PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30
2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 1
WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B
ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B
ACCC VOLTAGE REPORT
DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx
SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB
MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon
CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
BASE CASE ------BASE CASE
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.7 97.0 110.7
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 347.8 335.0 104.7
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 57951 [HAW G5 122.000] TO BUS 57973 [HAWTHRN5161.00] CKT 1 ------CONTINGENCY SINGLE 1
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 110.9 97.0 115.9
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 370.6 335.0 113.0
59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 453.9 450.0 100.9
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 57953 [MONTG2 122.000] TO BUS 57995 [MONTROS5161.00] CKT 1 ------CONTINGENCY SINGLE 3
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 107.7 97.0 111.9
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 350.5 335.0 105.6
57995 MONTROS5 161 57952*MONTG1 122.0 1 189.5 197.2 195.0 101.2
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 57954 [MONTG3 118.000] TO BUS 57995 [MONTROS5161.00] CKT 1 ------CONTINGENCY SINGLE 4
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 107.8 97.0 112.0
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 350.7 335.0 105.6
57995 MONTROS5 161 57952*MONTG1 122.0 1 189.5 196.8 195.0 100.9
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 57962 [IAT G2 125.000] TO BUS 57982 [IATAN 7345.00] CKT 1 ------CONTINGENCY SINGLE 12
56765*HOYT 7 345 56766 JEC N 7 345 1 987.5 1077.7 1076.0 100.5
PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30
2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 2
WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B
ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B
ACCC VOLTAGE REPORT
DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx
SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB
MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon
CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 57968 [STILWEL7345.00] TO BUS 57981 [LACYGNE7345.00] CKT 1 ------CONTINGENCY SINGLE 24
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 111.3 97.0 116.2
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 360.3 335.0 109.1
59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 453.9 450.0 100.9
96751 2REEDS 69.0 52690*CARTHG 269.0 1 34.7 36.7 36.0 100.6
X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT
'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 56996 TIOGA 4 138 0.9489 0.9507
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 58033 [BRKRIDG5161.00] TO BUS 58047 [OVERLPK5161.00] CKT 1 ------CONTINGENCY SINGLE 111
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.5 97.0 110.6
58036 OLATHE 5 161 58045*SWITZER5 161 1 213.0 372.2 335.0 115.1
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 346.4 335.0 104.2
X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT
'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 58033 BRKRIDG5 161 0.9489 0.9821
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 58036 [OLATHE 5161.00] TO BUS 58045 [SWITZER5161.00] CKT 1 ------CONTINGENCY SINGLE 118
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 107.0 97.0 111.2
58033*BRKRIDG5 161 58047 OVERLPK5 161 1 156.1 370.6 335.0 114.2
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 349.9 335.0 105.4
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 58042 [SPRGHL 5161.00] TO BUS 58126 [LACKMAN5161.00] CKT 1 ------CONTINGENCY SINGLE 125
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 125.1 97.0 131.3
57235*CAPTAIN3 115 57278 WAVERLY3 115 1 94.6 116.8 118.0 102.3
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 345.7 335.0 104.2
X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT
'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 57254 MOONLIT3 115 0.9410 0.9744 57255 MOONLTJ3 115 0.9428 0.9762
57262 160TH 3 115 0.9347 0.9823 57265 SOUTHTN3 115 0.9377 0.9799
57267 SPRINGH3 115 0.9289 0.9889 57273 TIMBRLN3 115 0.9447 0.9798
58042 SPRGHL 5 161 0.9289 1.0044
PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30
2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 3
WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B
ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B
ACCC VOLTAGE REPORT
DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx
SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB
MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon
CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 58059 [MALTABN5161.00] TO BUS 58063 [SWAVRLY5161.00] CKT 1 ------CONTINGENCY SINGLE 137
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.8 97.0 110.9
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 348.2 335.0 104.9
59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 450.2 450.0 100.1
59242*CLINTON5 161 96071 5CLINTN 161 1 98.2 105.4 100.0 105.6
X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT
'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 58063 SWAVRLY5 161 0.6676 0.9600
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 58059 [MALTABN5161.00] TO BUS 58064 [NORTON-5161.00] CKT 1 ------CONTINGENCY SINGLE 138
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.8 97.0 110.9
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 348.2 335.0 104.9
59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 450.2 450.0 100.1
59242 CLINTON5 161 96071*5CLINTN 161 1 98.2 104.5 100.0 104.8
X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT
'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 58059 MALTABN5 161 0.6799 0.9621 58063 SWAVRLY5 161 0.6799 0.9600
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 58062 [SALSBRY5161.00] TO BUS 58064 [NORTON-5161.00] CKT 1 ------CONTINGENCY SINGLE 141
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 107.2 97.0 111.4
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 349.0 335.0 105.2
59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 451.9 450.0 100.4
59242*CLINTON5 161 96071 5CLINTN 161 1 98.2 105.7 100.0 107.3
X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT
'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 58059 MALTABN5 161 0.8498 0.9621 58063 SWAVRLY5 161 0.8486 0.9600
58064 NORTON-5 161 0.8517 0.9658 58070 WEST---5 161 0.8484 0.9629
58071 S EAST 5 161 0.8492 0.9636 58072 MRSHLJT5 161 0.8504 0.9646
58073 MIAMI 5 161 0.8480 0.9626
PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30
2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 4
WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B
ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B
ACCC VOLTAGE REPORT
DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx
SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB
MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon
CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 58094 [SWAVRLY269.000] TO BUS 58101 [DOVERPT269.000] CKT 1 ------CONTINGENCY SINGLE 170
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 106.7 97.0 110.8
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 347.9 335.0 104.7
59242*CLINTON5 161 96071 5CLINTN 161 1 98.2 100.9 100.0 101.0
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 57977 [CRAIG 7345.00] TO BUS 56772 [STRANGR7345.00] CKT 1 ------CONTINGENCY SINGLE 193
57180 TEC E 3 115 57182*TECHILE3 115 1 230.4 258.5 236.0 108.8
57233*166TH 3 115 57243 JAGGARD3 115 1 106.7 164.0 97.0 170.4
57235*CAPTAIN3 115 57278 WAVERLY3 115 1 94.6 116.9 118.0 101.3
57243*JAGGARD3 115 57261 PENTAGN3 115 1 64.2 119.3 92.0 132.4
57982*IATAN 7 345 59199 ST JOE 3 345 1 683.3 991.7 956.0 103.1
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 466.7 335.0 142.7
59203 NASHUA 5 161 59204*SMTHVL 5 161 1 155.9 240.3 245.0 101.1
59204 SMTHVL 5 161 59221*PLTCTY 5 161 1 180.6 265.6 245.0 111.0
59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 453.9 450.0 100.9
X------BUS -----X V-CONT V-INIT X------BUS -----X V-CONT V-INIT
'KCPLHV ' BUSES WITH VOLTAGE LESS THAN 0.9500: 56996 TIOGA 4 138 0.9499 0.9507 57977 CRAIG 7 345 0.9388 0.9604
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 57982 [IATAN 7345.00] TO BUS 56772 [STRANGR7345.00] CKT 1 ------CONTINGENCY SINGLE 196
57982*IATAN 7 345 58160 IATAN 5 161 11 362.6 621.8 605.0 102.8
57982*IATAN 7 345 59199 ST JOE 3 345 1 683.3 1003.9 956.0 104.0
58160 IATAN 5 161 59221*PLTCTY 5 161 1 347.8 406.2 335.0 123.4
59202 SIBLEY 5 161 59151*SIBLEY#322.0 1 446.5 451.8 450.0 100.4
PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E WED, MAY 18 2005 7:30
2005 SPP UPDATE 2 REDUCE MODEL(3-14-05)2015 SP SPP-2004-BC 1 PAGE 5
WITH KCPL FIXES + IATAN 2 900MW + IATAN 345/161 TX I2B
ACCC OVERLOAD REPORT: MONITORED ELEMENTS LOADED ABOVE 100.0 % OF RATING SET B
ACCC VOLTAGE REPORT
DISTRIBUTION FACTOR FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Base Case Fixed + I2 +I2B.dfx
SUBSYSTEM DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\subsystem.SUB
MONITORED ELEMENT FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\MonElements.mon
CONTINGENCY DESCRIPTION FILE: E:\TS_Shared\TRANPLAN\Iatan 2\I2B Plan\2015\Contingencies.con
X------C O N T I N G E N C Y E V E N T S ------X X-- O V E R L O A D E D L I N E S --X X--MVA(MW)FLOW--X
X---- MULTI-SECTION LINE GROUPINGS ----X FROM NAME TO NAME CKT PRE-CNT POST-CNT RATING PERCENT
OPEN LINE FROM BUS 57982 [IATAN 7345.00] TO BUS 59199 [ST JOE 3345.00] CKT 1 ------CONTINGENCY SINGLE 197
56920*TECHILL5 161 WND 1 1 58.0 81.2 69.0 117.6
57152 CIRCLVL3 115 57165*HTI JCT3 115 1 81.5 104.1 97.0 106.2