TARGET CORPORATION

SEPTEMBER 2011

Elevator QEI / Turnover Performance Report

SERVICE ELEVATOR 1

TARGET T-0184

2120 W. MAIN STREET

ALHAMBRA, CA 91801

by: Elevator Consulting Services, Inc.


FREIGHT ELEVATOR

Equipment Inventory -- Main Machine Room

Control Type: SELLECTIVE COLLECTIVE

Contract Speed: 100 FPM – UP

100 FPM – DN

Machine Type: BOREHOLE HYDRAULIC

PUMP UNIT

MCE HMC-2000 CONTROLLER

INSTALLED BY SPECIALIZED ELEVATOR

Door Equipment: GAL MOVFR 2 SPEED SIDE OPENING

Door Size/Type: 5’ 0’ WIDE X 7’ 0” HIGH F & R

Number of Openings: TWO (1) FRONT (1) REAR

Floors Served: B, *1

Travel: PIT - 4’ 0”

B TO 1

OVERHEAD - 12’6”

Complex Unit No.: 1

City / State Number: 107621

CA

Capacity: 9000 LBS

Emergency Light: OK

Alarm Bell: OK

Maintenance Log: YES

Oil Log: NI

Service Vendor: SPECIALIZED ELEVATOR


PERFORMANCE

Speed Up: 125 FPM

Speed Down: 125 FPM

Perform Up: 21.2 SEC

(B TO 1)

Perform Down: 23.0 SEC

(1 TO B)

Door Open 3.4 SEC – F

3. SEC – R

Door Close: 7.8 SEC – F

SEC – R

Car Call Dwell: SEC – F

SEC – R

Hall Call Dwell: SEC – F

SEC – R

Nudging: SEC – F

SEC – R

Torque: 5 LBS – F

5 LBS – R

Ride Quality

Ride: OK

Deceleration Up: OK

Deceleration Down: OK

Acceleration Up: OK

Acceleration Down: OK

Stop: OK

Leveling: OK

Equipment Room

Access: OK

Headroom: OK

Enclosure: OK

Lighting: OK

FLORESCENT 8’ LONG

Cleanliness: NI

Air Circulation,Ventilation: FAIR

Pipes, Ducts, Non Elev: NONE

Parts: NONE

Group II Keys: NO

GFIC Receptacle : OK

Fire Extinguisher: NI

Guarding: OK

Self Closing, Locking door: OK

Numbering of Units: NI

Sprinkler in Room: YES

Shunt Trip Protection: NO

Lockable, fused disconnect: OK

LLSRK100

Grounded: YES

110 Volt Disconnect: YES

LOCKABLE TOGGLE

MSDS documentation: OK

Oil Monitoring Sheet: OK

Signage on door: OK

Control Panel

Type of Control: MICROPROCESSOR

Manufacturer: MCE

Install Date: 6-2011

Installation Code: ASME 17.1 2004

TITLE 8 GROUP IV

Cleanliness: OK

Identification: OK

MCE JOB # 2011072009

SERIAL # 3292614

Software Version: STND HC-U10-U1

V900.2 B6E2

HC DVR U15

V900.077FD

HC RDR U26

V900.0 F686

HC RDR U28

V900.0 FD7F

HC CTLU53

V1.0.0 1491

U28

V1.0.0 48EF

U26

V1.0.0 C134

Guarding: OK

Labeled: YES / CSA

Code Data Tag: OK

Components-Controller

Relays: OK

Enclosed / Open Style: ENCLOSED

Contacts: OK

Resistors: OK

P.C. Boards / Timer: OK

Wiring: OK

Performance: OK

Camera Wire: OK

Starters - Dual

Type: ELECTRONIC

Mfg: SIEMENS

Size: AC 53a6-6 30-80

Part #: 72LG34AFA

Software Version: G

Contacts: OK

Wiring: OK

Mounting: OK

Starts: 1021 5/18/11


Pump Unit

Model: STND

Mfg: SPECIALIZED

Cleanliness: OK

Leaks: NONE

Belts: OK

Noise: OK

Sheaves: OK

Oil Level: OK

Oil: OK

Pump: OK

IMO

AG3DB-350

Shut Off: YES

Valves: OK

MAXTON

UC1A

Muffler: FREEMAN

Seals: OK

Covers: OK

Viscosity Control: OK

Acceptance Test: PENDING

Tagged: 5-18-11

5 Year Load Test: N/A

Tagged: N/A

Oil Coolers

Existing: YES

Cleanliness: NI

Mfg: HYDAC

Model: BUCR3S

Hoses: OK

Wiring: OK

Leaks: NONE

Air Filter: OK

Oil Filter: NONE

Motor Mfg: BALDOR

KW: 1.30

RPM: 1200

AMPS: 10.0

Motor

Isolation: N/A

Grounded: OK

Covers: N/A

HP: 60

RPM: 1725

AMPS: 77

Frame: 326T

Type: LEROY SOMMERS

Starts / Hr: 80

Hoistway Equipment

Selector Car Top Device

Cleanliness: OK

Sensors: OK

Tape: OK

Vanes: OK

Magnets: OK

Limit Switches

Roller Noise: OK

Operation: OK

Type: SUNS STND

Rails

Cleanliness: OK

Lubrication: OK

Type: T- 18.5

Fastening: OK

Roller Guide: OK

ELSCO

6” TANDEMS

Cable Condition

Traveling: OK

Suspension: OK

Spares: OK

Kellum Grips: OK

Ropes: N/A

Cable Tie Rt: N/A

Lt: N/A

Governors

Mfg: N/A

Model: N/A

Safety Type: N/A

Max Trip Speed: N/A

Max Load: N/A

Min Force to Act: N/A

Hoistway Equipment

Car Top

Cleanliness: NI

Maintenance Station: OK

Stop Switch: OK

Data Plate: NI

Light: OK

Light guards: OK

Roller Guides: OK

6” ELSCO TANDEMS

GFIC Receptacles: YES

Emerg exit locked: YES

Windows in Hoistway: NO

Multiple Hoistways: N/A

Stenciled: PENDING

Hoistway Venting

Existing: NO

Motorized: N/A

Safety Bars: N/A

Key Switch: N/A

Size (3%): N/A

Door Equipment / GAL MOVFR

FRONT REAR

Cleanliness: OK OK

Door Protection: SCANNER SCANNER

Lubrication: OK OK

Belts: OK OK

Chains: OK OK

Bearing: OK OK

Hangers: OK OK

Arms: OK OK

Noise OK OK

Tracks: OK OK

Upthrusts: OK OK

Restrictor: OK OK

Gibs: OK OK

Fire Tabs: OK OK

Car Enclosure

Ventilation: OK

FAN

Walls: STEEL PAINTED

Car Lighting: FLORESCENT

3 FIXTURES

CLEAN LENS

Ceiling: OK

STEEL CANOPY

Doors: STAINLESS STEEL F & R

Position Indicators: OK

DIGITAL IN MAIN & AUX COP

Handrails / Bumpers: 2 TIER

1 ROUND @ 32” TO TOP

1 – 6” BARSTOCK 8” TO TOP

Flooring: ALUMINUM DECKING

Certificate Frame: OK

EXPIRES 9/2011


Entrance Equipment

Cleanliness: OK

Lubrication: OK

Tracks: OK

Hangers: OK

Gibs: OK

Interlocks: OK

GAL

Noise: OK

Upthrusts: OK

Closers: OK

Braille: N/A

Emergency Fire Box

Main Egress Landing: 1ST FLOOR

Existing in Lobby: NO – NOT USED IN CA

Machine Room Key: N/A

Phase I, II Keys: N/A

Pit Access Key: N/A

Tagged: N/A

Car Operating Panel MAIN AUX

Type: INNOVATION INNOVATION

VANDAL RESISTANT VANDAL RESISTANT

Condition: OK OK

Height Compliance: OK OK

Braille Identification: OK OK

Illuminated: YES YES

Buttons: OK OK

Phone: OK N/A

Phone Callback #: N/A N/A

Alarm Button: OK OK

Stop Switch: KEYED KEYED

Emergency Light: OK OK

Capacity Plate / Engraved: OK

Fire Panel

Fire Fighters Inst: OK

Phase II Key Switch: YES

OFF/HOLD/ON

Call Cancel: YES

Fire Hat: YES

Certificated: YES

Door Open: OK – F

OK – R

Door Close: OK – F

OK – R

Stop Button: PUSH / PULL

Hall Buttons

Type: INNOVATION

Illuminated: OK

Height OK

Mechanical: OK

Lanterns: N/A

Fire Signage: OK

SIGNAGE ABOVE FIXTURE

Phase I Key Switch: YES – 1ST LEVEL

BYPASS/OFF/ON

Phase I Instructions: OK

SIGN ABOVE

FIXTURE

Service Panel

Inspection: TOGGLE

Light: TOGGLE

Independent: TOGGLE

Card Reader: TOGGLE

Fan: TOGGLE

Emerg. Light Test: PUSH BUTTON

GFI: YES


Pit Equipment

Cleanliness: OK

Car Buffer: OK

Cwt Buffer: N/A

Gov. Tension Sheave: N/A

Lights: OK

Light Guards: OK

Light Switch: OK

Stop Switch: OK

Ladder: OK

GFIC Receptacles: OK

Rupture Valves: YES

Jack seal: OK

Piston: OK

Pit Buckets: OK

Dead End Hitch Rt: N/A

Dead End Hitch Lt: N/A

PVC Liner: N/A

Return Line: OK

Sprinkler: YES


Bottom of Car

Cleanliness: OK

Safeties: N/A

Trav Cable Suspension: OK

Toe Guard Length: OK

Isolation: NONE

Light Fixture: NONE

Light Guard: N/A

Roller Guides: OK

ELSCO

6” TANDEM

Receptacle: NO

GFI Receptacle: NO


T – 0184 TARGET

ALHAMBRA, CA

SERVICE ELEVATOR

CORRECTIVE ITEMS

The following minimum items need corrective action taken. Documentation on completion is required. State ID - 107621 Acceptance Test – 5/23/11

1.  Clean car top and elevator pit.
Completion Date ______Initialed ______

2.  Clean elevator machine room.
Completion Date ______Initialed ______

3.  Maintain current maintenance control records current.
Completion Date ______Initialed ______

4.  Clean out controller.
Completion Date ______Initialed ______

5.  Replace all duct covers.
Completion Date ______Initialed ______


T – 0184 TARGET

ALHAMBRA, CA

SERVICE ELEVATOR

RECOMMENDATIONS

  1. Install a fire extinguisher in the machine room. Needs to be an ABC unit, minimum of 5 lb unit, properly mounted and serviced within normal guidelines.
  1. Patch, seal around machine room door.
  1. Fire caulk hole where hoses, Greenfield come into machine room from oil cooler.
  1. Upgrade light fixtures in the machine room to 19ft candles minimum.
  1. Nema 4 wiring to pit light.

END OF REPORT

NI – NEEDS IMPROVEMENT 19 of 20 T- 0184 SERVICE ELEVATOR

OK – ACCEPTABLE SEPTEMBER 2011 QEI / TURNOVER &PERFORMANCE REVIEW