Section273000:ElevatorLanding-Two-WayCommunicationSignage

  • ElevatorLandingSignage

Part1-General

1.0Summary

1.1TheElevatorLandinglocationsshallinclude3coderequiredsigns(Part#7050E/7087/7049).

1.21007.9oftheIBC2009requiresiftheexitsignsareilluminated,ElevatorLandingsignsshallbeilluminated(Part#7050E).

1.31007.9oftheIBC2009requirestactilesignagecomplyingwithICCA117.1shallbelocatedateachentrancetothearea(Part#7087)

1.41007.11oftheIBC2009requiresinstructionsontheuseoftheareaunderemergencyconditionsshallbepostednexttoeachCallBox(Part#7049).Theinstructionsshallincludeallofthefollowing:

1.4.1Personsabletousetheexitstairwaydosoassoonaspossible,unlesstheyareassistingothers.

1.4.2Informationonplannedavailabilityofassistanceintheuseofstairsorsupervisedoperationofelevatorshowtosummonsuchassistance.

1.4.3Directionsforuseofthetwo-waycommunicationssystemwhereprovided.

2.0Submittals

2.1SubmitProductdatasheets.Includeoperationmanuals.

3.0Construction

3.1TheInternallyIlluminatedLED(Part#7050E)shallbe10.5”Hx14”Wx3”D.SignmusthaveRedLEDlightsthatprovideconstantuniformillumination.SignmustbeULlistedtomeetUL924, NEC,OSHA,NFPA,andLifeSafetyCodeIlluminationrequirements.Signmustalsobeprovided

withDirectionalleftrightarrows.

3.2Tactilesignage(Part#7087)shallbewhiteletterswithbluebackground.Signsshallhave“Peelandstick”mountingforeasyinstallation.Signsshallalsoincluderaisedlettersandbraille.Dimensionsshallbe8”Wx8”H.

3.3Instructionsignage(Part#7049)shallincludeblackletterswithwhitebackground.Signsshallhave“PeelandStick”mountingforeasyinstallation.Dimensionsshallbe6”Wx8”H.

4.0Mounting

4.1TheElevatorLandingIlluminatedsign(Part#7050E)shallbemountedatorbelow80”attheentrancetotheareatoconformtocharacterheightandproportion.

4.2TheElevatorLandingtactilesignage(Part#7087)shallbemountedatorbelow60”attheentrancetothearea.

4.3TheElevatorLandingInstructionsignage(Part#7049)shallbemountednexttotheCallBoxintheelevatorlandingatorbelow48”.

5.0Graphics

5.1ElevatorLandingsignsshallstatethewords“EmergencyCommunication”.

5.2TactilesignagemustincludebothraisedlettersBraille.

5.3Add“D”toIlluminatedSign(Part#7050E)fordoublesidedsign.

6.0Electrical

6.1The(7050E)signshallbe120/277vacandhavebuilt-inbatterybackup.

7.0ProductSubstitutions

7.1Nosubstitutions

8.0Warranty

7.1TheElevatorLandingIlluminatedsignage(Part#7050E)shallbewarrantedforaperiodoftwo

years.

9.0Manufacturer

Themanufacturershallbe:Rath

N56W24720NorthCorporateCircle

Sussex,WI53089

800-451-1460

Website: