PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30

2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 1

WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B

ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B

ACCC VOLTAGE REPORT

DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx

SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB

MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon

CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

BASE CASE ------BASE CASE

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.7 97.0 110.7

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 347.8 335.0 104.7

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 57951 [HAW G5 122.000] TO BUS 57973 [HAWTHRN5161.00] CKT 1 ------CONTINGENCY SINGLE 1

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 110.9 97.0 115.9

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 370.6 335.0 113.0

59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 453.9 450.0 100.9

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 57953 [MONTG2 122.000] TO BUS 57995 [MONTROS5161.00] CKT 1 ------CONTINGENCY SINGLE 3

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 107.7 97.0 111.9

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 350.5 335.0 105.6

57995 MONTROS5 161 57952*MONTG1 122.0 1 189.5 197.2 195.0 101.2

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 57954 [MONTG3 118.000] TO BUS 57995 [MONTROS5161.00] CKT 1 ------CONTINGENCY SINGLE 4

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 107.8 97.0 112.0

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 350.7 335.0 105.6

57995 MONTROS5 161 57952*MONTG1 122.0 1 189.5 196.8 195.0 100.9

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 57962 [IAT G2 125.000] TO BUS 57982 [IATAN 7345.00] CKT 1 ------CONTINGENCY SINGLE 12

56765*HOYT 7 345 56766 JEC N 7 345 1 987.5 1077.7 1076.0 100.5

PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30

2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 2

WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B

ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B

ACCC VOLTAGE REPORT

DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx

SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB

MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon

CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 57968 [STILWEL7345.00] TO BUS 57981 [LACYGNE7345.00] CKT 1 ------CONTINGENCY SINGLE 24

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 111.3 97.0 116.2

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 360.3 335.0 109.1

59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 453.9 450.0 100.9

96751 2REEDS 69.0 52690*CARTHG 269.0 1 34.7 36.7 36.0 100.6

X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT

'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 56996 TIOGA 4 138 0.9489 0.9507

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 58033 [BRKRIDG5161.00] TO BUS 58047 [OVERLPK5161.00] CKT 1 ------CONTINGENCY SINGLE 111

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.5 97.0 110.6

58036 OLATHE 5 161 58045*SWITZER5 161 1 213.0 372.2 335.0 115.1

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 346.4 335.0 104.2

X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT

'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 58033 BRKRIDG5 161 0.9489 0.9821

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 58036 [OLATHE 5161.00] TO BUS 58045 [SWITZER5161.00] CKT 1 ------CONTINGENCY SINGLE 118

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 107.0 97.0 111.2

58033*BRKRIDG5 161 58047 OVERLPK5 161 1 156.1 370.6 335.0 114.2

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 349.9 335.0 105.4

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 58042 [SPRGHL 5161.00] TO BUS 58126 [LACKMAN5161.00] CKT 1 ------CONTINGENCY SINGLE 125

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 125.1 97.0 131.3

57235*CAPTAIN3 115 57278 WAVERLY3 115 1 94.6 116.8 118.0 102.3

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 345.7 335.0 104.2

X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT

'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 57254 MOONLIT3 115 0.9410 0.9744 57255 MOONLTJ3 115 0.9428 0.9762

57262 160TH 3 115 0.9347 0.9823 57265 SOUTHTN3 115 0.9377 0.9799

57267 SPRINGH3 115 0.9289 0.9889 57273 TIMBRLN3 115 0.9447 0.9798

58042 SPRGHL 5 161 0.9289 1.0044

PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30

2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 3

WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B

ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B

ACCC VOLTAGE REPORT

DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx

SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB

MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon

CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 58059 [MALTABN5161.00] TO BUS 58063 [SWAVRLY5161.00] CKT 1 ------CONTINGENCY SINGLE 137

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.8 97.0 110.9

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 348.2 335.0 104.9

59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 450.2 450.0 100.1

59242*CLINTON5 161 96071 5CLINTN 161 1 98.2 105.4 100.0 105.6

X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT

'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 58063 SWAVRLY5 161 0.6676 0.9600

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 58059 [MALTABN5161.00] TO BUS 58064 [NORTON-5161.00] CKT 1 ------CONTINGENCY SINGLE 138

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.8 97.0 110.9

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 348.2 335.0 104.9

59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 450.2 450.0 100.1

59242 CLINTON5 161 96071*5CLINTN 161 1 98.2 104.5 100.0 104.8

X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT

'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 58059 MALTABN5 161 0.6799 0.9621 58063 SWAVRLY5 161 0.6799 0.9600

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 58062 [SALSBRY5161.00] TO BUS 58064 [NORTON-5161.00] CKT 1 ------CONTINGENCY SINGLE 141

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 107.2 97.0 111.4

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 349.0 335.0 105.2

59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 451.9 450.0 100.4

59242*CLINTON5 161 96071 5CLINTN 161 1 98.2 105.7 100.0 107.3

X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT

'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 58059 MALTABN5 161 0.8498 0.9621 58063 SWAVRLY5 161 0.8486 0.9600

58064 NORTON-5 161 0.8517 0.9658 58070 WEST---5 161 0.8484 0.9629

58071 S EAST 5 161 0.8492 0.9636 58072 MRSHLJT5 161 0.8504 0.9646

58073 MIAMI 5 161 0.8480 0.9626

PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30

2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 4

WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B

ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B

ACCC VOLTAGE REPORT

DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx

SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB

MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon

CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 58094 [SWAVRLY269.000] TO BUS 58101 [DOVERPT269.000] CKT 1 ------CONTINGENCY SINGLE 170

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.7 97.0 110.8

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 347.9 335.0 104.7

59242*CLINTON5 161 96071 5CLINTN 161 1 98.2 100.9 100.0 101.0

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 57977 [CRAIG 7345.00] TO BUS 56772 [STRANGR7345.00] CKT 1 ------CONTINGENCY SINGLE 193

57180 TEC E 3 115 57182*TECHILE3 115 1 230.4 258.5 236.0 108.8

57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 164.0 97.0 170.4

57235*CAPTAIN3 115 57278 WAVERLY3 115 1 94.6 116.9 118.0 101.3

57243*JAGGARD3 115 57261 PENTAGN3 115 1 64.2 119.3 92.0 132.4

57982*IATAN 7 345 59199 ST JOE 3 345 1 683.3 991.7 956.0 103.1

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 466.7 335.0 142.7

59203 NASHUA 5 161 59204*SMTHVL 5 161 1 155.9 240.3 245.0 101.1

59204 SMTHVL 5 161 59221*PLTCTY 5 161 1 180.6 265.6 245.0 111.0

59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 453.9 450.0 100.9

X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT

'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 56996 TIOGA 4 138 0.9499 0.9507 57977 CRAIG 7 345 0.9388 0.9604

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 57982 [IATAN 7345.00] TO BUS 56772 [STRANGR7345.00] CKT 1 ------CONTINGENCY SINGLE 196

57982*IATAN 7 345 58160 IATAN 5 161 11 362.6 621.8 605.0 102.8

57982*IATAN 7 345 59199 ST JOE 3 345 1 683.3 1003.9 956.0 104.0

58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 406.2 335.0 123.4

59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 451.8 450.0 100.4

PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30

2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 5

WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B

ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B

ACCC VOLTAGE REPORT

DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx

SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB

MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon

CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con

X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X

X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT

OPEN LINE FROM BUS 57982 [IATAN 7345.00] TO BUS 59199 [ST JOE 3345.00] CKT 1 ------CONTINGENCY SINGLE 197

56920*TECHILL5 161 WND 1 1 58.0 81.2 69.0 117.6

57152 CIRCLVL3 115 57165*HTI JCT3 115 1 81.5 104.1 97.0 106.2