UTK Displacer Level Controller
Summary
Measuring element of UTK displacer level controllerisball float or displacer,measuring element is connected with magnet tube. When level raised, magnet tube moves up and enters external magnetic field. Through magnet induction effect or magnet coupling effect, the magnet controlling switch or offset magnet steel is pulled and makes switch contact on or off. When level goes down, the magnet tube moves down and goes out off the external magnet field. Then the magnetic controlling switch backs to the original state or the offset magnet steel goes down back to new balance position under the action of self-weight, then makes switch contact on or off. In this way, it realizes level controlling and alarming.
Main technical parameter
Nominal pressure: ≤16.0MPa;
Measuring accuracy: level controlling: ±4mm;
interface controlling: ±6mm;
Flange standard: HG/T20592-2009,
HG/T20615-2009 or on request
Ambient temperature: -40℃~+80℃
Operatingtemperature: -40℃~150℃
(high temperature type: 300℃)
Medium density: level controller: ρ≥0.5g/cm3
interface controller: ρ1 - ρ2≥0.25g/cm3
Medium viscosity: ≤1St(10-4m2/s)
Wetted material: 20, 304, 316L or on request
Power supply inlet: G1/2″(female thread)
oronrequest
Explosion-proof: ExdⅡCT4-T6,
ExiaⅡCT4-T6
Protection class: IP67
Relative equipment: safety barrier (see safety barrier recommendation sheet)
Contact capacity:
Switch type / Max.voltage AC / Max.
current (A) / Contact point
number / Contact
resistance
(≯Ω) / Switching speed (≯ms) / Service life
(≮ 104times)
Reed switch / 250V / 1 / SPDT / 0.03 / 3 / 50
Microswitch / 250V / 5 / SPDT / 0.03 / 3 / 50
Note: 24V DC is only for intrinsically safe.
UTK Displacer Level Controller
Controlling range:
For level controlling
Model / Measuringelement / Controlling
position / Max.pressure
MPa / Nominal diameter / Alarming setting-point
B(mm) / Range
H(mm) / Remark
UTK100 / Ball float / Upper
Or lower limit / 6.3 / DN40 / On request / Controlling position non-adjustable
UTK300 / Displacer / Upper
Or lower limit / 4.0 / DN80 / On request / Controlling
position is adjustable;
The rang of upper limit and
low limit are adjustable.
Upper and lower limits / On request
UTK400 / Displacer / Upper
Or lower limit / 16.0 / DN40 / On request / Controlling position non-adjustable
For interface controlling:
Model / Controllingposition / Max.pressure
MPa / Min.density / Min.density
difference / Alarming setting-point
B(mm)
g/cm3
Ball-float / Upper or lower limit / 4.0 / 0.5 / 0.25 / On request
UTK Displacer Level Controller
Model selection table
UTK-100
Model / Code / Code meaningUTK- / Displacer level controller
100 / Flange sealing
A / Normal type
B / Side-bottom mounted
C / Side-side mounted Ⅰ
D / Side-side mounted Ⅱ
1 / Reed switch
3 / Microswitch
X / Upper limit or low limit
* / Medium density(g/cm³)
-
* / Alarm setting-point
(distance to upper interface flange mm)
i / Intrinsically safe
d / Explosion isolating
UTK- □ □ □ □ □ - □ □
Example: UTK-100D3X0.8-178i is flange sealing, side-side mountedⅡtype, microswitch,upper or low limit alarm, medium density is 0.8g/cm³, alarm setting-point is 178mm, intrinsically safe displacer level controller.
UTK-300, UTK-400
Model / Code / Code meaningUTK- / Displacer level controller
300 / Top mounted
400 / High pressure type (side-side mounted)
1 / Reed switch
3 / Microswitch
X / Upper or lower limit
Y / Upper and lower limit(only for UTK300)
* / Medium density(g/cm³)
-
* / Alarm setting-point
(distance to upper interface flange mm)
i / Intrinsically safe
d / Explosion isolating
UTK- □ □ □ □ - □ □
Example: UTK-4003X0.8-178i is high pressure type, microswitch, upper or lower limit alarm, medium density is 0.8g/cm³, alarm setting-point is 178mm,intrinsically safe displacer level controller.
UTK Displacer Level Controller
Outline and installation dimensions
- Structure
Safety barrier recommendation sheet
Dandong Top Electronics Instrument Co., Ltd / TP5041-Ex, TP5045-ExShanghai Automation Instrument Institute / CS8041-Ex, CS8045-Ex
Order requirements
1
WWW.DDTOP.COM
Operating medium
Operating pressure
Operating temperature
Flange standard
Wetted material
Medium density
Alarm setting-point
Other special requirement
1
WWW.DDTOP.COM