Product Summary

QtyProduct

2Split System Air Conditioning Units (Small)

2Split System Air Conditioning Units (Large)

Split System Notes:
  1. Disconnect switches are not provided by Trane
  2. Fire/smoke devices are not provided by Trane
  3. External isolation/mounting pads not by Trane
  4. Controls/thermostats/sensors not by Trane
  5. Refrigerant piping specialties/linesets not by Trane
  6. Floor stands/mixing boxes, plenums not by Trane
  7. Secondary drain pans/condensate accessories not by Trane
  8. Start up and labor warranty not included
Tucker Biffel / Blaine Terry
Trane
4000 Dekalb Technology Pkwy
Building 100
Atlanta, GA 30340
Phone: (404) 321-7500 / The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval.


Table Of Contents

Product Summary

Split System Air Conditioning Units (Small) (Item A1)......

Tag Data......

Product Data......

Performance Data......

Mechanical Specifications......

Unit Dimensions......

Weight, Clearance & Rigging Diagram......

Accessory......

Split System Air Conditioning Units (Large) (Item B1)......

Tag Data......

Product Data......

Mechanical Specifications......

Unit Dimensions......

Weight, Clearance & Rigging Diagram......

Accessory......

Field Wiring......

Field Installed Options - Part/Order Number Summary......

Split System Air Conditioning Units (Small)......

Split System Air Conditioning Units (Large)......

Dalton City BOE Dalton MS Addition / November 06, 2013

Tag Data - Split System Air Conditioning Units (Small) (Qty: 2)

Item / Tag(s) / Qty / Description / Model Number
A1 / HP/AH3, HP/AH4 / 2 / 3 Ton Split H/P / 4TWR5036G1000-GAM5B0000M-1S-0----000-0--0

Product Data - Split System Air Conditioning Units (Small)

Item: A1 Qty: 2 Tag(s): HP/AH-3, HP/AH-4

4TWR5 Heat Pump Outdoor Unit

3 Ton Nominal Cooling Capacity

200 - 230 Volt / 1 Phase / 60 Hertz

5 year compressor parts warranty

GAM5B High Efficiency Convertible Air Handler

3 ton nominal capacity

208-230/1/60 Voltage

Low ambient head pressure control (Field Installed)

Anti-short cycle timer (Field installed)

4.80 kW Electric Heater w/ circuit breaker for 240/1/60 (Field Installed)

Performance Data - Split System Air Conditioning Units (Small)

Tags / HP/AH-3, HP/AH-4
Design clg outdoor DB (F) / 95.00
Cooling EDB (F) / 75.00
Cooling EWB (F) / 65.00
Rated gross capacity (AHRI) (Btuh) / 35400.00
Clg net total capacity (Btuh) / 35900.00
Clg net sensible capacity (Btuh) / 24300.00
Clg net latent capacity (Btuh) / 11600.00
Calc clg LDB (F) / 56.10
Calc clg LWB (F) / 54.90
SEER @ AHRI (btuh/watt) / 14.50
EER @ AHRI (EER) / 12.0
Cooling airflow (cfm) / 1200
Min system airflow clg (cfm) / 950
Max system airflow clg (cfm) / 1450
Min system airflow htg (cfm) / 950
Max system airflow htg (cfm) / 1450
AHRI airflow (cfm) / 950
AHRI reference number ( ) / 5863502
Compressor power @ (specific Ambient) (W) / 2507.0
Condenser fan power @ (specific SP) (W) / 216.0
Supply fan power @ (specified SP) (W) / 227.0
ASHRAE 90.1 S6.4.1 compliant / Yes
Htg outdoor DB (F) / 20.00
Heating airflow (cfm) / 1200
Heating capacity @ 47F (Btuh) / 32600.00
COP @ AHRI 47F (with Air Handler) (COP) / 3.38
COP @ AHRI 17F (with Air Handler) (COP) / 2.62
Heating capacity @ 17F (Btuh) / 20400.00
HSPF @ AHRI (btuh/watt) / 8.50
Heating EDB (F) / 60.00
Htg system net capacity (Btuh) / 22080.00
Htg system LDB (F) / 77.00
AHRI high compressor power heating mode (W) / 2383.0
AHRI low compressor pwer heating mode (W) / 1838.0
AHRI condenser fan power heating mode (W) / 216.0
AHRI supply fan power heating mode (W) / 227.0
Blower capability / 3.0 ton to 3.5 ton airflow
80 to 90 second blower off delay / Not Required
OD AHRI Model (Each) / -1.00

Mechanical Specifications - Split System Air Conditioning Units (Small)

Item: A1 Qty: 2 Tag(s): HP/AH-3, HP/AH-4

GAM5

Air-Tite II cabinet

2% or less air leakage

Precision applied - durable door seals

Specially designed air seal around refrigerant,

condensate and conduit connections

Double wall foamed cabinet system

R-4.2 insulating value

No loose fiber design

Smooth cleanable interior design

Sweat eliminating design

Composite foamed cabinet doors

Water proof cabinet design

Integrated horizontal drain pans

Modular cabinet with " allen wrench "quick latch" design

Multi-position up/down flow horizontal left/right

Side return option

Control board protection pocket built into cabinet wall

Alert port to view control board codes without door removal

10 alert codes

Low voltage terminal connection point

Quarter turn phillips head door fasteners

Vortica blower with polarized plug connections and integrated slide deck for easy removal

Patented enhanced coil fin

Dual refrigerant compatible as shipped

Slide in electric heaters with polarized plug connections (sold as accessory)

UVC light kit with safety switch and polarized plug connections (sold as accessory)

Labeled panels and connections

Molded in 1" standard filter rail

High efficiency ECM motor

Soft start fan motor operation

Built in fan delay modes

Maximum width of 23 1/2"

Compact 20 13/16" depth with doors removed

Two tone color

Fused 24v power

Safety door switch

1-year warranty

10-year warranty registered

Optional extended warranty available

Heater Section - 1 Phase Vertical Air Handler

A compartment is provided in the blower section for field installation of supplementary heater. Polarized plugs are provided for making electrical connections to the air handler control box from the supplementary heater.

Head Pressure Control Accessory

The Head Pressure Control (BAYLOAM***) accessory is a low voltage (24 Volts ) electronic head pressure control that cycles the condenser fan motor based on liquid temperature. The addition of this field installed Head Pressure Control accessory permits cooling operation to 0 deg F [-17.8 deg C] providing that non-bleed TXV's, quick start components, and compressor crankcase heat are provided with the system when required.

5 Minute Delay Relay Kit

This delay relay kit will prevent rapid on-off compressor cycling in light load conditions by not allowing compressor to operate for 5 minutes upon shutdown.

Head Pressure Control

Controls fan motor (on/off) in response to outdoor ambient temperature in conjunction with liquid line temperature. Accessory provides unit cooling operation to outdoor temperatures of 0F

General - 4TWR5

The 4TWR5 is fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115 F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application.

Casing - 4TWR5

Unit casing is constructed of heavy gauge, G90 galvanized steel and painted with a weather-resistant powder painton all louvers, panels, prepaint on all other panels. Corrosion and weather­proof CMBP-G30 DuraTuff base.

Refrigerant Controls - 4TWR5

Refrigeration system controls include condenser fan and compressor contac­tor. High and low pressure controls are inherent to the compressor. A factory installed liquid line drier is standard.

Compressor - 4TWR5

The Climatuff compressor features internal over temperature and pressure protection and total dipped hermetic motor. Other features include: centrifugal oil pump and low vibration and noise.

Condenser Coil - 4TWR5

The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.

Low Ambient Cooling - 4TWR5

As manufactured, this unit has a cool­ing capability to 55 F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 20 F.

Unit Dimensions - Split System Air Conditioning Units (Small)

Item: A1 Qty: 2 Tag(s): HP/AH-3, HP/AH-4

Unit Dimensions - Split System Air Conditioning Units (Small)

Item: A1 Qty: 2 Tag(s): HP/AH-3, HP/AH-4

Unit Dimensions - Split System Air Conditioning Units (Small)

Item: A1 Qty: 2 Tag(s): HP/AH-3, HP/AH-4

Unit Dimensions - Split System Air Conditioning Units (Small)

Item: A1 Qty: 2 Tag(s): HP/AH-3, HP/AH-4

Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Small)

Item: A1 Qty: 2 Tag(s): HP/AH-3, HP/AH-4

Accessory - Split System Air Conditioning Units (Small)

Item: A1 Qty: 2 Tag(s): HP/AH-3, HP/AH-4

Tag Data - Split System Air Conditioning Units (Large) (Qty: 2)

Item / Tag(s) / Qty / Description / Model Number
B1 / HP/AH1, HP/AH2 / 2 / 15 Ton Split H/P / TWA180040R0-TWE180E4R3A

Product Data - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

TWA Heat Pump Outdoor Unit

15 Ton Nominal Cooling Capacity

Dual Compressors

460 Volt / 3 Phase / 60 Hertz

5 year compressor parts warranty

ReliaTel Controls

TWE Air Handler Unit

15 Ton Nominal Cooling Capacity

Dual Circuit

460 Volt / 3 Phase / 60 Hertz Voltage

Supply Fan VFD (Single Zone VAV)

On/Off Low Ambient Control (Field Installed)

Condenser Coil Hail/Vandal Guard Kit (Field Installed)

19.92kw (460 volt / 60 Hz / 3 Phase) Electric heater (Field Installed)

Performance Data - Split System Air Conditioning Units (Large)

Tags / HP/AH-1, HP/AH-2
MCA - heat pump (A) / 33.40
MOP - heat pump (A) / 40.00
Total power - heat (kW) / 14.36
COP (COP) / 2.68
Min. H.P. operating weight (lb) / 765.0
Max. H.P. operating weight (lb) / 898.0
Condensing unit type / Heat pump unit
Airflow (cfm) / 5420
Cooling EDB (F) / 77.00
Cooling EWB (F) / 67.00
Ambient (F) / 95.00
Relative humidity (%) / 59.82
Heating EAT (F) / 60.00
Heating ambient WB (F) / 17.82
Heating ambient RH (%) / 70.00
Heating ambient DB (F) / 20.00
Gross total capacity (MBh) / 147.59
Gross sensible capacity (MBh) / 104.51
Latent capacity (MBh) / 43.10
Net total capacity (MBh) / 139.45
Net sensible capacity (MBh) / 96.35
Cooling LDB (F) / 60.84
Cooling LWB (F) / 58.97
Saturated suction temp (F) / 54.94
Discharge temperature (F) / 112.70
Gross heating capacity (MBh) / 124.29
Net heating capacity (MBh) / 131.11
Heating LAT (F) / 82.82
Heating delta T (F) / 22.82
Electric Heat Capacity (MBh) / 68.03
Electric heat delta T (F) / 11.56
Line length - actual (ft) / 100.00
Cond. location to A.H. / Same as air handler
Suction line size od (per circuit) / 1-1/8 in.
Liquid line size od (per circuit) / 1/2 in
Est. refrig. chrg / circuit (lb) / 31.2
Sight glass part # / GLS00830
Metering device / Expansion valve
External Static Pressure (in H2O) / 1.000
External plus component static pressure (in H2O) / 1.000
Supply fan power (bhp) / 2.59
Indoor motor RPM (rpm) / 867
MCA - A.H. (A) / 37.80
MOP - A.H. (A) / 40.00
MCA - A.H. for 230V w/elect heat (A) / 0.00
MOP - A.H. for 230V w/elect heat (A) / 0.00
Evaporator motor FLA (A) / 6.70
Evaporator face area (sq ft) / 16.33
Evaporator face velocity (ft/min) / 332
Evaporator fin spacing (Each) / 168.00
Evaporator rows (Each) / 4.00
Indoor motor power (kW) / 2.35
Condenser Fan Power (kW) / 1.10
Compressor power (kW) / 13.96
Total power (kW) / 17.41
EER @ AHRI (with air handler) (EER) / 10.6
EER @ AHRI (cond. unit only) (EER) / 10.6
IPLV @ AHRI (with Air Handler) (IPLV) / 0.0
IPLV @ AHRI (cond. unit only) (IPLV) / 0.0
Compressor 1 RLA (A) / 12.60
Compressor 2 RLA (A) / 12.60
Condenser motor 1 FLA (A) / 2.50
Condenser motor 2 FLA (A) / 2.50
Min. A.H. operating weight (lb) / 675.0
Max. A.H. operating weight (lb) / 729.0
Fan motor heat (MBh) / 7.34
Field supplied low static drive / Not required

Mechanical Specifications - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

General - TWA

Weatherproofed Steel Mounting/Lifting Rails

Hermetic Scroll Compressors

Plate Fin Condenser Coils

Fans and Motors

Standard Operating Range 50-125F (Min. 0°F with Low Ambient Accy)

Nitrogen Holding Charge

Certified and Rated in Accordance with AHRI and DOE Standards

Certified to UL 1995

Casing - TWA

Zinc Coated, Heavy Gauge, Galvanized Steel

Weather Resistant Baked Enamel Finish

Meets 672 hr Salt Spray Test

Removable Single Side Maintenance Access Panels

Lifting Handles in Maintenance Access Panels

Unit Base Provisions for Forklift and/or Crane Lifting

Refrigeration System - TWA

Dual Compressor (TWA180E, TWA240E)

Two (2) Separate and Independent Refrigerant Circuits

Each Refrigeration Circuit Equipped with Integral Subcooling Circuit.

Two (2) Direct Drive Hermetic Scroll Compressor with Centrifugal Oil Pump Providing Lubrication To Moving Parts

Suction Gas-Cooled Motors w/ ± 10% Voltage Utilization Range of Unit Nameplate Voltage

Reversing Valves

Crankcase Heaters

Internal Temperature and Current Sensitive Motor Overloads

Factory Installed Liquid Line Filter Driers

Phase Loss/Reverse Rotation Monitor

Liquid Line Service Valves (with gauge port)

Suction Line Service Valves (with gauge port)

No Compressor Suction and/or Discharge Valves (Reduced Vibration/Sound)

External High Pressure Cutout Devices

External Low Pressure Cutout Devices

Evaporator Defrost Control

Loss of Charge Protection (Discharge Line Thermostats)

Condenser Coil - TWA

3/8" Internally Enhanced Copper Tube Mechanically Bonded to Lanced Aluminum Plate Fins

Factory Pressure and Leak Tested to 660 psig.

Perforated Steel Hailguards Available (Factory Installed Option or Field Installed Accessory)

Condenser Fan - TWA

26" or 28" Propeller Fan(s)

Direct Drive

Statically and Dynamically Balanced

Condenser Motor(s) - TWA

Permanently Lubricated Totally Enclosed or Open Construction

Built-In Current and Thermal Overloads

Ball or Sleeve Bearing Type

Controls - TWA

Centralized MicroProcessor

Indoor and Outdoor Temperature Sensors Drive Algorithms Making Decisions for All Heating, Cooling, and Ventilation

Integrated Anti-Short Cycle Timer

Integrated Time Delay Between Compressors

Completely Internally Wired

Numbered and Colored Wires

Contactor Pressure Lugs or Terminal Block

Unit External Mounting Location for Disconnect Device

Single Point Power Entry

Hailguards - TWA

Condenser Coil Protection from Hail, Vandals, Etc.

Perforated, Painted Galvanized Steel

Factory or Field Installed

Low Ambient (Fan ON/OFF) - TWA

Provides Unit Cooling Operation to Outdoor Ambient of 0°F

Low Cost Solution

Liquid Line Temperature Controls Condenser Fan Operation

1 Kit Per Condenser Fan Required

General - TWE

Completely Factory Assembled

Convertible for Horizontal or Vertical Configuration

Convertible for Cooling Only or Heat Pump Application

Convertible for Left or Right External Connections (Refrigerant and/or Electrical)

Convertible for Front or Bottom Air Return

Nitrogen Holding Charge

Certified and Rated in Accordance with AHRI and DOE Standards

Certified to UL 1995 for Indoor Blower Coil Units

Casing - TWE

Zinc Coated, Heavy Gauge, Galvanized Steel

Weather Resistant Baked Enamel Finish

Access Panels with Captive Screws

Completely Insulated with Foil Faced, Cleanable, Fire Retardant, Permanent, Odorless Glass Fiber Material

Captured or Sealed Insulation Edges

Electrical Connection Bushings or Plugs

Refrigerant Connection Bushings or Plugs

Withstand Elevated Internal Static Pressure

Refrigeration System - TWE

Single or Dual Circuit

Distributor(s)

Thermal Expansion Valves (TXVs)

Evaporator Coil - TWE

3/8" Internally Enhanced Copper Tube Mechanically Bonded to Lanced Aluminum Plate Fins

Factory Pressure and Leak Tested to 449 psig.

Draw-Through Airflow

Dual Circuits Are Interlaced/Intertwined

Double Sloped, Removable, Cleanable, Composite Drain Pan

Four Drain Pan Positions

Indoor Fan - TWE

Double Inlet, Double Width, Forward Curved, Centrifugal Type Fan

Dual Fans On 10.4-20.912.5-25 Ton Air Handlers

Adjustable Belt Drive

Permanently Lubricated Bearings

Indoor Motor - TWE

Adjustable Motor Sheaves

Fixed Motors Sheaves (SZVAV and 2-Speed VFD)

Thermal Overload Protection

Permanently Lubricated Bearings

Meet Energy Policy of 1992 (EPACT)

Optional Over Sized Motors for High Static Applications

Controls - TWE

Completely Internally Wired

Numbered and Colored Wires

Magnetic Indoor Fan Contactor

Low Voltage Terminal Strip

Single Point Power Entry

Evaporator Defrost Control

Filters - TWE

Access From Side Coil Panels

Filters Slide on Rack

One Inch (1"), Throw-Away Filters on 4.6-8.335-10 Ton Units

Filter Rack Convertible to Two Inch (2") Capability on 5-10 Ton Units

Two Inch (2"), Throw-Away Filters on 10.4-20.912.5-25 Ton Units

Electric Heaters - TWE

Heavy Duty Nickel Chromium Elements

cETL Approved

Installs Directly On Fan Discharge

One or Two Stage Control (Dependent Upon Capacity)

Single Point Power Entry

Terminal Strip Connections

460V Heaters

Internally Wye Connected

Automatic Line Break High Limit Controls

230V Heaters

Internally Delta Connected

Automatic Reset of High Limit Controls Through Pilot Duty with Secondary Backup Fuse Links

Unit Dimensions - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

Unit Dimensions - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

Unit Dimensions - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

Unit Dimensions - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

Accessory - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

Accessory - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

Field Wiring - Split System Air Conditioning Units (Large)

Item: B1 Qty: 2 Tag(s): HP/AH-1, HP/AH-2

Field Installed Options - Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job.

Product Family - Split System Air Conditioning Units (Small)

Item / Tag(s) / Qty / Description / Model Number
A1 / HP/AH-3, HP/AH-4 / 2 / 3 Ton Split H/P / 4TWR5036G1000-GAM5B0000M-1S-0----000-0--0
Field Installed Option Description / Part/Ordering Number
Head pressure control / BAYLOAM103
Anti-short cycle timer / TAYASCT501A
3.60/4.80 kW Electric Heater with Ckt Brk for 208/240V 1 Phase 60 Hz / BAYEAAC05BK1AA

Product Family - Split System Air Conditioning Units (Large)

Item / Tag(s) / Qty / Description / Model Number
B1 / HP/AH-1, HP/AH-2 / 2 / 15 Ton Split H/P / TWA180040R0-TWE180E4R3A
Field Installed Option Description / Part/Ordering Number
Condenser Coil Hail/Vandal Guard Kit / BAYGARD061A
Low Ambient Control if no Hot Gas Bypass or Reliatel / BAYLOAMU02B
19.92kw (460 volt 60 cycle) 3 phase heater / BAYHTRM420A