Air Shower Tunnel (walk-in type) Appendix C
Page 1 of 5
· High velocity of clean air to remove surface lint from the body
· Interlocking system to prevent cross contamination
· Made of steel panel c/w powder coating to allow for easy cleaning
· To include recirculation system to trap dust and particles at pre-filter
· Sloped edges of door to prevent collection of dust
· Come with HEPA filter to remove 99.99% of particles bigger than 0.3microns.
· Operates on demand (activated by press switch or similar and deactivated by adjustable timer)
Air Shower Tunnel (walk-through type)
· High velocity of clean air to remove surface lint from the body
· Interlocking system to prevent cross contamination
· Made of steel panel c/w powder coating to allow for easy cleaning
· To include recirculation system to trap dust and particles at pre-filter
· Sloped edges of door to prevent collection of dust
· Come with HEPA filter to remove 99.99% of particles bigger than 0.3microns.
· Equipped with stainless steel barrier of 1m height to encourage people put up their hand while walking through the tunnel
· Operates on demand (activated by motion sensor and deactivated by adjustable timer)
General Requirements
1] To include 4 sessions of training for the Users and Technical Personnels
2] To provide Maintenance Manuals for the Equipment (English Version)
Optional Spare Parts
To provide optional critical spare parts list.
Page 2 of 5
Air Shower Tunnel (walk-in type) 1no.
Technical Data projected by designed by
consultant contractor
Jet air velocity m/s 22
HEPA filter (99.99% efficiency) no. 10
Nozzle (stainless steel) no. 80
Lighting (x5) W 20
Weight kg 2,050
Electrical
Voltage V 230 ......
Electrical load kW 4.0 ......
Overall dimensions (internal)
Length mm 1,000 ......
Width mm 5,000 ......
Height mm 1,960 ......
Overall dimensions (external)
Length mm 1,700 ......
Width mm 5,000 ......
Height mm 2,100 ......
Page 3 of 5
Air Shower Tunnel (walk-through type) 1no.
Technical Data projected by designed by
consultant contractor
Jet air velocity m/s 22 ......
HEPA filter (99.99% efficiency) no. 10
Railing (diameter) mm 38 ......
Railing no. 11
Nozzle (stainless steel) no. 80
Lighting (x10) W 20
Weight kg 3,800
Electrical
Voltage V 230 ......
Electrical load kW 8.0 ......
Overall dimensions (internal)
Length mm 1,000 ......
Width mm 10,000 ......
Height mm 1,960 ......
Overall dimensions (external)
Length mm 1,700 ......
Width mm 10,000 ......
Height mm 2,100 ......
Air Shower Tunnel (walk-in type) Page 4 of 5
Air Shower Tunnel (walk-through type) Page 5 of 5