dual fuel / Diesel / Bottled LPG
Av. Demand (kW) / 600 / 300
Medical Air / Provider / Air Liquide 4,000l tank / N/A / Bottled supplies / N/A
Av. Demand (l/day) / 300
Linen / Provider / Warrugal Linen / Gas / ALSCO / Austin
Av. Demand (kg/day) / 500
Food / Provider / Western Hospital / Gas / Skilled Meals
Demand (meals/day) / 1,000
UPS to all critical equipment/areas / YES/NO
If NO, list deficiencies / No
Deficient in Theatre #4 Day surgery