/ Tender Specification
Pump Control Base - Type: CPS-B2 (TFT)

Manufactured by:Condor Pressure Control GmbH

Type: Condor Pump Control Base

CPS-B2 (TFT) / 1.0-1.6 A

CPS-B2 (TFT) / 1.6-2.5 A

CPS-B2 (TFT) / 2.5-4.0 A

CPS-B2 (TFT) / 4.0-6.3 A

CPS-B2 (TFT) / 6.3-9.0 A

Microprocessor-controlled pump switching unit including power unit for level-dependent control and monitoring of two pumps with direct start-up to max. 4.0 kW output or 9.0 A current consumption.

Compact design in plastic housing with lockable clear cover, including a lockable main switch, motor protection switch for the pump and space reserve for installation of maximum two Zener barriers to operate the pumps and sensor system in explosive areas.

Operated and configured via a TFT colour display with touch function.

Connections:

  • Terminal block for mains connection 3xL/N/PE.
  • Pump connection on the power contactor.
  • One thermocontact for temperature detection in the pump motor standard T1 or ATEX T2 (zero-voltage safe) or programmable as AUX contact (ON/OFF).
  • Two 230 VAC / 2A voltage outputs for connecting an optional control cabinet heater and/or an optional small compressor.
  • One 24 VDC / 0.5 A voltage output for connecting an optional alarm light.
  • Three programmable potential-free alarm relays.
  • Floating switch connection 230 VAC for emergency operation in the event of sensor or electronic failure.
  • USB host port to connect a USB data stick
  • Plug-in base for retrofitting a GSM modem.
  • Plug-in socket for retrofitting an Ethernet module for web-based exchange of data.

Possible level measuring methods and connections:

  • Switching on and off via 2 or 3 float switches. (If the level measurement is performed using a level probe or the dynamic pressure gauge module, the input of float 1 can be used for "External shutdown"

and the input of float 2 as "External alarm".)

  • Separate high water float switch with forced switch-on function of the pumps.
  • Analog input 4-20 mA for level evaluation of a 2-wire level probe, freely parameterizable up to 60 mWs.
  • Subsequent optional installation of a pressure sensor 0-3.5 mWs for open or closed pressure measurement methods possible at any time.

Operation and display:

  • Operation and display is provided in the form of symbols and clear text via the TFT colour display.
  • Functions are selected and settings are made using a stylus or via manual touch operation.
  • LED display for operational readiness and faults.
  • Integrated buzzer for faults (can be switched off).
  • The motor protection switches of the pumps can be operated from the outside and thus even by laymen.
  • Main switch with emergency stop function (lockable).
  • Display of actual level in the selected unit or switch position of the connected float switch.
  • Actual display of the pump mode and pump run.
  • Actual display of the present motor current.
  • Pump menu with manual 0 automatic function and maintenance switch.
  • Setup menu for setting rarely changed data during commissioning.
  • Maintenance menu for programming service appointments

and query of operating hours and switching cycles.

  • Alarm menu for function setting of the alarm relays and messages in case of faults occurring.
  • Error history of the last 50 errors.
  • Compressor or agitator function including timer programme.
  • USB menu for exchanging control data and software updates via a USB stick.
  • GSM or Ethernet with built-in optional modem or module.
  • Alarm indication as symbol on the display.
  • Battery charge level.
  • Explanation of the most important functions on the device.
  • The connection diagram is provided in the terminal compartment.

Adjustable control parameters:

  • Available languages: German, English, French, Italian, Dutch.
  • Date, time, summer/winter time switching.
  • Display light off after time (1-30 min.).
  • Password input for protection against unauthorised access.
  • Switch-on delay after power failure (0-1000 sec.).
  • Rotary field and phase testing.
  • Thermal contact selectable between (standard, ATEX or AUX contact).
  • Level units selectable (mm, cm, mbar, bar, Torr, psi, Pa)
  • Measuring method (4…20 mA, dynamic pressure*, 2-3 floats).
  • On and off level freely programmable.
  • Alarm level adjustable.
  • Separate high water float selectable.*
  • Function "Fill container" selectable.
  • Compressor or agitator function.
  • Timer with four switch-on and -off times selectable.
  • Battery module for voltage supply of the electronics in the event of a power failure selectable.*
  • Delay time between individual pumps adjustable (1-99 sec.).
  • Load change function selectable.
  • Exchange type selectable (none, order, by operating hours or switching cycles).
  • Pump level assignment
  • Switching option for single pump control.
  • Pump run-on time adjustable (1-120 sec.).
  • Max. pump run time selectable (1-9999 min. stop or 1-9999 min. alarm).
  • Electronic pump current monitoring adjustable.
  • Quickstart of the pump to prevent settling, adjustable (1-9999 hours for 1-99 sec.).
  • Cyclical empty pumping (e.g. to prevent odour formation), adjustable (1-9999 hrs.).
  • Maintenance intervals and display of a service number.
  • Switching behaviour and control of the alarm relay programmable.
  • Delay times programmable for the individual faults (1-999 sec.).

*only possible with optional hardware.

Options:

  • Installation of a pressure sensor 0-3.5 mWs for open or closed pressure measurement processes possible at any time.
  • GSM module for fault forwarding can be retrofitted in the control system.
  • Ethernet module for web-based data exchange can be retrofitted in the control system.
  • Battery module with 2x lithium battery 3.7 V / 2250 mAh can be retrofitted into the control system.
  • Installation of max. two Zener barriers for intrinsically safe circuits.
  • Variants in 230 V version 1L/N/PE.

Technical data:

Operating voltage: 3xL/N/PE 230/400 V AC 50 Hz

Control voltage: 24 V DC, 230 V AC

Ambient temperature:0…+50 °C

Humidity:0…90% rel. hum. (non-condensing)

Storage temperature:-20…+70°C

Protection class:IP54

Dimensions:W265 x H270 x D145 mm

Cable entries:3xM25, 4xM16, 1xM20, 1xM12, 1xM10

The switchgear is ready for connection. Fusing is provided by the customer at max. 25 A.

Manufacturer: Condor Pressure Control GmbH

/ Condor Pressure Control GmbH
Warendorfer Straße 47 – 51
D-59320 Ennigerloh / Telefon: +49 (0) 25 87 / 89 – 0
Telefax: +49 (0) 25 87 / 89 - 140 /

Seite 1 von 4