FITTING INSTRUCTIONS

For

HONEYWELL FAN/LIMIT STAT

CONTROL PANEL

To

POWRMATIC OUH HEATER


Identifying Your Heater

The model of your heater can be identified on the data plate attached to one of the heater panels.

The serial number will identify the age using the chart below.

1)The serial number has 2 Middle Letters (i.e. H20GE002)

1st Middle Letter = Year2nd Middle Letter = Month

1984 - Z1995 - LJanuary - M Example: Serial No. H20GE002

1985 - Y1996 - KFebruary - L

1986 - X1997 - JMarch - K The two middle letters are G & E

1987 - W1998 - HApril - J

1988 - V1999 - GMay - H This would make the date of

1989 - T2000 - FJune - G manufacture AUGUST 1999

1990 - S2001 - EJuly - F

1991 - R2002 - DAugust - E

1992 - P2003 - CSeptember - D

1993 - N2004 - BOctober - C

1994 – M2005 - ANovember - B

December - A

2)The serial number has 2 numbers and a Middle Letter (i.e. H2014E002)

2 Numbers = YearMiddle Letter = Month

06 - 2006January - A Example: Serial No. H2014E002

07 - 2007February - B

08 - 2008March - C The Middle figures are 14 & E

09 - 2009April - D

10 - 2010May - E This would make the date of

11 - 2011June - F manufacture MAY 2014

12 - 2012July - G

Etc..August - H

September - I

October - J

November - K

December - L

Fitting Instructions

WARNING

Isolate the electrical supply to the Heater AND any Controls that may be wired to the heater.

1) Remove and discard the cable between the Honeywell stat and the control panel.

2)Remove and discard the cable between the burner and the control panel.

3)Remove and discard the cable between the main fan and the control panel.

4)Remove any control cables and power cables from the control panel.

5)The control panel can now be removed from the heater and discarded.

6)Fit the new control panel onto the same panel that the burner and the Honeywell stat are fitted to, position it in the opposite corner to the Honeywell stat. Drill 4 x 3mm holes for each corner, do this by using the template provided.

7)Fit the control panel using the screws and spacers provided.

8)Remove the old Honeywell stat and replace with the new. If the original stat is not a Honeywell then refer to the Stat Position diagram and drill a 28mm hole in the correct location.

9)Using the new cable and the P clips provided wire the Burner, Main Fan

New Honeywell stat and any Power/Control Cables into the control panel,

please use the diagrams provided on the last page for connections.

Note: Follow the wiring diagram for your type of heater.

COMPONENTS INCLUDED IN YOUR KIT

  • 1 No. New Honeywell Fan/Limit Stat- 143000306
  • 1 No. OUH Control Panel- Model Specific
  • 3m 3 Core 1.5mm2 Cable- 175210431
  • 6m 5 Core 1.0mm2 Cable- 140700526
  • 2m 2 Core 0.75mm2 Cable- VN0911280
  • 10 No. 6.3mm Push On Crimps- 180174146
  • 10 No. Butt Splice- 142400310
  • 7 No. M20 Glands- 147002095
  • 15 No. Plastic P Clips- 141816421
  • 4 No. Spacers- 180010202
  • 4 No. Fixing Screws- 180000915
  • 4 No. Washer M5- 180008705

PLEASE FOLLOW THE STEPS ON THE FOLLOWING PAGES FOR THE

FITTING OF THE ABOVE COMPONENTS.

Final Steps

  1. Make sure you have followed the wiring diagram and double check all connections.
  1. Pull the white button on the Honeywell fan/limit stat outward so the Fan circuit is in the Automatic mode.
  1. Check that the brass link between the lower fan and limit connections of the Honeywell fan/limit stat has been removed.
  1. Re-apply the power.
  1. Initially the high limit interlock relay will need to be reset as indicated by the indicator on the new button that was installed. Please note that every time power is lost to the unit the high limit interlock relay will need to be reset.
  1. Set the temperature pins on the Honeywell fan/limit stat to 86°, 122° & 194° respectively. Note these are in Fahrenheit not Centigrade. The equivalent values are 30°C, 50°C & 90°C.
  1. Start the heater and make sure the main fan starts when the middle pin (set to 122) passes the temperature indicating arrow. Carefully rotate the centre dial of the Honeywell stat until the high limit pin (set at 194°) passes the temperature indicating arrow, this should stop the burner and illuminate the limit reset button. Release the centre dial and wait for the unit to cool, the main fan will stop when the temperature falls below the first pin (set to 86°).
  1. Push the limit reset button to reset the interlock relay. The heater can now be left to operate normally.