SECTION074114
STANDING-SEAMMETALROOFPANELS
PART1-GENERAL
1.1RELATEDDOCUMENTS
A.DrawingsandotherContractDocuments,listedintheagreementbetweentheOwnerandContractor,applytothisSection.
1.2SUMMARY
A.Sectionincludesstanding-seammetalroofpanels.
1.3PREINSTALLATIONMEETINGS
A.Pre-installationConference:ConductconferenceatProjectsite.
1.4DESIGN AND PERFORMANCE REQUIREMENTS
A.Complete engineered system by manufacturers engineering department including
B.Design Load:
1.Calculate wind uplift using ASCE-‘10
2.Calculate clip spacing
3.Verify stress and deflection of panel meet project design load
4.Verify project design loadconditions with ASTM 1592
5.Verify project design load conditions with UL580 class 90
C.Panels must be able to be tapered
D.Panels must be able to be tapered
E.Panels may be factory curved down to a 5’ radius
F.Panels may be gravity curved on the jobsite down to 25’ radius
G.UL-Approved Rated Fire Roofs:
1.1, 1 ½ and 2 hour fire-rated assemblies per UL construction numbers P225, P510, P514, P516, P701 and P715
H.UL90 Rating:
1.24 ga. ”steel panels installed over 1/2” plywood spaced at maximum of 2'-0" o.c.
2.24. ga. 18” steelpanels spaced a maximum of 2’-0" o.c. installed over 22 ga. metal deck and up to 6" of rigid insulation and bearing plates to support clips.
I.ASTM 1592:
1.24 ga. Steel Panels:
a.59.39 psf @ 1’-3”
2.42.42 psf @ 2’-6”
1.1SUBMITTALS
A.ProductData:Foreachtypeofproduct.
1.Includeconstructiondetails,materialdescriptions,dimensionsofindividualcomponentsandprofiles,andfinishesforeachtypeofpanelandaccessory.
B.ShopDrawings:
1.Includefabricationandinstallationlayoutsofmetalpanels;detailsofedgeconditions,joints,panelprofiles,corners,anchorages,attachmentsystem,trim,flashings,closures,andaccessories;andspecialdetails.
2.Accessories:Includedetailsoftheflashing,trim,andanchoragesystems,atascaleofnotlessthan1-1/2inchesper12inches.
3.IfaWTWisrequired,shopdrawings or Fabrals standard detailsmustbereviewedbythemanufacturerpriortoinstallation
C.Samples:Foreachtypeofexposedfinishrequired,preparedonSamplesofsizeindicatedbelow.
1.MetalPanels:12incheslongbyactualpanelwidth.Includeclips,fasteners,closures,andothermetalpanelaccessories.
2.IncludesimilarSamplesoftrimandaccessoriesinvolvingcolorselection.
D.QualificationData:ForInstaller.
E.ProductTestReports:Foreachproduct,fortestsperformedbyaqualifiedtestingagency.
F.Fieldquality-controlreports.
G.SampleWarranties:Forspecialwarranties.
H.MaintenanceData:Formetalpanelstoincludeinmaintenancemanuals.
1.2QUALITYASSURANCE
A.InstallerQualifications:[Anentitythatemploysinstallersandsupervisorswhoaretrainedandapprovedbymanufacturer.][Installerofsheetmetalroofingforaminimumof10yearsdocumentedexperience.]
B.PanelManufacturer:Minimum of10yearsexperienceinmanufacturingarchitecturalroofpanelsinapermanentstationaryindoorfacility.Providefacilityinformationifrequested.
1.3DELIVERY,STORAGE,ANDHANDLING
A.Delivercomponents,metalpanels,andothermanufactureditemssoasnottobedamagedordeformed.Packagemetalpanelsforprotectionduringtransportationandhandling.
B.Unload,store,anderectmetalpanelsinamannertopreventbending,warping,twisting,andsurfacedamage.
C.Storepanels,flashingsandaccessoriesionasafe,dryenvironmentunderawaterproofbreathablecoveringtopreventwaterdamage.Allowforadequateventilationtopreventcondensation.Panelsandflashingswithstrippablefilmshallnotbestoredindirectsunlight.
D.Removestrippableprotectivecoveringonmetalpanelsduringinstallation.
E.Uponreceiptofdeliveryofmetalpanelsystem,andpriortosigningthedeliveryticket,theinstalleristoexamineeachshipmentfordamageandforcompletionoftheconsignment.
1.4FIELDCONDITIONS
A.WeatherLimitations:Proceedwithinstallationonlywhenexistingandforecastedweatherconditionspermitassemblyofmetalpanelstobeperformedaccordingtomanufacturers'writteninstructionsandwarrantyrequirements.
1.5COORDINATION
A.Coordinatesizesandlocationsofroofcurbs,equipmentsupports,androofpenetrationswithactualequipmentprovided.
B.Coordinatemetalpanelinstallationwithraindrainagework,flashing,trim,constructionofsoffits,andotheradjoiningworktoprovidealeakproof,secure,andnoncorrosiveinstallation.
1.6WARRANTY
A.MaterialandWorkmanshipWarranty:Manufactureragreestorepairorreplacecomponentsofmetalpanelsystemsthatfailinmaterialsorworkmanshipwithinspecifiedwarrantyperiod.
1.Failuresinclude,butarenotlimitedto,thefollowing:
a.Structuralfailuresincludingrupturing,cracking,orpuncturing.
b.Deteriorationofmetalsandothermaterialsbeyondnormalweathering.
2.WarrantyPeriod:TwoyearsfromdateofSubstantialCompletion.
B.PaintFinishWarranty:30yearsfromdateofSubstantialCompletion.Ifmetalliccolorsareused,the“fade”partofthewarrantyshallberemoved.
1.30yearsforKynartypefinish.
2.20yearsforMetallic/Micafinish,Customfinish
C.Installer’sWarranty:Submitinstaller'swarranty,signedbyInstaller,coveringtheWorkofthisSection,includingallcomponentsofroofpanelsforthefollowingwarrantyperiod:
1.WarrantyPeriod:TwoyearsfromdateofSubstantialCompletion
D.Weather-tightWarranty:
1.WarrantyPeriod:TwentyyearsfromdateofSubstantialCompletion
PART2-PRODUCTS
2.1MANUFACTURER
2.2Fabral®Facilities:
Jackson,GA
Telephone:800.884.4484 Website:
Grapevine,TXTelephone:800.477.9066Website:
CedarCity,UT
Telephone:800.432.2725Website:
1.2STANDING-SEAMMETALROOF PANELS
SNAP ON SEAM
1.AZ50GalvalumeSteel:
a.MaterialGauge:[24][22]gauge.
b.ExteriorFinish:Asselectedfrommanufacturer’spremiumfinishes.
c.Color:Asselectedfrommanufacturer’sfullrange.
2.Aluminum:
a.MaterialThickness:[0.032][0.040]thick.
b.Surface:[Smooth,flat][StuccoEmbossed]finish.
c.ExteriorFinish:Asselectedfrommanufacturer’spremiumfinishes.
d.Color:Asselectedfrommanufacturer’sfullrange.
3.RibSpacing:Manufacturer’sstandard.
4.PanelCoverage:[12][16][18]inches.
5.PanelHeight: inch.
6.AZ50GalvalumeSteel:
a.MaterialGauge:[24][22]gauge.
b.ExteriorFinish:Asselectedfrommanufacturer’spremiumfinishes.
c.Color:Asselectedfrommanufacturer’sfullrange.
2.1MATERIALS
A.Metallic-CoatedSteelSheet:aluminum-zincalloy-coatedsteelsheet (Galvalume)complyingwithASTMA792/A792M,ClassAZ50/AZ55coatingdesignation;structuralquality.Pre-paintedbythecoil-coatingprocesstocomplywithASTMA755/A755M.
B.AluminumSheet:Coil-coatedsheet,ASTMB209,alloyasstandardwithmanufacturer,withtemperasrequiredtosuitformingoperationsandstructuralperformancerequired.
2.2MISCELLANEOUSMATERIALS
A.MiscellaneousMetalSub-framingandFurring:Providemanufacturer'sstandardsectionsasrequiredforsupportandalignmentofmetalpanelsystem.
B.PanelAccessories:Providecomponentsrequiredforacomplete,weather-tightpanelsystemincludingtrim,copings,fasciae,mullions,sills,cornerunits,panelclips,flashings,sealants,gaskets,fillers,panelclosures,andsimilaritems.Matchmaterialandfinishofmetalpanelsunlessotherwiseindicated.
C.FlashingandTrim:Provideflashingandtrimformedfromsamematerialasmetalpanelsasrequiredtosealagainstweatherandtoprovidefinishedappearance.Locationsinclude,butarenotlimitedto,eaves,rakes,corners,bases,framedopenings,ridges,fasciae,andfillers.Finishflashingandtrimwithsamefinishsystemasadjacentmetalpanels.
D.PanelFasteners:Self-tappingscrewsdesignedtowithstanddesignloads.
E.PanelSealants:Providesealanttyperecommendedbymanufacturerthatarecompatiblewithpanelmaterials,arenon-staining,anddonotdamagepanelfinish.
1.SealantTape:Buytl
2.JointSealant: One Part Poly
3.Butyl-Rubber-Based,Solvent-ReleaseSealant:ASTMC1311.
2.3FABRICATION
A.General:Providefactory-formedmetalroofpanelsystemcomplyingwithASTME1514requirements.
B.Providepanelprofile,includingmajorribsandintermediatestiffeningribs,ifany,forfulllengthofpanel.
C.Formpanelsincontinuouslengths,endlapsarenotpermitted.
D.Fieldformingofpanelsshallbedonebyfactoryemployeesoperatingthemachines.
E.Fabricatemetalpaneljointswithfactory-installedbutylsealantthatprovideaweathertightsealandpreventmetal-to-metalcontact,andthatminimizenoisefrommovements.
F.SheetMetalFlashingandTrim:Fabricateflashingandtrimtocomplywithmanufacturer'srecommendationsandrecommendationsinSMACNA's"ArchitecturalSheetMetalManual"thatapplytodesign,dimensions,metal,andothercharacteristicsofitemindicated.
1.Formexposedsheetmetalaccessoriesthatarewithoutexcessiveoilcanning,buckling,and
toolmarksandthataretruetolineandlevelsindicated,withexposededgesfoldedback toformhems.
2.SeamsforAluminum:Fabricatenonmovingseamswithflat-lockseams.Formseamsandsealwithepoxyseamsealer.Rivetjointsforadditionalstrength.
3.SeamsforOtherThanAluminum:Fabricatenonmovingseamsinaccessorieswithflat-lockseams.Tinedgestobeseamed,formseams,andsolder.
4.SealedJoints:Formnon-expansion,butmovable,jointsinmetaltoaccommodatesealantandtocomplywithSMACNAstandards.
5.Concealfastenersandexpansionprovisionswherepossible.Exposedfastenersarenotallowedonfacesofaccessoriesexposedtoview.
6.Fabricatecleatsandattachmentdevicesfromsamematerialasaccessorybeinganchoredorfromcompatible,noncorrosivemetalrecommendedinwritingbymetalpanelmanufacturer.
a.Size:AsrecommendedbySMACNA's"ArchitecturalSheetMetalManual"ormetalpanelmanufacturerforapplication,butnotlessthanthicknessofmetalbeingsecured.
2.4FINISHES
A.Protectmechanicalandpaintedfinishesonexposedsurfacesfromdamagebyapplyingastrippable,temporaryprotectivecoveringbeforeshipping.
B.AppearanceofFinishedWork:Variationsinappearanceofabuttingoradjacentpiecesareacceptableiftheyarewithinone-halfoftherangeofapprovedSamples.Noticeablevariationsinsamepieceareunacceptable.VariationsinappearanceofothercomponentsareacceptableiftheyarewithintherangeofapprovedSamplesandareassembledorinstalledtominimizecontrast.
A.SteelPanelsandAccessories:
1.Two-CoatFluoropolymer:AAMA621.Fluoropolymerfinishcontainingnotlessthan70percentPVDFresinbyweightincolorcoat.Prepare,pretreat,andapplycoatingtoexposedmetalsurfacestocomplywithcoatingandresinmanufacturers'writteninstructions.
2.MicaFluoropolymer:AAMA621.Two-coatfluoropolymerfinishwithsuspendedmicaflakescontainingnotlessthan70percentPVDFresinbyweightincolorcoat.Prepare,pretreat,andapplycoatingtoexposedmetalsurfacestocomplywithcoatingandresinmanufacturers'writteninstructions.
3.Three-CoatMetallicFluoropolymer:AAMA621.Three-coatfluoropolymerfinishwithsuspendedmetallicflakescontainingnotlessthan70percentPVDFresinbyweightinbothcolorcoatandcleartopcoat.Prepare,pretreat,andapplycoatingtoexposedmetalsurfacestocomplywithcoatingandresinmanufacturers'writteninstructions.
4.ConcealedFinish:Applypretreatmentandmanufacturer'sstandardwhiteorlight-coloredacrylicorpolyesterbackerfinishconsistingofprimecoatandwashcoatwithaminimumtotaldryfilmthicknessof0.5mil.
B.AluminumPanelsandAccessories:
1.Two-CoatFluoropolymer:AAMA2605.Fluoropolymerfinishcontainingnotlessthan70percentPVDFresinbyweightincolorcoat.Prepare,pretreat,andapplycoatingtoexposedmetalsurfacestocomplywithcoatingandresinmanufacturers'writteninstructions.
2.MicaFluoropolymer:AAMA2605.Two-coatfluoropolymerfinishwithsuspendedmicaflakescontainingnotlessthan70percentPVDFresinbyweightincolorcoat.Prepare,pretreat,andapplycoatingtoexposedmetalsurfacestocomplywithcoatingandresinmanufacturers'writteninstructions.
3.Three-CoatMetallicFluoropolymer:AAMA2605.Three-coatfluoropolymerfinishwithsuspendedmetallicflakescontainingnotlessthan70percentPVDFresinbyweightinbothcolorcoatandcleartopcoat.Prepare,pretreat,andapplycoatingtoexposedmetalsurfacestocomplywithcoatingandresinmanufacturers'writteninstructions.
4.ExposedAnodizedFinish:
a.ClearAnodicFinish:AAMA611,[AA-M12C22A41,ClassI,0.018mm][AA-M12C22A31,ClassII,0.010mm]orthicker.
b.ColorAnodicFinish:AAMA611,[AA-M12C22A42/A44,ClassI,0.018mm][AA-M12C22A32/A34,ClassII,0.010mm]orthicker.
PART3-EXECUTION
3.1EXAMINATION
A.Examinesubstrates,areas,andconditions,withInstallerpresent,forcompliancewithrequirementsforinstallationtolerances,metalpanelsupports,andotherconditionsaffectingperformanceoftheWork.
1.Examineprimaryandsecondaryroofframingtoverifythatrafters,purlins,angles,channels,andotherstructuralpanelsupportmembersandanchorageshavebeeninstalledwithinalignmenttolerancesrequiredbymetalroofpanelmanufacturer.
2.Examinesolidroofsheathingtoverifythatsheathingjointsaresupportedbyframingorblockingandthatinstallationiswithinflatnesstolerancesrequiredbymetalroofpanelmanufacturer.
B.Examineroughing-inforcomponentsandsystemspenetratingmetalpanelstoverifyactuallocationsofpenetrationsrelativetoseamlocationsofmetalpanelsbeforeinstallation.
C.Proceedwithinstallationonlyafterunsatisfactoryconditionshavebeencorrected.
3.2PREPARATION
A.MiscellaneousSupports:Installsub-framing,furring,andothermiscellaneouspanelsupportmembersandanchoragesaccordingtoASTMC754andmetalpanelmanufacturer'swritten recommendations.
3.3METALPANELINSTALLATION
A.General:Installmetalpanelsaccordingtomanufacturer'swritteninstructionsinorientation,sizes,andlocationsindicated.Installpanelsperpendiculartosupportsunlessotherwiseindicated.AnchormetalpanelsandothercomponentsoftheWorksecurelyinplace,withprovisionsforthermalandstructuralmovement.
1.Shimorotherwiseplumbsubstratesreceivingmetalpanels.
2.Flashandsealmetalpanelsatperimeterofallopenings. Refer to manufacturers recommendations.
3.Installflashingandtrimasmetalpanelworkproceeds.
4.Panels to be in onecontinuouslength,longlengthroofsmustbefieldformedbyManufacturer.
5.Provideweather-tightescutcheonsforpipe-andconduit-penetratingpanels.
B.Fasteners:
1.SteelPanels:Usestainless-steelfastenersforsurfacesexposedtotheexterior;usegalvanized-steelfastenersforsurfacesexposedtotheinterior.
2.AluminumPanels:Usealuminumorstainless-steelfastenersforsurfacesexposedtotheexterior;usealuminumorgalvanized-steelfastenersforsurfacesexposedtotheinterior.
C.AnchorClips:AnchormetalroofpanelsandothercomponentsoftheWorksecurelyinplace,usingmanufacturer'sapprovedfastenersaccordingtomanufacturers'writteninstructions.
D.MetalProtection:Wheredissimilarmetalscontacteachotherorcorrosivesubstrates,protectagainstgalvanicactionasrecommendedinwritingbymetalpanelmanufacturer.
E.Standing-SeamMetalRoofPanelInstallation:Fastenmetalroofpanelstosupportswithconcealedclipsateachstanding-seamjointatlocation,spacing,andwithfastenersrecommendedinwritingbymanufacturer.
1.Installclipstosupportswithself-tappingfasteners.
2.Installpressureplatesatlocationsindicatedinmanufacturer'swritteninstallationinstructions.
3.SeamedJoint:Crimpstandingseamswithmanufacturer-approved,motorizedseamertoolsometalroofpanels,andfactory-appliedsealantarecompletelyengaged.
F.AccessoryInstallation:Installaccessorieswithpositiveanchoragetobuildingandweathertightmounting,andprovideforthermalexpansion.Coordinateinstallationwithflashingsandothercomponents.
G.FlashingandTrim:Complywithperformancerequirements,manufacturer'swritteninstallationinstructions,andSMACNA's"ArchitecturalSheetMetalManual."Provideconcealedfastenerswherepossible,andsetunitstruetolineandlevelasindicated.Installworkwithlaps,joints,andseamsthatwillbepermanentlywatertightandweatherresistant.
1.Installexposedflashingandtrimthatiswithoutbucklingandtoolmarks,andthatistruetolineandlevelsindicated,withexposededgesfoldedbacktoform hems.Installsheetmetalflashingandtrimtofitsubstratesandachievewaterproofandweather-resistantperformance.
2.ExpansionProvisions:Provideforthermalexpansionofexposedflashingandtrim.Spacemovementjointsatamaximumof10feetwithnojointsallowed within24inchesofcornerorintersection.Wherelappedexpansionprovisionscannotbeusedorwouldnotbesufficientlyweatherresistantandwaterproof,formexpansionjointsofintermeshinghookedflanges,notlessthan1inchdeep,filledwithmasticsealant(concealedwithinjoints).
3.4ERECTIONTOLERANCES
A.InstallationTolerances:Shimandalignmetalpanelunitswithininstalledtoleranceof1/4inchin20feetonslopeandlocationlinesasindicatedandwithin1/8-inchoffsetofadjoiningfacesandofalignmentofmatchingprofiles.
3.5FIELDQUALITYCONTROL
A.Manufacturer'sFieldService:Engageafactory-authorizedservicerepresentativetoinspectmetalroofpanelinstallation,includingaccessories.Reportresultsinwriting.
B.Removeandreplaceapplicationsofmetalroofpanelswheretestsandinspectionsindicatethattheydonotcomplywithspecifiedrequirements.
C.Prepareinspectionreports.
D.Installermusthaveinstallationshopdrawingsonsiteatalltimes.
3.6CLEANINGANDPROTECTION
A.Removetemporaryprotectivecoveringsandstrippablefilms,ifany,asmetalpanelsareinstalled,unlessotherwiseindicatedinmanufacturer'swritteninstallationinstructions.Oncompletionofmetalpanelinstallation,cleanfinishedsurfacesasrecommendedbymetalpanelmanufacturer.Maintaininacleanconditionduringconstruction.
B.Replacemetalpanelsthathavebeendamagedorhavedeterioratedbeyondsuccessfulrepairbyfinishtouchuporsimilarminorrepairprocedures.