TARGET CORPORATION
FEBRUARY 2005
Elevator QEI / Performance Report
FREIGHT ELEVATOR #3
T-1054 TARGET
TANFORAN PARK
1150 EL CAMINO REAL
SAN BRUNO, CA 94066
by: Elevator Consulting Services, Inc.
FREIGHT ELEVATOR
Equipment Inventory -- Main Machine Room
Control Type: SAPB
Contract Speed: 65 FPM- UP
70 FPM – DN
Machine Type: MINNESOTA PUMP UNIT
VIRGINIA CONTROLLER
Door Equipment: COURION
Door Size/Type: 12’ 0’ WIDE X 8’ 0” HIGH
Number of Openings: THREE (3) IN LINE
Travel: 35’ 0”
Floors Served: *1, 2, 3
Complex Unit No.: 5
City / State Number: 11035
Capacity: 8000 LBS
Emergency Light: OK
Alarm Bell: OK
Maintenance Log: SIGN IN AT GUEST SERVICES
PERFORMANCE
Speed Up: 95 FPM
Speed Down: 95 FPM
Perform Up: 18.9 SEC
Perform Down: 19.2 SEC
Door Open: 7.5 SEC
Door Close: 7.5 SEC
ALL +/- .2 SEC
Ride Quality
Ride: OK
Deceleration Up: OK
Deceleration Down: OK
Acceleration Up: OK
Acceleration Down: OK
Stop: OK
Leveling: OK
Equipment Room
Access: OK
Headroom: OK
Enclosure: OK
Lighting: OK
OLD STYLE FLORESCENT – UPGRADE TO T8
Cleanliness: OK
Air Circulation,Ventilation: OK
Pipes, Ducts, Non Elev: NONE
Parts: OK
GFIC Receptacle : REG UNIT
Fire Extinguisher: OK
SERVICED 10-04
Guarding: OK
Self Closing, Locking door: OK
VENTED THROUGH DOOR
Numbering of Units: NI
Smoke Head: YES
Sprinkler in Room: YES
Heat Head: NO
Lockable, fused disconnect: YES
BREAKER
110 Volt Disconnect: YES
Shunt Trip Protection: NO
MSDS documentation: OK
Oil Monitoring Sheet: OK
Signage on door: OK – “EQUIPMENT ROOM” ONLY
Control Panel
Type of Control: RELAY MH
Manufacturer: VIRGINIA
Install Date: 1997
Installation Code: TITLE 8 GROUP II
ASME 17.1 1996
Cleanliness: OK
Identification: OK
JOB # MHF 1216
Software Version: GE FANUC
SERIES 90-30
Guarding: OK
U. L. Label: OK
Components-Controller
Relays: OK
Enclosed / Open Style: ENCLOSED
Contacts: OK
Capacitors: OK
Resistors: OK
P.C. Boards / Timer: NI
Wiring: OK
Performance: OK
Rectifiers: N/A
Door Controller
Mfg: COURION
Model: E
Relays: OK
Resistors: OK
Capacitors: OK
Coils: OK
Motherboard: OK
Fuses: OK
Timers: OK
Starters
Type: WYE DELTA
Mfg: TELEMANIQUE
Size: D40
Contacts: OK
Connections: OK
Rescuvator
Mfg: REYNOLDS & REYNOLDS
Model: UV3-480 / 220
Serial No.: 960-0651-1
Meters: OK
Wiring: OK
Battery: OK
Pump Unit
Mfg: MEI
Model: MHF 1216
Cleanliness: OK
Leaks: NONE
Noise: OK
Oil Level: OK
Oil: OK
Belts: N/A
Sheaves: N/A
Pump: OK – IMO 250
Subs/ Dry: SUBS
Shut Off: NO
Valves: OK
UC-2A
Muffler: IN-LINE
Seals: OK
Covers: OK
Viscosity Control: N/A
Acceptance Test: OK
Tagged: 11-8-96
Load Test: OK
Tagged: 2-04
MITSUBISHI
Oil Coolers
Existing: YES
Model: DAD
Fins: OK
Fans: OK
Wiring: OK
Motor
Isolation: OK
Grounded: OK
Covers: OK
HP: 50
RPM: 1750
AMPS: 118 / 59
Starts / Hr: 80
Hoistway Equipment
Selector Car Top Device
Cleanliness: OK
Tape: OK
Tape Guides: OK
Wiring: OK
Limit Switches
Roller Noise: OK
Operation: OK
Type: GEM / MEI STND
Rails
Cleanliness: OK
Lubrication: OK
Type: T / JUMBO – 22 LBS
Fastening: OK
Shoes: OK
Cable Condition
Traveling: OK
TC Suspension: OK
Piston Traveler: N/A
TC Spares: OK
Hoist Cables: N/A
Cable Ties: N/A
Shackles: N/A
Hoistway Equipment
Car Top
Cleanliness: FAIR
Maintenance Station: OK
Stop Switch: OK
Data Plate: YES
Light: OK
Light guards: OK
Guides: OK
GFIC Receptacles: NO
Emerg exit locked: YES
Windows in Hoistway: N/A
Multiple Hoistways: N/A
Stenciled: NO
Hoistway Venting
Existing: NONE
Motorized: N/A
Safety Bars: N/A
Key Switch: N/A
Size (3%): N/A
Gate Operator - Courion
Cleanliness: OK
Door Protection: SAFETY EDGES
TAPE BOOT
Lubrication: OK
Belts: OK
Chains: MONITOR
Limit Assembly: OK
Idler Sheaves: OK
Sprockets: OK
Noise OK
Tracks: OK
Shoes: OK
Car Enclosure
Ventilation: OK
OPEN
Walls: STEEL W / ALUMINUM DECKING WAINSCOT
Car Lighting: FLORESCENT
OLD STYLE FIXTURES
Ceiling: STEEL
Position Indicators: NONE
Handrails / Bumpers: 2 STAINLESS RAILS / 3 WALLS
AT 15 & 35 “ TO TOP
Flooring: STEEL DECKING
Gate: MESH
Certificate: NO / FRAME EXISTS
Entrance Equipment
Cleanliness: FAIR
Lubrication: OK
Tracks: OK
Chains: OK
Shoes: OK
Interlocks: QIP / COURION
Noise: OK
Covers: OK
Motors: OK
Belts: OK
Access Devices: OK
Emergency Fire Box
Main Egress Landing: 1
Existing in Lobby: NO
Machine Room Key: NO
Phase I, II Keys: NO
Pit Access Key: NO
Tagged: NO
Car Operating Panel
Type: ADAMS VANDAL RESISTANT
Height Compliance: OK
Braille Identification: YES
Buttons: OK
Phone: PUSH TO TALK
Alarm Button: OK
Stop Switch: PUSH / PULL
Emergency Light: NO
Capacity Plate / Engraved: OK
Fire Fighters Inst: NO
Phase II Key Switch: YES
OFF / ON
Certificated: FRAME ONLY
Signage: OK
C1 LOADING
Hall Buttons
Type: ADAMS VANDAL RESISTANT
Illuminated: YES
Height: OK
Mechanical: YES
Lanterns: NO
Fire Signage: ENGRAVED IN FACE PLATE
Phase I Key Switch: YES
Phase I Instructions: YES
Pit Equipment
Cleanliness: FAIR
Car Buffer: OK
Cwt Buffer: N/A
Lights: OK
Light Guards: OK
Light Switch: OK
Stop Switch: OK
Ladder: OK
GFIC Receptacles: YES
Rupture Valve: YES
Jack seal: OK
PVC Liner: NO
Shut Off: YES
Piston pans: N/A
Bottom of Car
Cleanliness: OK
Safeties: N/A
Trav Cable Suspension: OK
Toe Guard Length: NON CONFORMING / 9” TO BEND
CODE IS 21”
Isolation: NONE
Light Fixture: OK
Light Guard: OK
Guides: OK
Receptacle: PORCELAIN FIXTURE ONLY
GFI Receptacle: NO
T-1054 TARGET
SAN BRUNO, CA
FREIGHT ELEVATOR
CORRECTIVE ITEMS
The following minimum items need corrective action taken. Documentation on completion is required.
Load Test – 2-04
1. Replace the pit light bulb.
2. Vacuum the car top.
3. Label RED relay or replace with adjustable resistor.
4. Controller takes 2 to 3 minutes to recycle if main line is turned off before rescuvator. Investigate why.
T-1054 TARGET
FREIGHT ELEVATOR
SAN BRUNO, CA
RECOMMENDED IMPROVEMENTS
1. The jack was never capped at the pit floor. This leaves it open for debris to fall down the hole and create potential problems. Cap the jack hole with concrete, mesh system.
Budget $ 2,400.00
2. Install “Elevator Equipment Room” signage on the machine room door. Budget $ 90.00
3. Provide adequate machine room lighting. Light shall provide a minimum of 10 foot candles at the floor level. ASME 17.3 Rule 2.2.3
4. Provide compliant cab lighting. There shall be not less than two lamps and provide a minimum of 5 ftc for passenger elevators and 2.5 ftc for freight elevators. ASME 17.3 Rule 3.4.5,
5. Install heat heads per contract.
6. Upgrade the existing receptacles to a GFIC receptacle in the pit and machine room. ASME 17.1 Rule 105.5c, 106.1e, NEC 620-85.
7. Install an adequate toe guard.
8. Auto close is needed. Will work if button is pushed, need timer.
NI – NEEDS IMPROVEMENT 19 T-1054 FREIGHT ELEVATOR #3
OK – ACCEPTABLE FEBRUARY 2005 QEI / MAINTENANCE REVIEW