Sika Sarnafil Waterproofing Specification ManualGrid System Contents
Introduction
System Description...... iii
System Components...... iii
Regional Offices...... iv
Part 1 – General Conditions
1.01 Description...... 1
1.02 Quality Assurance...... 1
1.03 Submittals...... 2
1.04 Product Delivery, Storage and Handling...... 2
1.05 Job Conditions...... 2
1.06 Sequencing of the Work...... 4
1.07 Warranties...... 4
Part 2 - Products
2.01 Waterproofing Membrane...... 5
2.02System Flashing Products and Accessories...... 6
2.03Leveling, Separation, and Protection Layers...... 8
2.04 Drainage Panels...... 9
2.05Thermal Insulation...... 9
2.06 Precast Concrete Pavers and Pedestals...... 11
2.07Related Materials...... 12
Part 3 – Execution
3.01 General...... 13
3.02 Examination...... 13
3.03 Substrate Preparation...... 13
3.04 Sub-Membrane Containment Grid Installation...... 15
3.05Control Test Drain Installation (If Specified)...... 16
3.06Leveling Layer Installation...... 16
3.07Thermoplastic Waterproofing Membrane Installation...... 17
3.08Hot-Air Welding of Lap Areas...... 17
3.09Membrane Flashings...... 18
3.10Metal Flashings...... 19
3.11Temporary Cut-Off...... 20
3.12Water Tests...... 20
3.13Electric Field Vector Mapping (EFVM)...... 21
3.14Separation Layer Installation (If Specified)...... 21
3.15Protection Layer Installation...... 21
3.16Installation of Drainage Panels (If Specified)...... 22
3.17Insulation and Filter Fabric Installation (Insulated Areas)...... 22
3.18 Precast Concrete Paver System (If Specified)...... 22
3.19Monitoring the Installation of Finishing Layers and Overburden...... 23
3.20Details...... 23
8-073-1
Sika Sarnafil Waterproofing Specification ManualGrid System Introduction
INTRODUCTION TO
SIKA SARNAFIL WATERPROOFING GRID SYSTEM
System Description
Sika Sarnafil’s Waterproofing Grid System is a complete membrane waterproofing system designed to protect below-grade structures from the effects of water infiltration leading to structural deterioration and interior water damage. The system is primarily intended to protect plaza decks but is also applicable for parking decks, foundation slabs, tunnels, planters, balconies/terraces, interior applications and roofing applications utilizing pavers, concrete or landscaping as overburden.
The Grid System design combines the performance characteristics of an adhered system with the ease of installation of a loose-laid system. The Grid System design consists of thermoplastic membrane strips which are fully adhered to the substrate to form a grid pattern. The Sarnafil G476 waterproofing membrane is loose-laid on a leveling layer over the substrate and welded to the containment grid strip.
The Grid System can be designed with an optional control test drain assembly which, installed at the low point of the deck below the completed membrane, becomes an indicator of water infiltration. The grid system and the control test drain system provide the building owner with the means to diagnostically ensure the integrity of the completed waterproofing system prior to and after the installation of the overburden. It provides the means to effectively identify the location of water entry, prevent the migration of moisture from one grid area to another, and most importantly minimize the amount of overburden to be removed if leakage were to occur after installation.
System Components
The Grid System design includes the following:
1.Sarnacol 2165Adhesive.
2.Sarnafil G459 Grid Strip Membrane.
3.Sarnafelt NWP-HD Leveling Layer.
4.Sarnafil G476 Waterproofing Membrane.
/5.Sarnafelt NWP Separation Layer (Optional).
6.Sarnafil Protection Layer.
7.Sarnafil Drainage Panel (Optional).
8.Sarnatherm Insulation (Optional).
REGIONAL OFFICES
NEW ENGLAND REGION225 Dan Road
Canton, MA02021
Phone:(781)821-0865
Fax:(781)821-9205
EASTERN REGION
One Park Way 3rd Floor
Upper Saddle River, NJ07458
Phone:(201)327-0479
Fax:(201)327-4069
SOUTHERN REGION
3483 Satellite Boulevard
Duluth, GA30096
Phone:(770)495-0025
Fax:(770)495-0027
MIDWEST REGION
20W267 101st Street, Unit E
Lemont, IL60439
Phone:(630)739-9740
Fax:(630)739-9741 / SOUTHWEST REGION
1213 West Loop, N, Suite 130
Houston, Texas77055
Phone: (713)812-0102
Fax: (713)812-0107
NORTHWEST REGION
20412 87th Avenue South
Kent, WA98031
Phone:(253)872-0258
Fax:(253)872-0273
MOUNTAIN REGION
356 Reed Avenue
Salt Lake City, Utah84103
Phone:(801)575-8648
Fax:(801)355-4407
WESTERN REGION
10701 Holder Street
Cypress, CA90630
Phone:(714)821-9377
Fax:(714)821-9356
CANADA
Sika Sarnafil
6820 Davand Drive
Mississauga, ON L5T 1J5
Canada
Phone:(800)268-0479
Fax:(905)670-5278
WEB ADDRESS:
/ EMAIL ADDRESS:
8-073-1
Sika Sarnafil Waterproofing Specification ManualGrid System
SECTION 071354.03
THERMOPLASTIC SHEET WATERPROOFING
SIKA SARNAFIL WATERPROOFING GRID SYSTEM
GUIDE SPECIFICATION FOR THE INSTALLATION
OF A THERMOPLASTIC MEMBRANE WATERPROOFING
SYSTEM WITH CONTAINMENT GRIDS
Instructions to Specifier
Instructions to Specifier are designated by [ ]. Specifier is to select one of the options provided for project specific specifications.
This guide specification may be used for waterproofing the following types of construction: plaza decks, foundation slabs, split slabs, tunnels, earth covered roof structures, fountains, balconies and terraces, and Protected Membrane Assemblies (PMA). Details with hydrostatic pressure may require additional design considerations; consult with Sika Sarnafil’s Waterproofing Department.
PART 1 -GENERAL CONDITIONS
1.01DESCRIPTION
A.Scope
To install a loose laid thermoplastic membrane waterproofing system with containment grids with integral flashings and other components.
The work includes but is not necessarily limited to the following:
1.Substrate Preparation
2.Containment Grids
3.Control Test Drains (If Specified)
4.Geotextile Leveling Layer
5.Waterproofing Membrane
6.Membrane Flashings
7.Metal Flashings
8.Protective Layer(s)
9.Insulation (If Specified)
10.Drainage Layer (If Specified)
11.Monitoring the Installation of Finishing Layers or Backfill
12.Sealants and Adhesives
13.Pavers (If Specified)
B.Related Work Under Other Sections
[Instruction to Specifiers: Specify other related sections such as contract documents, site work, plumbing, etc.]
1.02QUALITY ASSURANCE
A.This waterproofing system shall be applied only by a waterproofing Applicator authorized by Sika Sarnafil prior to bid.
B.Installation of leveling layer, waterproofing membrane, separation layer, flashing membrane, expansion joints, membrane protection layers, drainage layer and insulation shall be the responsibility of the membrane applicator to ensure undivided responsibility.
C.Obtain primary waterproofing materials, membrane and flashings, from a single manufacturer with not less than 10 years of successful experience in waterproofing application. Provide other system components only as approved by manufacturer of primary materials.
D.If a Sika Sarnafil Standard Warranty is required for the project, the waterproofing Applicator shall arrange with Sika Sarnafil to have the services of a full time monitor. The Applicator shall include all costs for the monitor, including expenses in his bid price.
E.Pre-construction conference to be held with the owner, architect, Applicator’s field superintendent, waterproofing foreman, Sika Sarnafil representative, and other involved trades to discuss waterproofing practices applicable to this project.
F.There shall be no deviation made from the contract specification or the approved shop drawings without prior written approval by the owner or the owner’s representative, and/or design professional, and Sika Sarnafil.
G.Water testing of the completed waterproofing system (minimum of 24 hours) is required for Standard and recommended for Membrane Only warranties. Water testing shall be witnessed and confirmed in writing by the owner’s representative, the waterproofing Applicator, and Sika Sarnafil (Standard warranty only).
H.Water testing may be supplemented with Electric Field Vector Mapping (EFVM) – low voltage electronic leak detection by a qualified testing agency. See Section 3.13.
I.All work shall be completed by trained and authorized personnel.
1.03SUBMITTALS
The Applicator shall submit to the owner’s representative and/or design professional the following:
1.A letter from the manufacturer certifying that the Applicator is an approved Sika Sarnafil waterproofing applicator in good standing.
2.Shop drawings and details that have been stamped and accepted by Sika Sarnafil.
3.Specimen copy of Sika Sarnafil’s warranty.
4.Specimen copy of Applicator’s warranty.
1.04PRODUCT DELIVERY, STORAGE AND HANDLING
A.All products delivered to the job site shall be in the original unopened containers or wrappings.
B.Handle all materials to prevent damage. All materials shall be placed on pallets and fully protected from moisture with canvas tarpaulins.
C.Membrane rolls shall be stored lying down on pallets and fully protected from moisture with canvas tarpaulins.
D.Bonding adhesives shall be stored at temperatures above 40°F (5°C).
E.All flammable materials shall be stored in a cool dry area away from sparks and open flames. Follow precautions outlined on container or supplied by the material manufacturer/supplier.
F.Any materials which the owner’s representative and/or Sika Sarnafil determine to be damaged are to be removed from the job site and replaced at no cost to the owner.
1.05JOB CONDITIONS
A.Proceed with waterproofing membrane installation only after substrate preparation is complete. Owner’s representative and/or design professional and waterproofing Applicator must accept substrate before proceeding with membrane installation.
B.Substrate must be clean and smooth. With the exception of areas to receive grid strips, damp concrete is acceptable, however no standing or visible water is allowed. Do not work in rain or snow or adverse weather conditions. Severe temperatures, moisture and humidity may affect the installation of products during construction. Comply with applicable installation requirements for all components.
C.Only install new waterproofing that can be made weathertight each day including all flashing work.
D.All work shall be scheduled and executed without exposing the interior building areas to the affects of inclement weather. The building and its contents shall be protected against all risks.
E.The structure must be designed to support the system, including the overburden and the water test. The adequacy of the structural support must be verified in writing by the owner, the owner’s design professional, architect, or engineer.
F.The Applicator shall take precautions that storage and/or application of materials and/or equipment does not overload the deck or building structure.
G.All new and temporary construction, including equipment and accessories, shall be secured in such a manner, at all times, as to preclude wind blow-off or damage.
H.Temporary waterstops shall be installed at the end of each day’s work and shall be removed before proceeding with the next day’s work. Waterstops shall be compatible with all materials and shall not emit dangerous or incompatible fumes.
I.The Applicator is cautioned that certain membranes are incompatible with asphalt, coal-tar, and oil-based and plastic-based cements. Creosote and penta-based materials are also incompatible. Such materials shall not come in contact with the waterproofing membrane at any time. If such contact occurs, the material shall be cut-out and discarded. The Applicator should consult the manufacturer with respect to material compatibility, precautions and recommendations.
J.Arrange work sequence to avoid use of newly-constructed waterproofing for storage, walking surface, and equipment movement. Where such access is absolutely required, the Applicator shall provide all necessary protection and barriers to segregate the work area and to prevent damage to adjacent areas. Both HDPE protection and felt separation sheet (or G445 protection and felt separation sheet) shall be provided for all waterproofing areas which receive traffic during construction. Any damage which occurs to the waterproofing membrane and/or system is to be brought to the attention of the owner’s representative and/or design professional and Sika Sarnafil. All damage is to be repaired according to Sika Sarnafil’s recommendations. The party responsible for damage shall bear the cost of repairs.
K.Prior to and during application, all dirt, debris and dust shall be removed from surfaces either by vacuuming, sweeping, blowing with compressed air, pressure washing and/or similar methods.
L.All waterproofing materials, insulation, flashings and metal work removed for construction shall be immediately taken off the site to a legal dumping area authorized to receive such materials.
M.If any unusual or concealed condition is discovered, stop work and notify the owner’s representative and/or design professional and Sika Sarnafil immediately, in writing.
N.Liquid materials such as solvents and adhesives shall be stored and used away from open flames, sparks and excessive heat.
O.Contaminants, such as grease, fats, oils, and solvents, shall not be allowed to come into direct contact with the waterproofing membrane. Any such contact shall be reported to Sika Sarnafil.
P.The Applicator shall verify that all drain lines are connected and un-blocked before starting work. Report any such blockages or non-connected drains to the owner’s representative and/or design professional in writing.
Q.Site cleanup, including both interior and exterior building areas below or adjacent to, or in any way affected by the construction, shall be complete and to the owner’s satisfaction.
R.All landscaped areas affected by waterproofing activities shall be raked clean and seeded, if required.
S.All paved areas shall be swept clean.
T.All areas stained, dirtied, and discolored or otherwise damaged due to waterproofing activities shall be cleaned, restored, and replaced as required.
U.The Applicator should take necessary precautions when using adhesives around air in-takes. The smell of the adhesive could be a disturbance to the building owner and occupants. It is the Applicator’s responsibility to notify the owner and take the proper precautions.
1.06SEQUENCING OF THE WORK
Work in conjunction with other trades to complete work in a timely manner including installation of protection layer(s), drainage panels, and insulation. Coordinate with other trades to avoid traffic over completed membrane surfaces.
1.Do not proceed with installation of protection layers and backfill over the completed sections of the waterproofing without the acceptance of the owner’s representative, design professional, general contractor, and Sika Sarnafil (when a Standard warranty is specified).
1.07WARRANTIES
A.Applicator’s Warranty
General
1.A waterproofing project management agreement with Sika Sarnafil Services or a full-time Sika Sarnafil approved monitor is required to obtain a Standard warranty. The Applicator shall include the cost of these services including all expenses in his bid.
2.The cost of exposing the waterproofing membrane for purposes of investigation and/or repair, such as removal and replacement of any concrete, paving, backfill or overburden, shall be the Owner’s responsibility.
3.A Sika Sarnafil Representative’s presence on a project regardless of reason, length, or frequency, does not imply that any additional coverage beyond that stated in the warranty is in effect.
B.Applicator’s Warranty
The Applicator shall supply the owner with a minimum two-year workmanship warranty. The warranty obligation shall run directly to the owner with a copy to Sika Sarnafil.
C.Sika Sarnafil Warranty
[Instruction to Specifiers: The following warranty types are available; select one]
Membrane warranty 5 years
Membrane warranty 10 years
Standard 5 years (full time monitoring required - see A. 1. above)
Standard 10 years (full time monitoring required - see A. 1. above)
1.Membrane Warranty
[Instruction to Specifiers: Fill in warranty length below.]
The Applicator shall provide a Sarnafil membrane only warranty to the building owner at the successful completion of the project. The warranty shall be limited to the performance of the waterproofing membrane for a period of years.
2.Standard Warranty
[Instruction to Specifiers: Fill in warranty length below.]
The Applicator shall provide a Sika Sarnafil Standard (labor and material) warranty to the building owner at the successful completion of the project. The waterproofing membrane manufacturer shall warrant to the building owner the repair of any leaks in the waterproofing membrane resulting from defects in the membrane or workmanship for a period of years.
PART 2 -PRODUCTS
2.01WATERPROOFING MEMBRANE
The manufacturer of the thermoplastic waterproofing membrane system shall have a track record of producing and marketing a reinforced PVC sheet system for waterproofing applications for at least 10 years. Subject to this and other technical requirements, provide products of the following:
1.Sika Sarnafil
Canton, Massachusetts
Thermoplastic membrane: polyvinyl chloride (PVC) flexible sheets with non-woven fiberglass reinforcing.
[Instruction to Specifiers: 80 mils is the standard thickness for Sarnafil waterproofing membrane and it is recommended for most applications. Other thicknesses are available based on project specific design criteria and are shown below. Durability and puncture resistance is a function of membrane thickness. Do not use G476 in situations where the membrane will be permanently exposed to sunlight.]
a)Sarnafil G476-15, 60 mil (1.5 mm), thermoplastic waterproofing membrane with fiberglass reinforcement.
ParametersASTM Test MethodTypical Physical Properties
Overall thickness, inches (mm), min.D 7510.060 (1.5)
Tensile Strength, psi.D 6381,500
Elongation at Break, %D 638240 MD, 240 CMD
Seam Strength, % of Tensile StrengthD 63890%
Retention of Properties After Heat AgingD3045
Tensile Strength, % of originalD 63895%
Elongation at Break, % of originalD 63895%
Tear Resistance, lbfD 100421.3
Linear Dimensional Change, %D 12040
Weight Change after immersion in water, %D5702.5
Static Puncture Resistance, 56 lbs. (250 N)D5602Pass
Dynamic Puncture Resistance 117.7 ft-pdl (5 J)D5635Pass
b)Sarnafil G476-20, 80 mil (2.0 mm), thermoplastic waterproofing membrane with fiberglass reinforcement.
ParametersASTM Test MethodTypical Physical Properties
Overall thickness, inches (mm), min.D 7510.080 (2.0)
Tensile Strength, psi.D 6381,500
Elongation at Break, %D 638240 MD, 240 CMD
Seam Strength, % of Tensile StrengthD 63890%
Retention of Properties After Heat AgingD3045
Tensile Strength, % of originalD 63895%
Elongation at Break, % of originalD 63895%
Tear Resistance, lbfD 100421.3
Linear Dimensional Change, %D 12040.0
Weight Change after immersion in water, %D5702.5
Static Puncture Resistance, 56 lbs. (250 N)D5602Pass
Dynamic Puncture Resistance 235.5 ft-pdl (10 J)D5635Pass
c)Sarnafil G476-24, 96 mil (2.4 mm), thermoplastic waterproofing membrane with fiberglass reinforcement.
ParametersASTM Test MethodTypical Physical Properties
Overall thickness, inches (mm), min.D 7510.096 (2.4)
Tensile Strength, psi.D 6381,500
Elongation at Break, %D 638240 MD, 240 CMD
Seam Strength, % of Tensile StrengthD 63890%
Retention of Properties After Heat AgingD3045
Tensile Strength, % of originalD 63895%
Elongation at Break, % of originalD 63895%
Tear Resistance, lbs.D 100421.3
Linear Dimensional Change, %D 12040.0
Weight Change after immersion in water, %D5702.5
Static Puncture Resistance, 56 lbs. (250 N)D5602Pass
Dynamic Puncture Resistance, 235.5 ft-pdl (10 J)D5635Pass
2.02SYSTEM FLASHING PRODUCTS AND ACCESSORIES
A.Flashing
[Instruction to Specifiers: Below you will find the various Sarnafil flashing membranes used for flashings and penetrations. The flashing membrane should be specified at the same thickness as the waterproofing membrane. If difficult details exist (i.e. pipes) a lesser thickness membrane may be specified. Select appropriate product below.]