ADCC, Inc. STRUCTURED CABLING SYSTEMS - PRE-BID AND JOB COMPLETION CHECK LIST

Customer Name: ______Date of Site Visit: ______

Site address:______

City, State, Zip:______

Contact name:______

Contact phone number:______

Pre-bid completed by:______

Job Completion completed by:______

Number of Buildings: ______Number floors per building:______

Number of Closets per building: ______Per Floor ______

Number of Copper locations to becabled ______Number cables per outlet ______Avg. Wire Run length _____

Installation is: Copper Only ______Fiber Only ______Copper & Fiber ______

Type of fiber and strand count (s)______Length (s)______

Installation is to conformto the EIA/TIA Standards and NEC Code for:

Category 5e_____ Category 6_____T568A _____ T568B _____ Fiber ______

1.Check here if Conduits are used for horizontal distribution______

Conduits are no longer than 100 feet, with two orfewer 90 degree bends between pulling points

______

Inside bend radius is no greater than 6 times the conduit diameter

(10 times for conduits 2” and over).______

2.Check here if Ceiling Space is used for horizontal distribution______

All horizontal cables are plenum rated.______

Cables are not laying directly on ceiling tiles or T-bars.______

Cable support devices (J hooks, rings) are in use and arespaced no more than 5 feet apart. ______

  1. Twisted Pair Cable Terminations

Outlets are installed right side up. ______

Cables are not wrapped or twisted around mounting collars.______

Correct connectors used (T568A/T568B).______

The jackets are maintained right up to the connectors.______

Pairs are terminated in the correct positions.______

Check here if Patch Panels are installed.______

Cables are properly routed and dressed.______

Jackets remain up to edge of connecting blocks.______

Pairs are terminated in the correct positions.______

Twists are maintained, and are undistortedto the point of termination.______

Check here if 110 Patch Panels are installed.______.

Cables are terminated in the correct positions.______

Pairs are terminated in the correct positions.______

There is no visible conductor insulation damage______

Pair twists are maintained up to the point of termination.______

Bends in pairs are tight and conductors are not spread apart.______

Check here if any Consolidation Points exist.______

There is only one consolidation point or Multi-User TOto any horizontal link.______

4.Labeling is complete and accurate at all work area outlets, alltelecommunication closets, and in all equipment rooms. ______

5.Check here if intra-building Backbone Cables are installed.______

All twisted pair backbone cable shields are properly grounded at both ends.______

Unshielded backbone cables are tie-wrapped to a 6AWGinsulated wire at regular intervals and the 6AWG wire(coupled bonding conductor) is properly grounded at bothends. ______

6.Check here if inter-building Backbone Cables are installed.______

All pairs in twisted pair inter-building backbone cables areequipped with approved gas tube or solidstate overvoltage protection at both ends. ______

(Make sure no digital modules for analog use are installed)

Ground lugs on protector panels are properly connected toan acceptable ground with 6AWG conductors. ______

All twisted pair cable shields are properly grounded atboth ends.______

Metallic elements of fiber optic cables are properlygrounded at both ends.______

7).Hanging supports are within 5 ft. (1.5 meters) centers.______

Cable spans between hanging supports exhibit visible sagas an indication of acceptable tension. ______

Visible sag is seen between hanging supports.______

Tie wraps are tight enough to snugly hold cables together, but do not deform cable jackets. ______

Cable bends in outlet boxes are no tighter than 0.87 inch______

Cable folds are no greater than 90 degrees.______

Cables in outlet boxes are not longer than 1 foot.______

In high-density patch panel terminations, cables are routedsuch that 12 cables are terminated on the left side of thepanel and 12 cables are terminated on the right side of thepanel.______

8. Modular Outlets

Conductors are seated according to color chart on the outlet.______

Caps are seated securely on top of the conductors.______

Jacket is maintained as close as possible to the outlet.______

Open loops are not in evidence in outlet channel.______

Pair twist is maintained right up to the point of termination.______

9.Fiber Terminations

All fiber cables are properly routed and secured.______

At all termination locations, fiber slack is properly stored, withoutexceeding minimum bend radius. ______

Fiber connectors have been properly installed.______

10.Testing

All pairs in all twisted pair cables have been tested for continuity and position.______

Documentation of the test results is available.______

All connector zed fibers have been tested for continuity,position and loss.______

Documented loss requirements and test results availablefor each fiber______

Each fiber’s measured loss meets or exceeds the designrequirements.______

Additional information about site: