PART 1 GENERAL

1.1SECTION INCLUDES

  1. Overhead coiling insulated fire doors.

1.2RELATED SECTIONS

** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.

  1. Section 05500 - Metal Fabrications: Support framing and framed opening.
  1. Section 06200 - Finish Carpentry: Wood jamb and head trim.
  1. Section 08710 - Door Hardware: Product Requirements for cylinder core and keys.
  1. Section 09900 - Painting: Field applied finish.
  1. Section 16130 - Raceway and Boxes: Conduit from electric circuit to door operator and from door operator to control station.
  1. Section 16150 - Wiring Connections: Power to disconnect.

1.3REFERENCES

** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.

  1. ASTM A 653 - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
  1. ASTM A 666 - Standard Specification for Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar.
  1. ASTM A 924 - Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process.
  1. ASTM B 221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes.
  1. ASTM B 221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric).
  1. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum).
  1. NEMA MG 1 - Motors and Generators.
  1. NFPA-80 – Standard for Fire Doors and Fire Windows.

1.4DESIGN / PERFORMANCE REQUIREMENTS

  1. Fire Rated Assemblies: Provide assemblies complying with NFPA 80 and listed in UL Directory or Intertek Testing Services (Warnock Hersey Listed) Directory.

** NOTE TO SPECIFIER ** Select the following paragraph for use with Series 635 doors. Delete if not required.

  1. Oversize Door Certification: Provide UL oversize label for oversize door assemblies exceeding 152 square feet (14.12 square m) or 13 feet 6 inches (4.11 m) in any dimension.

1.5SUBMITTALS

  1. Submit under provisions of Section 01300.
  1. Product Data: Manufacturer's data sheets on each product to be used, including:
  2. Preparation instructions and recommendations.
  3. Storage and handling requirements and recommendations.
  4. Details of construction and fabrication.
  5. Installation methods.
  1. Shop Drawings: Include detailed plans and elevations, details of framing members, anchoring methods, clearances, hardware, and accessories. Include relationship with adjacent construction.

** NOTE TO SPECIFIER ** Delete selection samples if colors have already been selected.

  1. Selection Samples: For each finish product specified, two complete sets of color chips representing manufacturer's full range of available colors and patterns.
  1. Verification Samples: For each finish product specified, two samples, minimum size 6 inches (150 mm) square, representing actual product, color, and patterns.
  1. Manufacturer's Certificates: Certify products meet or exceed specified requirements.
  1. Operation and Maintenance Data: Submit lubrication requirements and frequency, and periodic adjustments required.

1.6QUALITY ASSURANCE

  1. Manufacturer Qualifications:Company specializing in performing Work of this sectionwith a minimum of five yearsexperience in the fabrication and installation of security closures.
  1. Installer Qualifications:Installer Qualifications:Company specializing in performing Work of this section with minimum three years and approved by manufacturer.

** NOTE TO SPECIFIER ** Include a mock-up if the project size and/or quality warrant taking such a precaution. The following is one example of how a mock-up on a large project might be specified. When deciding on the extent of the mock-up, consider all the major different types of work on the project.

  1. Mock-Up: Provide a mock-up for evaluation of surface preparation techniques and application workmanship.
  2. Finish areas designated by Architect.
  3. Do not proceed with remaining work until workmanship, color, and sheen are approved by Architect.
  4. Refinish mock-up area as required to produce acceptable work.

1.7DELIVERY, STORAGE, AND HANDLING

  1. Store products in manufacturer's unopened packaging until ready for installation.
  1. Protect materials from exposure to moisture. Do not deliver until after wet work is complete and dry.
  1. Store materials in a dry, warm, ventilated weathertight location.

1.8PROJECT CONDITIONS

  1. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

1.9COORDINATION

  1. Coordinate Work with other operations and installation of adjacent materials to avoid damage to installed materials.

PART 2 PRODUCTS

2.1MANUFACTURERS

  1. Acceptable Manufacturer: Overhead Door Corp., 2501 S. State Hwy. 121, Suite 200, Lewisville, TX 75067. ASD. Tel. Toll Free: (800) 275-3290. Phone: (469) 549-7100. Fax: (972) 906-1499. Web Site: E-mail: .

** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.

  1. Substitutions: Not permitted.
  1. Requests for substitutions will be considered in accordance with provisions of Section 01600.

2.2OVERHEAD COILING INSULATED FIRE DOORS

  1. Overhead Coiling Fire service Doors: Overhead Door Corporation Series 635 Insulated Fire Doors.
  2. Label: Provide fire doors certified with the following listing.

** NOTE TO SPECIFIER ** Select one or more of the following paragraphs for the door size(s) required and delete the ones not required. Note that UL Labels are standard and FM labels are optional.

  1. Rolling fire doors for masonry/steel construction up to 152 sf (14.12 sm) and 13 feet 6 inch (4.12 m) in width or height shall be labeled:

** NOTE TO SPECIFIER ** Select one of the following paragraphs to suit the projects requirements and delete the ones not required. Note that UL Labels are standard and FM labels are optional.

1)UL 4-Hour Class A Label for non-masonry fire walls.

2)UL 3-Hour Class A Label for non-masonry fire walls.

3)FM 3-Hour Class A Label for non-masonry fire walls.

4)ULC 3-Hour Label for non-masonry fire walls.

5)UL 1-1/2 Hour Class B Label for non-masonry fire walls.

6)FM 1-1/2 Hour Class B Label for non-masonry fire walls.

** NOTE TO SPECIFIER ** Select the following paragraphs for UL Label and delete if not applicable.

  1. Rolling fire doors over 152 sf (14.12 sm) shall receive the UL Oversize Fire Door Label.

** NOTE TO SPECIFIER ** Select the following paragraphs for optional FM Label and delete if not applicable.

  1. Rolling fire doors over 152 sf (14.12 sm) and not exceeding 18 feet (5.49 sm) in height or width shall receive the Factory Mutual Label for Oversize Fire Doors. Doors over 18 ft (5.49 m) must be reviewed by FM.

** NOTE TO SPECIFIER ** Select the following paragraphs as required and delete if not required.

  1. If UL labeled smoke protection is required, then provide doors with Underwriters' Laboratories, Inc. label for "Leakage Rated Assembly" or "S" label.

1)Comply with NFPA 105 air leakage requirements.

2)Pass UL test procedure 1784.

  1. Curtain: Interlocking roll-formed slats. Windlocks shall be attached to each end of alternate slats to prevent lateral movement.
  2. Flat profile type F-265 with back cover and mineral wool filling internal space. For doors over 24 feet (4.27 m) thru 24 feet (6.10 m) wide, fabricated of:

** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.

1)24 gauge galvanized steel.

2)22 gauge galvanized steel.

  1. R-Value: 4.5.
  2. STC (Sound Transmission Class).

1)Door Assembly17

2)Door Assembly with brush seals18

3)Curtain Only23

  1. Finish:

** NOTE TO SPECIFIER ** Select the following paragraphs for the slat and hood materials required and delete the ones not required.

  1. Galvanized Steel: Slats and hood shall be galvanized steel in accordance with ASTM A 653 and finished with a rust-inhibitive, roll coating process, including bonderizing, a 0.2 mils thick baked-on prime paint, and a 0.6 mils thick baked-on polyester (powder coated) top coat. Top coat color shall be:

** NOTE TO SPECIFIER ** Select one of the following paragraphs and delete the ones not required.

1)Gray polyester top coat.

2)Tan polyester top coat.

3)White polyester top coat.

4)Brown polyester top coat.

5)Powder coating finish in color as selected by Architect from manufacturer’s standard colors.

  1. Non-galvanized exposed ferrous surfaces shall receive one coat of rust-inhibitive primer.
  1. Bottom Bar: Two structural steel angles 1-1/2 inch by 1-1/2 inch by 1/8 inch (38 mm by 38 mm by 3 mm) minimum.

** NOTE TO SPECIFIER ** Select one of the following optional paragraphs and delete the ones not required.

  1. Provide sloping bottom bar within UL limits.
  2. Provide insulated bottom bar.
  1. Guides: Three structural steel angles with minimum thickness of 1/4 inch (6 mm) mounted to the face of the jamb. Guides also include locking bar or wind bar.

** NOTE TO SPECIFIER ** Select one of the following fastening paragraphs to meet projects installation requirements and delete the one not required.

  1. Fasten to Masonry Fire Walls with UL listed expansion anchors, or welded to steel jambs in accordance with fire door manufacturer’s instructions, or by bolts on steel jambs, or by thru-bolts on hollow masonry or soft brick wall.
  2. Fasten Guides to Non-Masonry Fire Walls as recommended by the manufacturer.
  1. Brackets:

** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.

  1. Hot rolled prime painted steel to support counterbalance, curtain and hood.
  2. Galvanized steel to support counterbalance, curtain and hood.
  1. Counterbalance: Helical torsion spring type housed in a steel tube or pipe barrel, supporting the curtain with deflection limited to 0.03 inch per foot of span. Counterbalance shall be adjustable by means of an adjusting tension wheel.
  2. Hood:

** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required. Add the last paragraph for optional FM labeled hoods only.

  1. Fabricate of 24 gauge galvanized primed steel minimum for wall openings thru 19 feet (5.79 m) wide.
  2. Fabricate of 22 gauge galvanized primed steel for wall openings over 19 feet (5.79 m) wide.
  3. Hood equipped with thermally controlled, internal, galvanized steel flame baffle as required for FM listing.

** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.

  1. Provide one intermediate support bracket for wall openings over 13 feet 6 inch (4.15 m) wide
  2. Provide two support brackets for wall openings over 19 feet (5.79 m) wide.

** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required.

  1. Manual Operation:

** NOTE TO SPECIFIER ** Select one of the following manual operation paragraphs and delete the ones not required.

  1. Chain hoist.
  2. Crank operation.

** NOTE TO SPECIFIER ** Include the following paragraph if electric motor operation is required and delete if not required.

  1. Electric Motor Operation: Provide UL listed electric operator, size as recommended by manufacturer to move door in either direction.
  2. Sensing Edge Protection:

** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.

1)Pneumatic sensing edge.

2)Electric sensing edge.

  1. Operator Controls:

** NOTE TO SPECIFIER ** Select one of the following operation paragraphs and delete the one not required.

1)Push-button operated control stations with open, close, and stop buttons.

2)Key operation with open, close, and stop controls.

3)Push-button and key operated control stations with open, close, and stop buttons.

** NOTE TO SPECIFIER ** Select one of the following location paragraphs and delete the one not required.

4)Controls for interior location.

5)Controls for exterior location.

6)Controls for both interior and exterior location.

** NOTE TO SPECIFIER ** Select one of the following two paragraphs and delete the one not required.

7)Controls surface mounted.

8)Controls flush mounted.

  1. Special Operation:

** NOTE TO SPECIFIER ** Select one of the following operation paragraphs and delete the one not required.

1)Vehicle detector operation.

2)Radio control operation.

3)Card reader control.

4)Photocell operation.

5)Door timer operation.

6)Commercial light package.

7)Explosion and dust ignition proof control wiring.

** NOTE TO SPECIFIER ** Select one of the following paragraphs for manual operation or electric motor operation and delete the one not required.

  1. Automatic Closure Standard Fire Door: UL approved release mechanism equipped with a 165 degree fusible link.
  2. Doors will be equipped with FireKing release mechanism, requiring only one sash chain to be routed to the operated side (sash chain not required to be routed to adjusting wheel side.)

1)The release mechanism shall include the FireKing planetary gear differential system.

2)The door will close by a thermally actuated link rated @165°F, or by an optional listed releasing device, or by manually activating the release handle.

3)All counterbalance spring tension shall be maintained when the release mechanism is activated.

4)After closing by manual activation of the release handle, the door shall be able to be reset by one person from one side of the door (re-engaging the release handle). No tools shall be required to reset the FireKing release mechanism.

5)Motor operator limits shall remain synchronized during normal operation and during drop testing.

  1. Fire Sentinel time-delay release mechanism provides an added measure of safety to control the doors' closure.

** NOTE TO SPECIFIER ** Select one of the following paragraphs for Fire Sentinel models and delete the ones not required.

1)Model FSXP:

(a)Voltage input 24 VDC only,

(b)Voltage output 24 VDC,

(c)Must be powered by a building alarm system with a backup power source.

(d)Release time delay: Factory set at 10 seconds. Can be field adjusted by dipswitch settings to 20, 30 and 60 seconds,

(e)Can use normally open proximity switch to detect door is closed will not release on alarm, will release during power outage.

(f)Unit can support 2 or 4 wire smoke detector system (maximum of 4 Class B Style A detectors. Release devices are normally open contacts. Provided with 4 wire detectors when detectors are specified with an end of line relay.

(g)Load Rating: Support and Release 40 lbs. maximum.

(h)Box dimension: 9.7 inches high by 7.5 inches wide by 5 inches deep.

2)Model FSXPBB

(a)Voltage is universal: 24 VDC, 24 VAC and 120 VAC

(b)Voltage output 24 VDC

(c)Release time delay: Factory set at 10 seconds can be field adjusted by dipswitch settings to 20, 30 and 60 seconds.

(d)Can use normally open proximity switch to detect door is closed or normally open down operator down limit switch.

(e)Can support 2 or 4 wire smoke detector system (maximum of 4 Class B Style A detectors. Release devices are normally open contacts. Provided with 4 wire detectors when detectors are specified with an end of line relay.

(f)Unit has one 12 VDC battery but as noted above 24 VDC output.

(g)Power Loss Time delay: 72 hours.

(h)Unit can power an optional ADA horn / strobe 24 VDC.

(i)Load Rating: Support and Release 40 lbs. maximum.

(j)When used with and electric operator, the operator must be modified to accept wiring from Fire Sentinel.

(k)Box dimension: 9.7 inches high by 7.5 inches wide by 5 inches deep.

3)Model FSXPBBVB

(a)Voltage is universal: 24 VDC, 24 VAC and 120 VAC

(b)Voltage output 24 VDC

(c)Release time delay: Factory set at 10 seconds can be field adjusted by dipswitch settings to 20, 30 and 60 seconds.

(d)Can use normally open proximity switch to detect door is closed or normally open down operator down limit switch.

(e)Can support 2 or 4 wire smoke detector system (maximum of 4 Class B Style A detectors. Release devices are normally open contacts. Provided with 4 wire detectors when detectors are specified with an end of line relay.

(f)Unit has one 12 VDC battery but as noted above 24 VDC output.

(g)Power Loss Time delay: 72 hours.

(h)Unit can power an optional ADA horn / strobe 24 VDC.

(i)Load Rating: Support and Release 40 lbs. maximum.

(j)When used with and electric operator, the operator must be modified to accept wiring from Fire Sentinel.

(k)Provide with a Voice Board.

(l)Power Loss Time delay: 24 hours with addition of a Voice Board.

(m)Voice Board is a factory installed.

(n)9.7 inches high by 7.5 inches wide by 5 inches deep.

4)Model FSAFCB: For use with electric operator.

(a)Voltage input 120 VAC only

(b)Voltage output is 24 VDC

(c)Release time delay: Factory set at 10 seconds can be field adjusted by dipswitch settings to 20, 30 and 60 seconds.

(d)The unit can support 2 or 4 wire smoke detector system (maximum of 4 Class B Style A detectors. Release devices are normally open contacts.

(e)Unit has two 12 VDC batteries wired in series for 24 VDC output.

(f)Requires the use of an electric safety edge on the bottom bar.

(g)Unit is wired into electric operator to drive door close on alarm. If the electric edge is activated by an obstruction in the opening unit will open the door and reinitiate closing for three cycles. If obstruction is not removed by the fourth cycle unit will stop door on the obstruction and remain at that point until obstruction is remove then will activate operator to close door. Or by adjusting the dipswitches the unit can be set to release the door from the operator for a governor controlled door closing.

(h)Unit is supplied with a combination ADA horn / strobe combination and a test keyswitch. Keyswitch allows the unit to be tested without the activation of the alarm system or smoke detector.

** NOTE TO SPECIFIER ** Select the following optional paragraph if required. Delete if not required.

(i)Central Fire Alarm: Electric Release Mechanism operated from fire alarm system.

(j)Electric operator is modified to accept Fire Sentinel.

(k)Load Rating: Support and Release 40 lbs. maximum.

(l)Power Loss Time delay: 48 hours

(m)Box dimension: 10 inches high by 10 inches wide by 5 inches high.

5)Model FSAFCBVB: For use with electric operator.

(a)Voltage input 120 VAC only

(b)Voltage output is 24 VDC

(c)Release time delay: Factory set at 10 seconds can be field adjusted by dipswitch settings to 20, 30 and 60 seconds.

(d)The unit can support 2 or 4 wire smoke detector system (maximum of 4 Class B Style A detectors. Release devices are normally open contacts.

(e)Unit has two 12 VDC batteries wired in series for 24 VDC output.