A.B. Hopkins Generating StationElectric Generator System
August 1 2014Test Bank of Questions Unit 2 HPA
Test Bank of Questions
Electric Generator SystemHOPKINS REPOWERING PROJECT
UNIT HP2A
1.TH-HOP-16Electric Generator System
What is the purpose of the exciter?
- Controls final generator voltage
- Boosts voltage between the HP/IP and LP turbines
- Starts the generator
- Synchronizes the generator to the step-up transformer
2.TH-HOP-16Electric Generator System
How is hydrogen removed from the hydrogen-cooled generator?
- Released to the atmosphere
- Purged using carbon dioxide
- Purged using instrument air
- Flushed out with water
3.TH-HOP-16Electric Generator System
Where are the field windings located?
- Exciter
- Stator
- Rotor
- Permanent Magnet Generator
4.TH-HOP-16Electric Generator System
What is the armature also called?
- Field windings
- HRSG
- Rotor
- Stator
5.TH-HOP-16Electric Generator System
What is one advantage of hydrogen cooling over air cooling?
- Windage and ventilation losses are reduced because of the low density of hydrogen gas
- An increase in output per unit of active material due to high density of hydrogen gas
- Life of insulation on stator winding is increased because of lower thermal conductivity
- Maintenance expense is reduced because hydrogen is an oxidizing agent
6.TH-HOP-16Electric Generator System
How is the electro-magnetic field for the generator formed?
- AC current is passed through the rotor windings
- AC current is passed through the stator windings
- DC current is passed through the rotor windings
- DC current is passed through the stator windings
7.TH-HOP-16Electric Generator System
What connects the steam turbine generator to the step-up transformers?
- Isolated phase bus
- Exciter
- Stator coil
- Run transformer
8.TH-HOP-16Electric Generator System
How is generator output voltage controlled?
- Regulating the general protective relays
- Regulating the turbine rotor
- Regulating the isolated phases
- Regulating strength of the main generator field
9.TH-HOP-16Electric Generator System
What happen when the generator field breaker is closed?
- Output voltage drops to zero
- Voltage is transferred to the manual control panel
- Voltage automatically rises to the preset no-load voltage
- Voltage automatically rises from no-load to full-load
10.TH-HOP-16Electric Generator System
Where is the permanent magnetic generator located?
- Turbine end of the generator
- Outboard end of the exciter shaft
- Inside the stator wrapper
- Inside the rotor casing
11.TH-HOP-16Electric Generator System
What is the purpose of the seal oil system?
- Prevents hydrogen from leading from the generator
- Provides lubrication to the bearing seals
- Removes hydrogen safely from the generator
- Prevents air from coming in contact with CO2
12.TH-HOP-16Electric Generator System
What is one function of the generator gas system?
- Generates hydrogen and carbon dioxide used in the generator
- Safely supplies and removes hydrogen from the hydrogen-cooled generator
- Regulates CO2 content of cooling hydrogen
- Converts liquid hydrogen to gas
13.TH-HOP-16Electric Generator System
What are the safe purity levels for hydrogen in the hydrogen-cooled generator?
- Below 4.1% and above 74.2%
- Above 74.2% only
- Between 4.1% and 72.4%
- 100% only
14.TH-HOP-16Electric Generator System
Which of the following is NOT a protection provided by the voltage regulator circuits?
- Over-excitation protection and maximum excitation limiter
- Minimum excitation limiter
- Volts per Hertz protection and volts per Hertz limiter
- Amps per Hertz limiter
15.TH-HOP-16Electric Generator System
Where is the hydrogen stored at the plant?
- Under the ammonia tanks
- On the turbine deck
- In the hydrogen building
- Behind the hydrogen control panel on the pump room floor
16.TH-HOP-16Electric Generator System
In the last step of manual synchronization of the generator, you adjust the regulating valves until the associated pressure gauges read what?
- ± 2" H2O
- 5 psi
- 12 psi above hydrogen pressure
- 95% purity
17.TH-HOP-16Electric Generator System
During synchronization, the synchroscope is placed on the bus to be synchronized. Which bus is that?
- Isolated phase bus
- North or south pole bus
- East or west bus
- Minimum excitation limiter
18.TH-HOP-16Electric Generator System
When the generator is taken out of service for a short term (less than three months), what is done with the turbine?
- Connected to the backup generator
- Purged with air
- Shut down
- Left on the turning gear
19.TH-HOP-16Electric Generator System
What should be done when the generator is shut down for a long duration?
- Operate the turning gear and lube oil system continuously
- Operate the seal oil and generator gas systems several hours each month
- Operate the turning gear and lube oil system several hours each month
- Disconnect the generator shaft from the turbine
20.TH-HOP-16Electric Generator System
What does the rotor act as?
- Large electromagnet
- Container for the stator
- Mechanical power supply for the turbine
- Static starter for the generator
Draft Page 1