WIMES 3.12Page 1
APPENDIX C - DATA SHEETS
INDEX
GENERAL DATA SHEET
SUMMARY OF MOTOR STARTER FUNCTIONAL UNITS DATA SHEET
MOTOR STARTER DATA SHEET
INSPECTION AND TESTING DATA SHEET
ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
GENERAL DATA SHEET (1 of 4)
Project Title / Document ReferenceProject Location / Revision
Project Number / Date
Assembly Supplier / Ref. Drgs. Included (Y/N)
6.1.3.2 Labelling
Application LabelISSUE 3DECEMBER 2016
WIMES 3.12Page 1
* - Indicates Purchaser’s default requirement
3.0 OPERATING ENVIRONMENT AND SERVICE CONDITIONS
1 / Site Location (P)Inland/coastal
Rural/urban/industrial
1 / Assembly Location () (P)
Inside (heated)
Inside (unheated)
1 / Type of Assembly Building/Structure (P)
1 / Location Hazards (P)
3 / Minimum Ambient Air Temperature (-5OC) (P)
4 / Unusual Service Conditions (P)
4.0 ELECTRICAL SYSTEM PARAMETERS
1 / Nominal Supply Voltage (kV) (P)3.3/6.6/Other?
Frequency and Number of Phases (P)
Frequency (Hz)
Number of phases
Type of Neutral Earthing () (P)
Solidly earthed
Resistance earthed
Reactance earthed
Fault Levels (MVA) (P) / Min / Max
Phase to phase
Phase to earth
5.0 PERFORMANCE SPECIFICATION
5.1 Service Life
1 / Minimum Service Life(25 years*) (P)
6.0 DESIGN SPECIFICATION
6.1 General
6.1.1 General
1 / Assembly Pattern () (P/S)Fixed
Withdrawable
6.1.2 Weights and Lifting Arrangements
1 / Weights (kg) (S)Complete Assembly
Heaviest maintenance lift
Heaviest erection lift
6.1.6 O & M Manuals
1 / Type Required () (P)Supplier’s standard
Purchaser’s standard
6.2 Assembly Configuration and Construction
6.2.1 Assembly Configuration
1 / Configuration () (P)Part of a ‘composite’ MVAssembly
Stand-alone
6.2.1.2 Stand-Alone Assemblies
3 / Cable Entry Arrangements () (P)Top
Bottom
4 / Details of Cable Types and Sizes (P)
ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
GENERAL DATA SHEET (2 of 4)
Project Title / Document ReferenceProject Location / Revision
Project Number / Date
Assembly Supplier / Ref. Drgs. Included (Y/N)
6.1.3.2 Labelling
Application LabelISSUE 3DECEMBER 2016
WIMES 3.12Page 1
6.2.2 Assembly Construction
3 / LSC Category (P/S)4 / Partition Class (P/S)
5 / IAC Classification (AF*)(P)
6 / Assembly Height (mm) (S)
7 / IP Rating (P/S)
8 / Anti-Condensation HeatersRequired (Y/N) (P)
8 / ACH Voltage (V) (P/S)
8 / ACH Rating (W) (S)
9 / Paint Finish (Supplier’s Standard*) (P)
6.3 Earthing
4 / Earth Busbar to be Tinned (Y/N) (P)6.4 Busbar Compartment and Busbar
2 / Ratings (P/S)Rated short-duration power freq. withstand voltage (kV)
Rated lightning impulse withstand voltage (kV)
Rated continuous current (A)
Rated short time withstand current (kA)
Rated peak withstand current (kA)
Rated duration of short circuit (s)
3 / Busbars to be Tinned (Y/N) (P)
4 / Method of Busbar Insulation (S)
10 / Busbar Earthing Requirements (P)
6.5 MV Equipment
6.5.2 Disconnectors (If Required/Provided for Fixed Pattern Assemblies)
6.5.2.2 Ratings and Characteristics
1 / Ratings and Characteristics (P/S)Rated voltage (kV)
Rated short-duration power freq. withstand voltage (kV)
Rated lightning impulse withstand voltage (kV)
Rated frequency (Hz) / 50
Rated short time withstand current (kA)
Rated peak withstand current (kA)
Rated duration of short circuit (s)
Rated mechanical endurance (M0, M1 or M2)
6.5.2.3 Operation and Indication
2 / Additional Interlocking/Padlocking Requirements (P)5 / Method of Verifying Disconnector Position (P/S)
6.5.2.4 Remote Monitoring
2 / Number, Configuration and Rating of Auxiliary Contacts (P/S)ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
GENERAL DATA SHEET (3 of 4)
Project Title / Document ReferenceProject Location / Revision
Project Number / Date
Assembly Supplier / Ref. Drgs. Included (Y/N)
6.1.3.2 Labelling
Application LabelISSUE 3DECEMBER 2016
WIMES 3.12Page 1
6.5.4 Vacuum Contactors
6.5.4.1 General
3 / Method of Measuring Contactor Contact Wear (S)6.5.4.2 Ratings and Characteristics
1 / Ratings and Characteristics (P/S)Rated voltage (kV)
Rated short-duration power freq. withstand voltage (kV)
Rated lightning impulse withstand voltage (kV)
Rated frequency (Hz) / 50
Rated short circuit breaking capacity (without fuse?) (kA)
Rated short circuit making capacity (kA)
Rated mechanical endurance
Rated electrical endurance
Rated chopping current (A)
Rated switching frequency (per hour)
Maximum opening time (ms)
Maximum closing time (ms)
6.5.4.3 Operation and Indication
2 / Contactor Control Unit Details (P/S)Supply voltage (V)
Power consumption
(closing/holding) (VA)
3 / Mechanical Latching Required (Y/N) (P)
4 / Opening Device Details (S)
Supply voltage (V)
Power consumption (VA)
Response time (ms)
6.5.4.4 Remote Control and Monitoring
2 / Number, Configuration and Rating of Auxiliary Contacts (P/S)6.5.5 Earthing Switches
6.5.5.2 Ratings and Characteristics
1 / Ratings and Characteristics (P/S)Rated voltage (kV)
Rated short-duration power frequency withstand voltage (kV)
Rated Lightning Impulse withstand voltage (kV)
Rated frequency (Hz)
Rated short time withstand current (kA)
Rated peak withstand current (kA)
Rated duration of short circuit (s)
Rated short circuit making current (kA)
Rated mechanical endurance
Rated electrical endurance
ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
GENERAL DATA SHEET (4 of 4)
Project Title / Document ReferenceProject Location / Revision
Project Number / Date
Assembly Supplier / Ref. Drgs. Included (Y/N)
6.1.3.2 Labelling
Application LabelISSUE 3DECEMBER 2016
WIMES 3.12Page 1
6.5.5 Earthing Switches (Continued)
6.5.5.3 Operation and Indication
2 / Additional Interlocking/Padlocking Requirements (P)3 / Method of Verifying Switch Position (P/S)
6.5.5.4 Remote Monitoring
2 / Number, Configuration and Rating of Auxiliary Contacts (P/S)6.5.7 Control Circuit Supplies
2 / CCS Voltage (110 V AC*) (P)8 / Additional Transformer Required for Voltage Measurement (Y/N) (P)
6.7 Motor Cable Connection Arrangements
1 / Cable Entry Arrangements () (P)Top
Bottom
6.8 Check and Test Facilities
1 / VPIS Required (Y/N) (P)6.10 Switchgear Tripping Unit (If Required)
1 / Tripping Unit Required (Y/N) (P)8.0 TRAINING (IF REQUIRED)
1 / Training Required at the Supplier’s Works (Y/N) (P)ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
SUMMARY OF MOTOR STARTER FUNCTIONAL UNITS DATA SHEET
Project Title / Document ReferenceProject Location / Revision
Project Number / Date
Assembly Supplier / Ref. Drgs. Included (Y/N)
ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
6.9 Motor Starter Functional Units (Clause 1)
FUNCTIONAL UNIT / CIRCUIT DESIGNATION / FU No.* / PAGEMOTOR STARTER
*Each functional unit shall be assigned a unique number (refer to the schematic diagram of Assembly). The numbering system shall be 1 to n, starting at the LHS of the Assembly.
ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
SINGLE LINE DIAGRAMS
Project Title / Document ReferenceProject Location / Revision
Project Number / Date
Assembly Supplier / Ref. Drgs. Included (Y/N)
ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
MOTOR STARTER DATA SHEET (1 of 2)
Project Title / Document ReferenceProject Location / Revision
Project Number / Date
Assembly Supplier / Ref. Drgs. Included (Y/N)
6.1.3.2 Labelling
Circuit Designation LabelISSUE 3DECEMBER 2016
WIMES 3.12Page 1
6.9.1 Motor Starters
1a / Motor Details (P)Rating (kW)
Full load current (A)
Starting current (kA)/
Duration (s)
Starts per hour
Uncorrected motor power factor (75 %/100 % load)
1b / Type of Motor Starter Required () (P)
Direct on line
Auto-transformer
Soft start
Rotor resistance
1c / Fuse Details (P/S)
Rated current (A)
1d / Contactor Details (P/S)
Rated Current (A)
Category of use
1e / Types of Motor/Pump Protection Required/Provided () (P/S)
3 ph overcurrent and E/F
Undercurrent
Thermistor
Thermostat
Seal failure
Bearing over-temperature
Loss of cooling water (water cooled motors)
Pump over-temperature
Pump low flow
Pump low inlet pressure
Pump high outlet pressure
Vibration
1f / Local and Remote Control Requirements/ Provisions () (P/S)
Requirement / Local / Remote
Start forward /
Start reverse
Inch forward
Inch reverse
Stop /
Emergency stop
Overload reset
Emergency stop reset
Fault reset /
Lamp test /
HOA selector switch
1g / Local and Remote Indication Requirements/ Provisions () (P/S)
Requirement / Local / Remote
Auto available /
Drive running /
Drive stopped /
Drive tripped /
Individual fault conditions
Emergency stop operated
1h / Local and Remote Measurement Requirements/Provisions () (P/S)
Parameter / Local / Remote
Phase current
Max. demand current
Phase voltages
kW, kVA, power factor
kWh kVARh
KWh, kVARh pulsed output
Hours run meter
Number of starts counter
ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
MOTOR STARTER DATA SHEET (2 of 2)
Project Title / Document ReferenceProject Location / Revision
Project Number / Date
Assembly Supplier / Ref. Drgs. Included (Y/N)
6.1.3.2 Labelling
Circuit Designation LabelISSUE 3DECEMBER 2016
WIMES 3.12Page 1
1i / Motor Protection Relay Details (P/S)Relay Function / Details (Type, etc)
1j / Current Sensor Details (P/S)
CT Function / Details (Ratio, Class, Burden, etc)
1k / Motor Cable Details (No. of cables, cable type, cable size (mm2), no. of cores, etc.) (P/S)
NOTES:
ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
INSPECTION AND TESTING DATA SHEET (1 of 1)
Project Title / Document ReferenceProject Location / Revision
Project Number / Date
Assembly Supplier / Ref. Drgs. Included (Y/N)
6.1.3.2 Labelling
Application LabelISSUE 3DECEMBER 2016
WIMES 3.12Page 1
7.0 INSPECTION AND TESTING
7.1 General
1 / Additional Tests Required () (P)a / Site commissioning tests
7.2 Factory Acceptance Tests (FATs)
1 / Samples of Supplier’s test schedules to be submitted before testing (Y/N) (P)3 / Details of Any Further FATs Required (P)
7.3 Witness Factory Acceptance Tests
3 / Availability/Distribution of Supplier’s Test Schedules (P)a / Schedules to be made available to the Purchaser at witness FATs
b / Schedules to be sent to the Purchaser before witness FATs
4 / Witness FATs to Include () (P)
5 / Details of Any Further Witness FATs Required (P)
ISSUE 3DECEMBER 2016
WIMES 3.12Page 1
APPENDIX D – SUPPLIER’S SUPPLEMENTARY DATA SHEET INFORMATION
Clause / Supplementary InformationISSUE 3DECEMBER 2016