SECTION16361

SECONDARYUNITSUBSTATION

PART 1 - GENERAL

1.1SCOPE

A.Thisspecificationprovidesthetechnicalrequirementsforan[indoor][outdoor]secondaryunitsubstationcompletefromtheincominglineterminalstotheoutgoingfeederterminals. Thecontractorshallprovidedandinstallallcomponentsasspecifiedhereinandshownonrelatedelectricaldrawings.

1.2RELATEDDOCUMENTS

A.AlloftheContractDocuments,includingGeneralandSupplementaryConditionsandDivision1GeneralRequirements,applytotheworkofthissection.

B.OtherSpecificationSectionsthatdirectlyrelatetotheworkofthissectioninclude,butarenotlimitedto,thefollowing:

1.[Section16290-ElectricalPowerMonitoringandControl]

2.[Section16341–MediumVoltageFusedInterrupter][Section 16341 – Medium Voltage Circuit Breaker Switchgear]

3.[Section16271–[DryTypeUnitSubstationTransformer][CastCoilUnitSubstationTransformer][OilFilledUnitSubstationTransformer]

4.[Section16441–Switchboards][Section16430–LowVoltageSwitchgear]

1.3SUBMITTALS

A.SubmitshopdrawingsandproductdataforapprovalandfinaldocumentationinthequantitieslistedaccordingtotheConditionsoftheContract. Alltransmittalsshallbeidentifiedbycustomername,customerlocationandcustomerordernumber.

B.DocumentsforApproval:One-linediagrams,dimensionedplans,sectionsandelevationsshowingminimumclearances,installeddevices,majorfeatures,nameplatelegendsandbillsofmaterial.

C.FinalDocuments:Recorddocumentationtoincludethosein1.3.Bandwiringdiagrams,single-lineandthree-linediagramsofswitchgearbusandcomponentconnections,productdataofaccessoriesorpartsnotpreviouslydescribedinthedrawings,listofrecommendedsparepartsandinstructionandinstallationmanuals

D.ProductData:Includefeatures,characteristicsandratingsofswitches,fusesandothercomponents,time-currentcharacteristiccurvesforpowerfusesandanyovercurrentdevices.

E.ShopDrawings:Detailequipmentassembliesandindicatedimensions,weights,requiredclearances,methodoffieldassembly,componentsandlocationandsizeofeachfieldconnection. Includethefollowing:

1.Enclosuretypeanddetails.

2.Nameplatelegends.

3.Busconfigurationwithsizeandnumberofconductorsineachbusrun,includingphase,neutralandgroundconductorsofmainandbranchbuses.

4.Currentratingsofbuses.

5.Short-timeandshort-circuitratingsofswitchgearassembly.

6.[Mimicbusdiagram.]

7.WiringDiagrams:Detailwiringforpower,signalandcontrolsystemsanddifferentiatebetweenmanufacturer-installedandfield-installedwiring.

1.4RELATEDSTANDARDS

A.Complywithrequirementsoflatestrevisionsofapplicableindustrystandards,specificallyincludingthefollowing:

1.ANSI/IEEE

2.NEMA

3.UL

1.5QUALITYASSURANCE

A.ManufacturerQualifications:Engageafirmwithatleast5yearsexperienceinmanufacturingswitchgear.

1.6DELIVERY,STORAGEANDHANDLING

A.Deliverproductsinfactorylabeledpackages. Shippinggroupsshallnotexceed15ft.inlength.

B.Storeandhandleinstrictcompliancewithmanufacturer’sinstructionsandrecommendations. Protectfrompotentialdamagefromweatherandconstructionoperations. Storesocondensationwillnotformonorinswitchgearandifnecessary,applytemporaryheatwhererequiredtoobtainsuitableserviceconditions.

PART 2 - PRODUCTS

2.1MANUFACTURERS

A.[ProvidetheentireunitsubstationbySiemensEnergyandAutomation,Inc.or pre-approved equal. Approved manufacturers are as follows:

1.SIEMENS

2.. ]

2.2GENERALREQUIREMENTS

A.Construction:

1.Theunitsubstationconsistofa:

a.[MediumVoltageFusedDisconnect]

b.[DryTypeUnitSubstationTransformer][CastCoilUnitSubstationTransformer][OilFilledUnitSubstationTransformer]

c.[LowVoltageSwitchboard][LowVoltageSwitchgear]

2.3COMPONENTS

A.[MEDIUMVOLTAGEFUSEDDISCONNECT][GISSWITCHGEAR]

1.InsertMediumVoltageSpechere.

B.[DRYTYPEUNITSUBSTATIONTRANSFORMER][CASTCOILUNITSUBSTATIONTRANSFORMER][LIQUIDFILLEDUNITSUBBSTATIONTRANSFORMER]

1.InsertTransformerSpechere.

C.[LOWVOLTAGESWITCHBOARD][LOWVOLTAGESWITCHGEAR]

1.InsertSwitchboard/SwitchgearSpechere.

PART 3 - EXECUTION

3.1INSTALLATION

A.General:Electricalcontractortoinstallmetal-cladswitchgearinaccordancewithmanufacturer’swritteninstructionsandthefollowingspecifications.

B.Installandanchorswitchgearinaccordancewithmanufacturer’sinstructions.

C.Tightenbusjoints,electricalconnectorsandterminalsaccordingtomanufacturer'spublishedtorque-tighteningvalues.Installequipmentgroundingconductorsforswitchgearwithgroundcontinuitytomainelectricalgroundbus.

3.2ADJUSTMENTS AND CLEANING

A.Manufacturer'sFieldServices:Engageafactory-authorizedservicerepresentativetoinspectfield-assembledcomponents,installationandconnectionofswitchgear;andtopretestandadjustswitchgearcomponents. Reportresultsinwriting.

B.Setfield-adjustable,protective-relaytripcharacteristics.

C.Cleanexposedsurfacesusingmanufacturerrecommendedmaterialsandmethods. Touch-updamagedcoatingandfinishesusingnon-abrasivematerialsandmethodsrecommendedbymanufacturer. Eliminateallvisibleevidenceofrepair.

3.3TESTING

A.Testing:Afterinstallingswitchgearandafterelectricalcircuitryhasbeenenergized,demonstrateproductcapabilityandcompliancewithrequirements.

B.Procedures: Performinspectionsandtestsspecifiedbelow. Reportvaluesthatdonotmeetmanufacturer'swrittenrecommendations. Certifycompliancewithtestparameters.

1.Switchgear: PerforminspectionsandtestsstatedinNETAATS,Section7.1.

2.InstrumentTransformers: PerforminspectionsandtestsstatedinNETAATS,Section7.10.

3.MeteringandInstrumentation: PerforminspectionsandtestsstatedinNETAATS,Section7.11.

4.Ground-FaultSystems: PerforminspectionsandtestsstatedinNETAATS,Section7.14.

5.BatterySystems: PerforminspectionsandtestsstatedinNETAATS,Section7.18.

6.SurgeArresters: PerforminspectionsandtestsstatedinNETAATS,Section7.19.

7.Removeandreplacemalfunctioningunitswithnewunitsandretest.

3.4WARRANTY

A.Equipment manufacturer warrants that all goods supplied are free of non-conformities in workmanship and materials for one year from date of initial operation, but not more than eighteen months from date of shipment.

3.5[STARTUPSERVICES]

A.[Engageafactory-authorizedservicerepresentativetoperformstartupservice.]

B.[TrainOwner'smaintenancepersonnelonproceduresandschedulesforenergizingandde-energizing,troubleshooting,servicingandmaintainingequipmentandschedules.]

C.[VerifythatswitchgearisinstalledandconnectedaccordingtotheContractDocuments.]

D.[Verifythatelectricalcontrolwiringinstallationcomplieswithmanufacturer'ssubmittalbymeansofpoint-to-pointcontinuitytesting. VerifythatwiringinstallationcomplieswithrequirementsinDivision16Sections.]

E.[Completeinstallationandstartupchecksaccordingtomanufacturer'swritteninstructions.]

ENDOFSECTION

October 4, 2018[Project Name]

Secondary Unit Substations16361-1