UNIT 3 : FAULT ANALYSIS – BALANCED FAULT

Possible 2 mark questions:

1. What is the need for short circuit studies or fault analysis?

The short circuit studies are essential in order to design or develop the protective schemes for various parts of the system. The protective scheme consists of current and voltage sensing devices, protective relays and circuit breakers. The selection of these devices mainly depend on various currents that may flow in the fault conditions.

2. What is the reason for transients during short circuits?

The faults or short circuits are associated with sudden change in currents. Most of the components of the power system have inductive property which opposes any sudden change in currents, so the faults are associated with transients.

3.What is meant by a fault?

A fault in a circuit is any failure which interrupts with the normal flow of current. The faults are associated with abnormal change in current, voltage and frequency of the power system. The faults may cause damage to the equipments, if it is allowed to persist for a long time. Hence every part of a system has been protected by means of relays and circuit breakers to sense the faults and to isolate the faulty part from the healthy part of the network in the event of fault

4. Why faults occur in a power system?

Faults occur in a power system due to insulation failure of equipments, flashover of lines initiated by a lightening stroke, permanent damage to conductors and towers or accidental faulty operations.

5. How are the faults classified?

In one method, the faults are classified as,

1. shunt faults - due to short circuits in conductors

2. series faults - due to open conductors.

In another method,

1.symmetrical faults - fault currents are equal in all the phases and can be analyzed on per phase basis

2. unsymmetrical faults – fault currents are unbalanced and so they can be analyzed only using symmetrical components.

6. List the various types of shunt and series faults.

Various types of shunt faults are

  1. Single line-to-ground fault
  2. Line-to-line fault
  3. Double line-to-ground fault
  4. Three phase fault

Various types of series faults are,

  1. One open conductor fault
  2. Two open conductor fault

7. What is meant by symmetrical fault.

The fault is called symmetrical fault if the fault current is equal in all the phases. This fault conditions are analyzed on per phase basis using Thevenin’s theorem or using bus impedance matrix. The three-phase fault is the only symmetrical fault.

8. List out the differences in representing the power system for load flow and short circuit studies.

Load flow studies / Fault analysis
1. Both resistances and reactances are
considered.
2. Bus admittance matrix is useful.
3. The exact voltages and currents are to be
determined. / Resistances are neglected.
Bus impedance matrix is used.
The voltages can be safely assumed as 1 p.u. and the prefault current can be neglected.

9. For a fault at a given location, rank the various faults in the order of severity.

In a power system, the most severe fault is three phase fault and less severe fault is open conductor fault. The various faults in the order of decreasing severity are,

1)3 phase fault

2)Double line-to-ground fault

3)Line-to-line fault

4)Single line-to-ground fault

5)Open conductor fault

10. What is meant by fault calculations?

The fault condition of a power system can be divided into subtransient, transient, and steady state periods. The currents in the various parts of the system and in the fault locations are different in these periods. The estimation of these currents for various types of faults at various locations in the system is commonly referred to as fault calculations.

11.What are the assumptions made in short circuit studies of a large power system network? (APR/MAY 2005)

1) The phase to neutral emfs of all generators remain constant, balanced and unaffected

by the faults.

2) Each generator is represented by an emf behind either the subtransient or transient

reactance depending upon whether the short circuit current is to be found immediately

after the short circuit or after about 3 – 4 cycles.

3) Load currents may often be neglected in comparison with fault currents.

4) All network impedances are purely reactive. Thus the series resistances of lines and

transformers are neglected in comparison with their resistances.

5) Shunt capacitances and shunt branches of transformers are neglected. Hence,

transformer reactances are taken as their leakage reactances.

12. What is synchronous reactance?

The synchronous reactance is the ratio of induced emf and the steady state rms current (i.e., it is the reactance of a synchronous machine under steady state condition). It is the sum of leakage reactance and the reactance representing armature reaction. It is given by,

Xs = Xl + Xa

Where,

Xs = Synchronous reactance

Xl = Leakage reactance

Xa = Armature reaction reactance.

13. Define subtransient reactance.(APR/MAY 2004)

The subtransient reactance is the ratio of induced emf on no-load and the subtransient symmetrical rms current, (i.e., it is the reactance of a synchronous machine under subtransient condition). It is given by,

Subtransient reactance,

Where

Xl = Leakage reactance

Xa = Armature reaction reactance

Xf = Field winding reactance

Xdw = Damper winding reactance.

14. Define transient reactance.

The transient reactance is the ratio of induced emf on no-load and the transient symmetrical rms current. (i.e.,it is the reactance of synchronous machine under transient condition). It is given by,

Transient reactance,

Where

Xl = Leakage reactanXa = Armature reaction reactanceXf = Field winding reactance

15.What is the significance of subtransient reactance and transient reactance in short circuit studies?

The subtransient reactance can be used to estimate the initial value of fault current immediately on the occurrence of the fault. The maximum momentary short circuit current rating of the circuit breaker used for protection or fault clearing should be less than this initial fault current.

The transient reactance is used to estimate the transient state fault current. Most of the circuit breakers open their contacts only during this period. Therefore for a circuit breaker used for fault clearing (or protection), its interrupting short circuit current rating should be less than the transient fault current.

16. Write down the equation determining fault current in a generator when its reactance is known.

The equation is,

,

where

= Steady state symmetrical fault current

= Transient symmetrical fault current

Xd = Direct axis synchronous reactance

Xd’ = Direct axis transient reactance

= RMS voltage from one terminal to neutral at no load.

17.Write the equation for subtransient and transient internal voltage of the generator.

The equation for subtransient internal voltage is,

Transient internal voltage is,

where

Eg’’ = Subtransient internal voltage of generator

Eg’ = Transient internal voltage of generator

Vt = Terminal voltage

IL = Load current

Xd’’ =Direct axis subtransient reactance

Xd’ =Direct axis transient reactance

18.Write the equation for subtransient and transient internal voltage of the motor.

The equation for subtransient internal voltage is,

Transient internal voltage is,

s

where

Em’’ = Subtransient internal voltage of generator

Em’ = Transient internal voltage of generator

Vt = Terminal voltage

IL = Load current

Xd’’ =Direct axis subtransient reactance

Xd’ =Direct axis transient reactance

19. How symmetrical faults are analyzed?

The symmetrical faults are analyzed using per unit reactance diagram of the power system. Once the reactance diagram is formed, then the fault is simulated by short circuit or by connecting the fault impedance at the fault point. The currents and voltages at various parts of the system can be estimated by any of the following methods.

1)Using Kirchoff’s laws

2)Using Thevenin’s theorem

3)By forming bus impedance matrix.

20. Define doubling effect and DC off-set current.

Doubling effect:

If a symmetrical fault occurs when the voltage wave is going through zero then the maximum momentary short circuit current will be double the value of maximum symmetrical short circuit current. This effect is called doubling effect.

DC off-set current:

The unidirectional transient component of short circuit current is called DC off-set current.

21.Differentiate between subtransient and transient reactance.

Subtransient reactance / Transient reactance
1) This is the ratio of induced emf and subtransient current.
2) Flux created by induced currents in the damper winding is included.
3) This is the smallest reactance among the reactance values.
4) This cannot be extrapolated. / 1) This is the ratio of induced emf and transient current.
2) There is no damper winding and hence no flux is created.
3) This is larger than the subtransient reactance.
4) This can be extrapolated backwards in time

22.What are symmetrical components?

An unbalanced system of N related vectors can be resolved into N systems of

balanced vectors called symmetrical components. Positive sequence components

Negative sequence components

Zero sequence components.

23. Write the symmetrical components of three phase system.

In a 3-phase system, the three unbalanced vectors (either current or voltage vectors) can be resolved into three balanced system of vectors. They are,

1)Positive sequence components

2)Negative sequence components

3)Zero sequence components.

24. Define negative sequence and zero sequence components.

Negative sequence components consist of three phasors equal in magnitude, displaced from each other by 120o in phase, and having the phase sequence opposite to that of the original phasors. Va2, Vb2 and Vc2 are the negative sequence components of Va, Vb and vc.

Zero sequence components consist of three phasors equal in magnitude and with zero phase displacement from each other. Vao, Vbo and Vco are the zero sequence components of Va, Vb and Vc.

25.Express the unbalanced voltages Va, Vb and Vc in terms of symmetrical components Va1, Va2 and Va0.

The expression of unbalanced voltages in terms of symmetrical components are,

(Or)

26. Express the symmetrical components Va1, Va2 and Va0 in terms of unbalanced vectors Va, Vb and Vc.

The expression of symmetrical components in terms of unbalanced vectors are,

(Or)

27. Define the operator ‘a’ and express the value of ‘a’ and ‘a2’ in both polar and rectangular form.

An operator which causes a rotation of 120o in the anticlockwise direction is known as operator ‘a’. The value of ‘a’ is 1120o.

The polar form and rectangular form of operator ‘a’ is given by,

a = 1120o ------polar form

= -0.5 + j0.806 ------rectangular form

The polar form and rectangular form of operator ‘a2’ is given by,

a2 = 1240o ------polar form

= -0.5 - j0.806 ------rectangular form

28.what are sequence impedances and sequence networks?

The sequence impedances are the impedances offered by the devices or components for the like sequence component of the current.

The single phase equivalent circuit of a power system consisting of impedances to current of any one sequence only is called sequence network.

29. What assumption is made at the star / delta transformer?

It is that the positive sequence quantities on the HV side lead their corresponding positive sequence quantities on the LV side by 30o. The reverse is the case for negative sequence quantities wherein HV quantities lag the corresponding LV quantities by 30o.

30.What is an unsymmetrical fault? List the various unsymmetrical faults.

The fault is called unsymmetrical fault if the fault current is not equal in all the phases. The unsymmetrical faults in a power system are,

1)Single line-to-ground fault.

2)Line-to-line fault.

3)Double line-to-ground fault

4)Open conductor fault.

31.Define positive sequence and negative sequence impedances.

The positive sequence impedance of an equipment is the impedance offered by the equipment to the flow of positive sequence current.

The negative sequence impedance of an equipment is the impedance offered by the equipment to the flow of negative sequence current.

Possible 16 marks:

  1. Explain the need for short circuit studies.
  2. Draw the relationship between the phase components and the sequence components.
  3. The phase ‘b’ of a three phase circuit is open. The currents in phases ‘c’ and ‘a’ are I and –I respectively. Determine the positive, negative and zero sequence components of the current in phase ‘a’.
  4. With the help of a detailed flow chart, explain how a symmetrical fault can be analysed using ZBus.
  5. What are the various types of faults? Discuss their frequency of occurrence and severity? Find the fault current when an L-L-G fault occurs at the terminals of an unloaded generator.
  6. Derive an expression for the positive sequence current Ia1 of an unloaded generator when it is subjected to a double line to ground fault.(APR/MAY 2004).
  7. Explain the short circuit model of a synchronous machine under short circuit conditions.
  8. What symmetrical components? Explain the symmetrical component transformation.
  9. What is meant by sequence impedance? Explain the sequence network of an unloaded generator.
  10. Explain the procedure for making short circuit studies of a large power system using digital computer. Illustrate the answer by considering a symmetrical fault. (NOV/DEC 2004)

1