Building Construction (2nd Edition)
Building Construction (2nd Edition)
Chapter 7-Structural Systems
Test Review
- Reinforced concrete of protected steel framing are found in Type I fire-resistive buildings.
- Use of unprotected steel results in a Type II building classification (non-combustible).
- Wood an masonry together are found in ordinary construction Type II and mill construction Type IV.
- 3 methods are used to reinforce concrete: ordinary, PRE-tensioned, and POST-tensioned.
- With ordinary reinforcing, wet concrete is poured around steel bars within a framework.
- Design engineers determine the number of reinforcing bars, diameter of bars, and depth of concrete around bars.
- Standard size reinforcing bars vary from 0.375" to 2.257".
- Vertical steel reinforcing bars are known as stirrups, which resist diagonal tension.
- Concrete beams are frequently cast in the shape of a tee (more efficient/lightweight).
- The primary function of reinforcing steel is to resist tensile forces but they can support some compressive forces.
- With prestressing, a compressive force is applied to the concrete BEFORE a load is applied by tightening or preloading the reinforced steel.
- Preloading of reinforcing steel creates compressive stresses in concrete to counteract tensile stresses from applied loads.
- Initial prestressed forces applied to reinforcing bars are slightly higher than what is needed to support the concrete and applied loads.
- 2 methods of prestressing concrete are PRE-tensioning and POST-tensioning.
- In PRE-tensioned concrete, steel strands are stretched between anchors creating a tensile force in the steel BEFORE applying concrete.
- PRE-tensioned concrete usually has a slight upward deflection.
- With POST-tensioning, reinforcing bars are NOT tensioned until AFTER the concrete is hardened.
- A general rule is that reinforcing steel should only be cut to rescue trapped victims.
- Reinforcing bars in POST-tensioned concrete is NOT bonded to the concrete and are likely to spring out of the concrete if cut.
- Cast-in-place concrete (AKA site-cast concrete) is poured into forms at the building site.
- Most cast-in-place concrete is proportioned at a central bulk plant and mixed in mixing trucks enroute to the work site.
- Power-driven mixers may be used on work sites for small cast-in-place jobs.
- When cast-in-place concrete arrives at the work site, a slump test is performed to check the quality of the concrete.
- A slump test checks moisture content by measuring the amount that a small cone shaped concrete settles after it is removed from the standard test mold.
- Concrete may be subjected to compression testing to determine quality (requires hardening).
- Reinforcing steel overlaps construction joints which occur between successive pourings of cast-in-place concrete.
- Common cast-in-place structural systems include flat slab, slab & beam, and waffle construction.
- Flat slab concrete frames are simple systems consisting of a slab supported by concrete columns.
- Flat slab concrete varies from 6 to 12 inches thick.
- Shear stresses exist where columns intersect with flat concrete slabs.
- In flat slab concrete frame buildings with heavy live loads, supporting columns are reinforced with additional concrete in the form of drop panels or mushroom capitals.
- Flat plate concrete systems can be found when buildings will support light loads as in residential or small commercial buildings.
- Slab & beam frame consists of concrete slab supported by beams or beams & girders.
- Waffle construction concrete uses square forms to produce a thicker slab but eliminates the weight of unnecessary concrete on the bottom half of the slab.
- Reinforcing steel is placed in the bottom of waffle construction formwork to provide reinforcement in 2 directions (AKA 2-way slabs).
- Precasting plants produce precast parts (most common) and whole modular units PRIOR to delivery to work site.
- From a construction standpoint, precast concrete structures have more in common with steel frame buildings than cast-in-place buildings.
- Precast concrete was not common until after World War II.
- Precast concrete is produced as slabs, beams, columns, and wall panels.
- Precast slab types include solid, hollow-core, single-tee, and double-tee.
- Precast solid slabs are used for short spans up to 30 feet.
- Precast tee-slabs are used for spans up to 120 feet.
- Precast slabs can be supported by girders & columns, wall panels, or both.
- Precast exterior wall panels are commonly used with a steel framework.
- Precast elements are usually lighter than similar cast-in-place elements.
- Precast elements can be connected by bolting, welding, and POST-tensioning.
- A corbel is a ledge that projects out from a column and supports a precast beam.
- Precast beams can be secured to columns with steel angles, cast into a column, or with POST-tensioned steel cables.
- Precast units may have a cement topping up to 1 1/2 inch thick.
- Buildings supported by concrete frame are usually enclosed by NON-bearing curtain wall.
- NON-bearing exterior curtain walls can be made of aluminum, glass, steel panels, and masonry.
- Curtain walls make it difficult to identify the structural system by observation alone.
- Stucco and exterior insulation finish systems (EIFS) may appear visually to be concrete.
- Concrete structural systems can have fire-resistance ratings from 1 to 4 hours.
- Fire resistance of concrete is affected by concrete density, thickness, quality, and load supported.
- Structural lightweight concrete has lower density and lower thermal conductivity which results in better insulation against fire and heat than standard concrete.
- Cast-in-place concrete is inherently more fire resistant than precast due to continuity of the concrete.
- Concrete which is supported by NON-fire-resistive members or that has openings not enclosed by rated fire doors or shutters, is considered NON-fire-resistive.
- Concrete cannot withstand an explosion.
- Because steel is a very dense material, it is not efficient to use a solid slabs or panels.
- Sheets of steel may be used as floor decking or in exterior curtain walls.
- Connection of the beam to a column transfers the load between members and determines structural rigidity.
- Beam & girder steel frames are classified as rigid, simple, or semi-rigid.
- Rigid steel frames resist bending forces.
- Simple steel frames primarily support a vertical force.
- Semi-rigid steel frames provide some diagonal support by using diagonal bracing or shear panels.
- Shear panels are reinforced wall located between columns and beams that provide lateral support and should be continuous from foundation to the highest story needed.
- Steel trusses are more economical than beams for carrying loads across greater spans.
- Steel trusses are frequently used in 3 dimensional space frames.
- 2 common basic steel trusses are the open-web joint and joist girder.
- Open-web steel joists are made with depths up to 6 feet and spans up to 144 feet (2 foot or less depth and 40 foot span is most common).
- Top and bottom chords of open-web steel joists can be made from 2 angles, 2 bars, or a tee-shaped member with diagonal members being flat bars continuous round bar (AKA bar joint) welded to top and bottom chords.
- Bar joists often support floors and roof decks.
- Joist girders can take the place of steel beams for the primary structural frame.
- Steel rigid frames with inclined roof members are widely used for 1 story industrial buildings and farm buildings.
- Steel rigid frames usually span 40 to 200 feet.
- The top of a rigid steel frame is the "crown" and the points where inclined members intersect vertical members are the "knees".
- Vertical members of steel rigid frames may or may not be rigidly connected to foundations depending on anticipated wind loads.
- 1 story rigid frame structures must be braced diagonally to prevent lateral deflection.
- Steel arches support roofs where large unobstructed floors are needed.
- Steel arches can span in excess of 300 feet.
- Steel arches may be girder arches (solid arch), or trussed arch (using truss shapes).
- Steel wire strengths can be as high as 300,000 psi.
- Suspension roof systems can use steel rods or cables to provide large unobstructed areas without obstruction of side vertical clearances (unlike arches).
- Steel suspension systems may be used with cantilever roofs.
- The cross section of steel columns can be very small compared to their length due to the high compressive strength of steel.
- An unprotected slender steel column can buckle easily from the heat of a fire.
- The most common steel column cross sections are hollow cylinder, rectangular tube, and wide flange.
- Factors which affect buckling of steel columns include length, cross section, and top/bottom support.
- With steel columns, the slenderness ratio is a comparison of the unbraced length to the shape and area of its cross section.
- Steel columns used for structural support should not have a slenderness ratio less than 120.
- Rigid connections at the ends of steel columns resist rotation and are more resistant to buckling.
- Cross sectional shape of a steel column affects buckling potential.
- Square steel columns have less tendency to buckle than tubular shapes.
- Mass of steel and structural connection is determined by structural design used.
- Rigid connections in beam & girder frames have greater mass at the point of connection.
- Steel beam & girder and steel trusses frequently use steel web gussett and plates for rigid connections.
- Steel gussett plates strengthen connections and increase steel mass at the connection.
- Large beam & girder frames with repeating sections tend to be mutually supporting (redundancy).
- The main interest in masonry for firefighters is its use in wall construction.
- The most commonly encountered load-bearing masonry walls are brick, concrete block, and combinations of both.
- Gypsum block and lightweight concrete block are limited to NON-load-bearing partition walls.
- Masonry walls can be found in fire-resistive and NON-fire-resistive buildings.
- The most basic masonry structure consist of exterior load bearing walls which support the floor and roof.
- Interior floors and roofs made of wood joists and rafters, along with exterior masonry walls, is termed "ordinary construction".
- Interior masonry walls provide lateral and vertical load support.
- Wood and steel trusses commonly support roofs of masonry wall buildings.
- Cast iron was frequently used for interior columns in the 19th Century.
- Thickness of masonry walls varies from a minimum 6 inches, up to several feet.
- Lower partitions of multi-story walls must be thicker to carry the increased dead load from upper portions.
- NON-reinforced masonry walls are usually limited to 6 stories in height.
- Steel or concrete structural frame is more economical than masonry bearing walls when the building is more than 2 to 3 stories in height.
- Reinforced masonry bearing walls can be as high as 20 stories and only 10 inches thick.
- Masonry units laid side-by-side in a horizontal layer is called a "course".
- Horizontal courses of brick laid on top of each other is called a "wythe".
- The simplest brick wall consists of 1 wythe.
- A brick wythe is commonly used with a concrete block wythe (AKA Concrete Block Brick Faced-CCBF).
- When bricks are placed horizontally, end-to-end, they create a "stretcher course".
- When bricks are placed vertically, on end, they create a "soldier course".
- Parallel wythes of bricks can be bonded together using a "header course" every 6th course, or by using corrosion-resistant metal ties to bond wythes together.
- Horizontal bonding of brick and block is usually done with metal ties.
- Exterior brick walls usually have a vertical cavity between exterior and interior wythes to prevent water seepage through mortar joints.
- Masonry walls are reinforced to permit taller buildings or to provide lateral stability.
- Grout is a mixture of cement, aggregate, and water.
- Grout can be used to fill cavities between 2 adjacent wythes of a brick wall or within the openings of concrete block for reinforcement.
- Buttresses and pilasters can be used to reinforce masonry walls.
- Support of masonry over an opening requires the use of a lintel, arch, or corbelling.
- Lintels are beams (usually steel angles) over an opening in a masonry wall.
- When the height of a masonry wall above an opening is shorter than a triangular section above the opening, a lintel must provide support for the entire weight of masonry above the opening.
- Lintels (most common), and arches are common methods of supporting loads over masonry openings.
- Corbelling is used only for architectural styling.
- A parapet is an extension of a masonry wall that projects above the roof.
- Parapets are found on exterior masonry walls and fire walls when buildings have combustible roofs, but may also be used for architectural styling.
- Parapets project 1 to 3 feet or more above the roof and usually have NO lateral support.
- Live loads of a building are transferred to bearing walls and columns by joists, beams, or trusses.
- Masonry buildings with wood interior framing are classified as "ordinary" or "heavy timber".
- In many residential and small commercial buildings, wood joists or beams rest on an indentation in the masonry wall, called a beam pocket.
- A "fire cut" is a cut made with a slight angle at the end of a wood joist or beam to allow the member to fall freely away from the wall in the case of structural collapse.
- Wood roof trusses are frequently supported by pilasters.
- Fire resistance of masonry depends on type of masonry and thickness.
- Walls made of fire-rated concrete masonry units or bricks can have 2 to 4 hours of fire resistance.
- Well-constructed masonry walls are usually last to fail in a wood-joisted building.
- Masonry wall failure is usually due to deterioration of the wall and/or structural members.
- Cracks in masonry walls are often due to foundation shift.
- One method of reinforcing masonry walls is by using tension rods extending through the walls and then attached to "thrust plates" on the outside.
- Masonry walls usually collapse as a result of interior framing collapse.
- Collapsing interior framing produces horizontal forces against a masonry wall, resulting in tensile forces which the mortar cannot resist.
- It should be assumed that a collapsing wall will fall out from a building a distance at least equal to the height of the wall.
- Building codes require less clearance between buildings with masonry or fire-resistive exterior walls.
- Wood is almost always used in a frame structural system.
- Use of solid logs for log cabins is perhaps the only use of wood for solid wall construction.
- The 2 types of wood framing systems most frequently encountered are timber framing and light wood framing.
- Wood timber framing is NOT the same as a building with exterior masonry walls and heavy timber framing.
- Other types of wood construction include pole, log, and prefabricated panel construction.
- Due to basic strength limitations of wood, it is usually not economical to use wood frames in buildings over 3 stories in height.
- Until water-powered saws were developed 2 centuries ago, producing individual wood boards was slow and laborious.
- In heavy timber designs, basic structural support is provided by beams and columns made of heavy timber.
- In heavy timber designs, columns are NOT less than 8 x 8 inches, and beams (except roof beams) are NOT less than 6 x 10 inches.
- Integrity of wood frame structures is affected by methods used to join joists, beams, and columns.
- Factors affecting the design of connections for timber construction include specific gravity of wood, wood shrinkage, position of fasteners, and size of wood and fasteners.
- Components of wood member connections include bearing blocks, steel straps/brackets, and mortise & tenon joints (older construction).
- Heavy timbers cut from a single log are usually NOT available in lengths greater than 20 feet.
- Glulams or timber trusses are used for greater spans of timber framing.
- Post & beam construction uses columns (AKA posts), and beams with dimensions less than heavy timber but greater than light frame construction.
- Posts in post & beam construction are usually 4 x 4 or 6 x 6 inches and space 4 to 12 foot apart.
- Post & beam framing is square or rectangular and must be braced for diagonal stability.
- Post & beam construction is usually more labor intensive than light frame construction.
- Interior wood surfaces of post & beam and heavy timber construction is left exposed and thus eliminates combustible voids and avenues for fire spread.
- The most popular form of wood framing is light wood frame construction.
- Light wood framing uses 2 inch nominal lumber such as 2 x 4 or 2 x 8 inch members.
- Vertical members of light wood framing are supported by joists or trusses, and inclined roofs are supported by rafters or light trusses.
- The 2 basic types of light wood framing are balloon frame and platform frame.
- Balloon framing can have open channels, due to continuous exterior wall studs, which permit fire spread from foundation to attic.
- In platform framing (AKA western framing), exterior wall studs are NOT continuous from floor to floor.
- Platform framing has double 2 x 4 inch members (AKA plates) laid horizontally along the top of the studs on each floor which act as fire stops.
- Light wood framing is usually covered with plaster or drywall.
- Fire in a balloon frame building is more difficult to control than in a platform frame building.
- Platform frame buildings are easier to erect than balloon frame.
- Wood shrinkage is greater in a direction perpendicular to the wood grain.
- Platform framing has more horizontal members than balloon frame, which results in greater wood shrinkage (causes cracks/misalignment).
- Exterior wall materials include sheathing, siding, building paper, and insulation.
- Sheathing provides structural stability, insulation, and an under layer for siding, and may be made of plywood, or particle board.
- Siding can be made of wood boards, aluminum, or of wood, asphalt, or asbestos cement shingles.
- Foam insulation promotes rapid fire spread over its surface and may require facing with a thermal barrier such as gypsum, by code.
- Fire spread due to combustion of foam insulation within a wall space is dependent on the amount of air within the space.
- Loose fill insulation types include granulated rock wool, granulated cork, mineral wool, glass wool, cellulose fiber, and shredded wood.
- Loose fill insulation can be treated with water-soluble salts to reduce combustibility, but will still smolder if involved in a fire.
- Brick veneers must be tied to a wall at intervals of 16 inches.
- Weep holes in brick veneers are 2 feet on center.
- An air space of approximately 1 inch exists between a brick veneer and its supporting wall.
- There is little difference between a brick veneer building and ordinary wood frame building in terms of fire behavior.
- A rule of thumb to determine whether a brick wall is load-bearing is a bearing wall will have a header course every 6th course.
- Concealed spaces must be opened to check for fire extension.
FireNotes, Inc.® 2004 Duplication Prohibited Page 1 of 6