Laboratory Ventilation System LabSystemPage:

Project:

Specifications:

------

Pos. / Specifications / Price/unit
in EUR / Quantity / Price
in EUR

------

07.0115.01

/

iCM-F-0

/

Fully variable, demand-related control, face velocity

Microprocessor based control system for variable, seamless control of the exhaust air volume flow depending on the sash opening and the constant face velocity. The face velocity is constantly regulated (e.g. 0.3 m/s), independent of the vertical sash position and independent of the horizontal slide window position.
A high-speed control algorithm compares the setpoint with the actual value measured by a face velocity sensor and regulates the flow quickly, precisely and steadily, independent of pressure fluctuations in the duct system.
The illuminated graphic LC display shows the operating status and the face velocity as a numeric value in m/s or ft/min. The integrated monitoring device for monitoring the ventilation functions of the fume hood is a component of the controller. The face velocity that is to be regulated is continually monitored and thus offers maximum safety for the operating personnel. When the safe face velocity is underrun, an acoustic and optical alarm is issued.
Technical features:
  • Microprocessor based variable control system with full graphic LC display
  • Numeric and bar graph display of the face velocity in m/s or ft/min
  • Low cost control in a compact, fitted version
  • External mains adapter 230VAC/15VDC
  • All system data are saved mains voltage failure-safe in the EEPROM
  • Programming and display of all system values via the integrated operating level
or PC2500 software
  • Air flow sensor for measuring the face velocity
  • Volume flow range 1:16
  • Integrated functional monitoring of safe operation of the fume hood in accordance with EN 14175 with acoustic and optical alarm
  • Optical and optionally acoustic alarm for the operating state "sash position > 50cm"
  • Emergency operation (Override) = VEMERGENCY
  • Night-time reduction (reduced operation) = VNIGHT
  • Monitoring of the customer ventilation system
  • Rapid predictive control algorithm
  • High-speed, stable, precise control through direct actuation of the servo motor with
feedback potentiometer
  • Response time and upward regulation of the exhaust air volume flow ≤ 2 sec
(VMIN → VMAX)
  • Programming of the downward regulation time for regulating the exhaust air volume
flow ≤ 2...24 sec (VMAX → VMIN)
  • Closed loop control
  • Suitable for all fume hood constructions

Integrated operating and display panel:
Operating and display panel integrated on the fume hood, with graphic LC display,
acoustic alarm and the following functions
  • Serial standard interface (RS232) for connection of a PC for programming and commissioning

Operating keys

  • Alarm acknowledgement
  • ON/OFF
  • Light ON/OFF
  • Reduced operation (VMIN or night-time reduction)
  • Emergency operation for maximum exhaust air volume flow (VMAX or override operation)
  • Second key level for menu operation

LED displays

  • Green LED display for operation (exhaust air volume flow within the permitted range) with a light surface of >1 cm2
  • Red LED display for critical underrun of the minium exhaust air volume
flow (malfunction) with a light surface of >1 cm2
  • Yellow LED display for overrun of the maximum exhaust air volume flow VMAX and override operation
  • Yellow LED display for reduced operation VMIN
  • Yellow LED display for Close sash with a light surface of >1 cm2

Actuator control:
Direct digital output (direct drive mode) for damper actuation with feedback potentiometer for the damper position
Analogueoutput:
1 standardised analogue output 0(2)...10VDC for actual value of exhaust air
Relay outputs:
All relay contacts are potential-free with a switching capactiy of 250VAC/3A
  • Alarm output (malfunction alarm) 1 x changeover contact
  • Light ON/OFF, 1 x normally open contact (230VAC/12A)
  • ON/OFF (feedback to DDC), 1 x changeover contact

Analogue input:

1 standardised analogue output 0(2)...10VDC for special applications

Digital inputs:

All inputs are galvanically separated and suitable forDDC remote functions. Electrical data: 24V DC, 10mA.
  • ON/OFF
  • DAY/NIGHT mode
  • Sash opening > 50 cm

Interface:

Serielles Interface (RS 485)

Damper:

  • Maintenance-free damper in PPs.
  • Volume flow range 90 – 1500 m3/h (1:16)
  • Polypropylene model, flame resistant (PPs)
  • Sound power level at 600 m3/h and 100 Pa system pressure < 50 dB(A)
  • Socket or standard flange model (optional)
  • Short construction length, L=250 mm with a connection diameter of D=250 mm
  • High speed actuator with direct actuation (direct drive mode and integrated capture of the angle of the damper position (feedback potentiometer)
  • Damper motor 12VDC with Direct Drive Mode
  • Running time < 3 sec for 900 angle

Technical Data:
Power supply / 100...230 VAC, ± 15 %, 50/60 Hz, Plug-in power supply
Nominal capacity / 10 VA

Manufacturer:

/ SCHNEIDER

Controller type:

/ iCM-F-0

Damper:

/ DK-250-P-MM-1
______/ ______/ ______

07.0115.01.1