Section Cover Page
Section 260010
2010-11-01 Electrical General Requirements

Use this Section to specify:

.1 General cross references required for coordination of Division 26 (electrical work) with related requirements and related work specified in other parts of the project specifications.

.2 General requirements which are common to most or all other Sections in Division 26.

This Master Specification Section contains:

.1 This Cover Sheet

.2 Data Sheet Specification Coordination

.3 Specification Section Text:

1. Related Requirements

2. Related Work

3. Products Supplied But Not Installed Under This Division

4. Products Installed But Not Supplied Under This Division

5. Connection of Work Provided Under Other Divisions

6. Electrical Utility Service Connections

7. Shop Drawings, Product Data and Samples

8. Project Record Drawings

9. Regulatory Requirements

10. Certificates

11. Reference Documents

12. Cleaning

BMS Basic Master Specification
Alberta Infrastructure
Master Specification System / Page 0
Data Sheet - Specification Coordination
Section 260010
2010-11-01 Electrical General Requirements

Specification Hierarchy:

.1 Division 01 specifies general requirements applicable to all of the work of the Contract.

.2 This Section260010 supplements Division 01 general requirements with general requirements applicable to most or all electrical work only. Do not repeat, in this Section, general requirements which are specified in Division01.

.3 Each Division26 technical Section specifies requirements applicable to the work of that Section. Do not repeat in technical Sections, general requirements which are specified in Division01 or in this Section.

.4 With respect to the foregoing, crossreference from the specific to the general, ie. each technical Section references this Section, this Section in turn references Division01 Sections.

Interdivisional Specification Coordination:

.1 Related Requirements:

.1 Specify under this article heading, crossreferences to general requirements specified elsewhere, but which are also applicable to the electrical work. This will primarily include general "administrative" type requirements specified in Division 01.

.2 Related requirements which are of particular importance to the electrical work may be highlighted by placing them under their own article heading eg. Product Options and Substitutions.

.2 Related Work:

.1 Specify under this article heading, crossreferences to work which is specified outside of Division 16 but which is directly related to the electrical work.

BMS Basic Master Specification
Alberta Infrastructure
Master Specification System / Page 02
Data Sheet - Specification Coordination (Cont'd)
Section 260010
2010-11-01 Electrical General Requirements

.3 Products Supplied but Not Installed Under This Division:

.1 Specify under this article heading each item of work supplied by the electrical subcontractor but which is installed by others. Also specify for each such item, the Division number or, if practicable, the Section number, wherein the installation of that item is specified.

.2 Coordinate with other disciplines as necessary to ensure that list of items and crossreferencing are comprehensive and accurate.

.4 Products Installed but Not Supplied Under This Division:

.1 Specify under this article heading each item of work requiring installation by the electrical subcontractor but which is supplied by others. Also specify for each such item, the Division number or, if practicable, the Section number, wherein the supply of that item is specified. Eg:

Electrical control devices and control panels for electric door operators supplied under Division 08.

Line voltage control devices supplied under Division 23.

Thermostats supplied under Division 23.

Etc.

.2 Coordinate with other disciplines as necessary to ensure that list of items and crossreferences are comprehensive and accurate.

.5 Connection of Work Provided Under Other Divisions:

.1 Specify under this article heading a crossreference to a separate Section ie. Section 262790 Connection of Equipment, which should contain a comprehensive list or schedule of equipment supplied and installed under other Divisions but requiring electrical connection by the electrical subcontractor.

END OF DATA SHEETS

BMS Basic Master Specification
Alberta Infrastructure
Master Specification System / Page 02
Section 260010
Plan No: Electrical General Requirements
Project ID: Page 4

1. RELATED REQUIREMENTS

.1 Summary of Work: Division01.

.2 Coordination: Division01.

.3 Regulatory Requirements: Division01.

.4 Submittals: Division01.

.5 Quality Control: Division01.

.6 Temporary Power: Division01.

.7 Product Options and Substitutions: Division01.

.8 [ :] Section[.]

2. RELATED WORK

.1 Concrete for electrical work: Section033000.

.2 Site painting of electrical work: Section099130.

.3 Trench Excavating and Backfilling: Section312338.

.4 [ ]: Section[ ].

3. PRODUCTS SUPPLIED BUT NOT INSTALLED UNDER THIS DIVISION

.1 Supply access doors and panels where required for access to electrical work in otherwise inaccessible ceilings, walls and floors. Supply such access doors and panels for installation under [Division [03], [04], and [09]] [Section].

SPECNOTE:Access panels may be in concrete (Div.03), masonry (Div.04), or gypsum board or plaster (Div.09). Edit accordingly.

.2 Supply plaster trims or frames for lighting fixtures, for installation under [Division 09] [Section ].

.3 Supply [ ] for installation under [Division ] [Section ].

.4 Supply [ ] for installation under [Division ] [Section ].

4. PRODUCTS INSTALLED BUT NOT SUPPLIED UNDER THIS DIVISION

.1 Install [ ] which are supplied under [Division ] [Section ].

.2 Install [ ] which are supplied under [Division ] [Section ].

.3 Install [ ] which are supplied under [Division ] [Section ].

.4 Install [ ] which are supplied under [Division ] [Section ].

.5 Install [ ] which are supplied under [Division ] [Section ].

5. CONNECTION OF WORK PROVIDED UNDER OTHER DIVISIONS

.1 Refer to Section 262790Connection of Equipment, for requirements pertaining to electrical connection of equipment supplied and installed under other Divisions.

SPECNOTE:Specify in a separate Section, as referenced, a comprehensive list or schedule of equipment requiring electrical connection and requirements related thereto.

6. ELECTRICAL UTILITY SERVICE CONNECTIONS

.1 Refer to Division 01 for requirements pertaining to utility service connections.

7. SHOP DRAWINGS, PRODUCT DATA AND SAMPLES

.1 Comply with requirements of Division 01.

.2 Submit shop drawings, product data and samples as specified, indicating details of construction, dimensions, capacities, weights and electrical performance characteristics of equipment and materials. Include data on manufacturer's recommended environmental conditions for equipment affected by temperature and humidity.

.3 Provide wiring, single line and schematic diagrams for electrical control systems and where otherwise applicable. Include wiring drawings or diagrams showing interconnection among work of different Sections.

.4 Shop drawings shall be mylar based, drawn in ink, professional quality drafting, same size and format as Contract drawings.

.5 Cross or block out from manufacturer's standard product data sheets all data inapplicable or irrelevant to project.

.6 All component identification numbers for communications equipment shall be generic.

8. PROJECT RECORD DRAWINGS

.1 Comply with requirements of Division 01.

.2 Record actual locations of all pull boxes, feeders, electrical equipment.

.3 Record any changes to branch circuit designations.

9. REGULATORY REQUIREMENTS

.1 Comply with Safety Codes Act and rules and regulations made pursuant thereto, including Canadian Electrical Code.

.2 Unless otherwise indicated, all references in the Contract Documents to "Canadian Electrical Code" or "CEC" shall mean the edition of the Canadian Electrical Code, Part I, CSA C22.1 and the variations made thereto by Alberta regulation, which are in force on the date of bid closing for the Contract.

.3 All electrical products shall be tested, certified and labelled in accordance with a certification program accredited by the Standards Council of Canada. Where a product is not so labelled, provide written approval by the authority having jurisdiction.

.4 Submit to authority having jurisdiction and utility company, necessary number of drawings and specifications for examination and approval prior to commencement of electrical work. Pay associated fees.

.5 Submit to Minister, copy of electrical permit obtained from authority having jurisdiction.

10. CERTIFICATES

.1 If authority having jurisdiction conducts an electrical inspection, submit copy of certificate of acceptance provided by authority having jurisdiction.

11. REFERENCE DOCUMENTS

.1 Comply with applicable standards of following organizations:

.1 Electrical and Electronic Manufacturers Association of Canada (EEMAC).

.2 National Electrical Manufacturers Association.(NEMA).

.3 Institute of Electrical and Electronic Engineers (IEEE).

.4 Insulated Power Cable Engineers Association (IPCEA).

12. CLEANING

.1 Do the following prior to Interim Acceptance of the Work, as required to remove all construction dust and debris:

.1 Clean out all cabinets and enclosures with vacuum or compressed air.

.2 Wipe all insulators with clean, dry rags.

.3 Clean all luminaires, with vacuum or clean dry rags.

END OF SECTION